W415-1769 / B / 08.27.18
EN
26
rough framing
3.2 minimum enclosure clearances
3" [76mm]
COMBUSTIBLE
NON-COMBUSTIBLE
BRICK 0” (0MM) IF
NON-COMBUSTIBLE
FINISHING IS USED
SUCH AS BRICK
AND STONE.
3" [76mm]
MINIMUM *
3" [76mm]
2"
[51mm]
1"
[25mm]
1"
[25mm]
50 1/2"
[1283mm]
54"
[1372mm]
CEILING
(MIN)
14 1/2"
[368mm]
42 5/8"
[1083mm]
MINIMUM
PLUS RISE*
15 5/8"
[403mm]
TOP EXIT ENCLOSURE
The appliance requires a minimum non-combustible enclosure height of 50 1/2" (1283mm). For temperature
requirements, the enclosure space around and above the appliance must be left unobstructed.
NOTE: The vent shield is telescopic and must be adjusted to shield the full depth of combustible wall
penetration.
* See "MINIMUM FRAMING DIMENSION" section for details on reducing vent pipe top clearances.
These parameters also apply to the illustrations found in the "MINIMUM ENCLOSURE CLEARANCES"
section.
TOP VENT