32
W415-1443 / C / 06.06.16
EN
37 1/2"
953mm
49 1/8"
1248mm
31 7/8"
810mm
Minimum clearance to combustible construction from appliance and vent surfaces:
Combustible
Framing:
-
0" to stand-offs
-
1" (25mm) to bottom and sides of the vent pipe*
-
3" (76mm) to top of the vent pipe*
Combustible Finishing:
-
0" to rear stand offs
-
4 1/2"(114mm) to front face top and 3"(76mm) to sides
-
53" (1346mm) to combustible enclosure top from base of the appliance
-
53" (1346mm) to ceiling from base of the appliance
* CBL36 HORIZONTAL VENT SECTIONS:
A minimum of 1" (25mm) at the bottom and sides and 3" (76mm)
at the top of the vent pipe on all horizontal runs to combustibles is required. Use fi restop spacer W010-1800
(supplied).
NOTE: The minimum clearances from the top of the horizontal vent pipe to combustible materials may
be reduced from 3" (76mm) to 1" (25mm) in those installations with a minimum 38" (965mm) vertical
vent rise made immediately off the fi replace collar.
* CBL36 VERTICAL VENT SECTIONS:
A minimum of 1" (25mm) all around the vent pipe on all vertical runs
to combustibles is required except for clearances in appliance enclosures. See "MINIMUM ENCLOSURE
CLEARANCES" section. Use fi restop spacer W500-0096 (not supplied).
INSIDE
CHASE
OUTSIDE
CHASE
SIDE
WALL
16 3/4"
425mm
2" 51mm
371/2" 953mm
37 1/2" 953mm
16 3/4"
425mm
5.2
NAILING TAB INSTALLATION
2
3
4
1
USE A SELF TAPPING SCREW TO SECURE SHORT SIDE OF NAILING BRACKET TO APPLIANCE. REPEAT FOR STEPS 2,3 AND 4.
NOTE: ADJUST BRACKET TO SUIT YOUR DESIRED FINISHING MATERIAL.