25
W415-0812 / D / 08.16.12
7.0 FRAMING
Minimum clearance to combustible construction from appliance and vent surfaces:
Sides, back, bottom, and top
0"
Vent pipe side, bottom and top*
2"
Recessed depth (corner installation)
25¼"
Ceiling
54" from bottom of appliance.
Enclosure
38" from bottom of appliance.
* HORIZONTAL VENT SECTIONS:
A minimum clearance of 1" at the bottom and sides and 2" at the top of the
vent pipe on all horizontal runs to combustibles is required. Use
fi
restop spacer W010-2116 (supplied).
* VERTICAL VENT SECTIONS:
A minimum clearance of 1" all around the vent pipe on all vertical runs to
combustibles is required except for clearances in appliance enclosures. Use
fi
restop spacer W500-0367 (not
supplied).
Horizontal Vent Off Appliance
Vertical Vent Off Appliance
A
= 43" using
fl
exible vent components.
B
= 45" using
fl
exible vent components.
7.1 MINIMUM CLEARANCE TO COMBUSTIBLES
7.2 MINIMUM CLEARANCE TO COMBUSTIBLE ENCLOSURES
Содержание BCDV40-N
Страница 51: ...51 W415 0812 D 08 16 12 17 0 SERVICE HISTORY 43 1...
Страница 52: ...52 W415 0812 D 08 16 12...