UM-15094500-AA0
Page 35
Object name
Type &
Instance
Readable/
Writable
Description
Range and Definition
Minimum Cooling
Temperature Setpoint
AV 39
R/W
Minimum Cooling
Temperature Setpoint
°C:0.0 ~50.0
°F: 32.0~122.0
Minimum Heating
Temperature
Setpoint
AV 40
R/W
Minimum Heating
Temperature Setpoint
°C:0.0 ~50.0
°F: 32.0~122.0)
Minimum Fan
Output
AV 41
R/W
Minimum Fan Output at Auto
Fan Mode (for Modulating
Fan Application)
0%~Reg 51
Maximum Fan
Output
AV 42
R/W
Maximum Fan Output at
Auto Fan Mode (for
Modulating Fan Application)
Reg 50~100%
Low Fan Speed
Setting
AV 43
R/W
Low Fan Speed Setting (for
Modulating Fan Application)
0%~Reg 53
Med. Fan Speed
Setting
AV 44
R/W
Med. Fan Speed Setting (for
Modulating Fan
Application)
Reg 52~Reg54
Hi Fan Speed
Setting
AV 45
R/W
Hi Fan Speed Setting(For
Modulating Fan Application)
Reg 53~100%
Minimum Off Time
AV 46
R/W
Minimum Off Time
0~600 seconds
Minimum On Time
AV 47
R/W
Minimum On Time
0~600 seconds
Integral-cycle
Time-2
AV 48
R/W
Integral Time and Output
Cycle Time 2
10~500 sec.
Set Point for
Humidity
AV 49
R/W
Set Point for Humidity
Control
0~1000 (0.0
~
100.0
%RH)
Dew Point Set Point
AV 50
R/W
Dew Point Temperature Set
Point
-999~9999: -99.9
~
999.9
℃
/°F
Occupancy Status
BI 0
R
Status of Occupancy
0: Room Occupied
1: Room Unoccupied
Window-Door Status
BI 1
R
Window/ Door Status
0: Door/Window Closed
1: Door/Window Open
Cooling-heating
Status
BI 2
R
Status of Cooling/Heating
Control
Output
0: Close & Off 1: Open & On
Relay 1 Status
BI 3
R
Status of Relay 1 (O/B
Valve)
0: Off, 1: On
Relay 2 Status
BI 4
R
Status of Relay 2 (Comp 1)
0: Off, 1: On
Relay 3 Status
BI 5
R
Status of Relay 3 (Comp 2)
0: Off, 1: On
Relay 4 Status
BI 6
R
Status of Relay 4 (Heating
Stage 3)
0: Off, 1: On
Relay 5 Status
BI 7
R
Status of Relay 5
0: Off, 1: On
Relay 6 Status
BI 8
R
Status of Relay 6
0: Off, 1: On