W415-1294 / 01.24.14
13
EN
Use the periscope kit to locate the air termination above grade. The periscope must be installed so that
when
fi
nal grading is completed, the bottom air slot is located a minimum 12” (304.8mm) above grade. The
maximum allowable vent length is 10’ (3.1m) for a
fi
replace and 8’ (2.4m) for a stove.
9.4A
24” (610mm)
MAXIMUM
0” (0mm) RISE
CORNER INSTALLATION
3.3 SPECIAL VENT INSTALLATIONS
29" (737mm)
MIN
12" (305mm)
MIN. TO
GRADE
The maximum vent length for a corner installation is 24" (610mm).
24" (610mm)
MIN
30 1/2" (774mm)
3.3.1 PERISCOPE TERMINATION
3.3.2 CORNER TERMINATION
12" (305mm)
MIN. TO
GRADE