W415-2369 / C / 12.09.20
EN
26
rough framing
3.2 minimum enclosure clearances
TOP VENT
3" [76mm]
COMBUSTIBLE
NON-COMBUSTIBLE
BRICK 0” (0MM) IF
NON-COMBUSTIBLE
FINISHING IS USED
SUCH AS BRICK
AND STONE.
3" [76mm]
MINIMUM *
3" [76mm]
1 1/2"
[38 mm]
1"
[25mm]
50 1/2"
[1283mm]
54"
[137.2cm]
CEILING
(MIN)
42 5/8"
[108.3cm]
MINIMUM
PLUS RISE*
1"
[25mm]
15 7/8”
[40.3cm]
FIRESTOP
50 1/2”
[128.3cm]
TOP EXIT ENCLOSURE
The appliance requires a minimum enclosure height of 50 1/2" (128.3cm). For temperature requirements, the
enclosure space around and above the appliance must be left unobstructed.
* See "minimum framing dimensions" section for details on reducing vent pipe top clearances.
These parameters also apply to the illustrations found in the "minimum enclosure clearances" section.
34 5/8"
[87.9cm]
The vent shield must extend the full depth of the combustible wall. It can be cut to suit depths less than 8 1/2"
(216mm).
note: