FOR ACCELATERM INSTALLATIONS 

 

The CICP18ACCNETBD Ethernet board is mounted in the Ac-
celaterm Interface board (see the Accelaterm installation instruc-
tions WI1989 for more information regarding the Interface board 
installation).   

 

Prior to opening the Ethernet board package or 
touching anything inside the control panel enclosure, 
discharge any static electricity from your body or 
clothing.  Use a grounded wrist strap or touch an 
unpainted, grounded metal object such as the metal 
frame of the panel enclosure. 

 
 

INSTALLATION 

 

1

.   Find the MAC address located on 

the white label wrapped around the 
Ethernet plug (circled in Fig. 10 at 
right).  Write the MAC address here:  
_______________________ and 
keep this paper in a safe location for 
future reference. 

 

 

2

.   Before installation, verify that the Accelaterm control panel is 

working correctly.   

 

3

.   Disconnect power to the system, including the battery wires.   

 

4

.    

Align the board:

  The Ethernet board is mounted in the top 

right corner of the Accelaterm Interface board.  See Fig. 11.  
Carefully align the two Ethernet board snap-lock standoffs 
with the two Interface PC board mounting holes.  Then align 
the Ethernet board plug with the Interface board receptacle 
"JP2" as shown below.   

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
      

Insert the board:

  With both standoffs and the plug aligned, 

firmly press the Ethernet board into the Accelaterm Interface 
board by holding the Interface board with the tips of your fin-
gers and squeezing the Ethernet board as shown Fig. 12. 

 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

5

.  Insert your CAT5/6 Ethernet cable first 

through a cable clamp (Fig. 13) and then 
through a knockout located on the right 
side of the panel enclosure.  Pull only 
enough of the Ethernet cable into the en-
closure to allow the plug to be easily in-
serted into the Ethernet board receptacle. 

 

6

.  In the parts bag, find the silver braided 

shield.  For FCC compliance, this braided shield must be both 
secured to the cable clamp and placed over the Ethernet cable 
in the interior of the panel enclosure.   

 
     

Note:

  The presence of this silver braided shield makes 

shielded twisted pair (STP) cable unnecessary.  In addition, 
unshielded twisted pair (UTP) cable does not need to be 
routed in conduit. 

 
 

 

 

 

 Before tightening the cable 

clamp, place the braided shield 
over the Ethernet cable.  

Pull the 

braided shield out through the 
panel knockout and into the ca-
ble clamp

.  Thus, the braided 

shield is grounded to the panel 
enclosure by the cable clamp (as 
shown in Fig. 14. 

 
 
 
 
 
 

7

.   The  Ethernet  cable 

must 

be covered by the braided shield but 

leave about one inch of cable exposed near the 
plug.  Note that this one inch of exposed cable 
should be measured with the Ethernet cable 
plugged into the Ethernet board receptacle.  If 
desired, use electrical tape to cover the end of 

the braided shield similar to the image shown in the Fig. 7 
photograph earlier in this manual.  

     

DO NOT cover the plug with the braided shield

.   

 
 

 

Fig. 10:  MAC address location 

Fig. 11:  Align the two snap-lock standoffs and plug with the Ac-
celaterm Interface board holes and receptacle "JP2". 

Two 

standoffs 

Mounting 

holes 

Plug 

Receptacle "JP2" 

Fig. 12:  Squeeze to insert the board 

Squeeze Here 

 

Fig. 13:  Cable 

Clamp 

 

Fig. 14:  PANEL EXTERIOR:  
Both the Ethernet cable and 
the braided shield must be 
grounded to the panel enclo-
sure by the cable clamp. 

 