UM-15094500-AA0
Page 12
User Mode Thermostat Operation
#
Item
Description
Remarks
1
Normal Display
Display current room or set-point
temperature.
Use the (
SP
) parameter in
the Engineering Menu or
[
MSV6
]
Display
to choose
Current room or Set- point
temperature on display.
2
Temperature
Setpoint Setting
using Up/Down
Arrows
Set the desired temperature.
The [
AV0
] / [
AV3
] Cool / Heat
Occupied and [
AV8
] / [
AV9
]
Unoccupied Cool / Heat
temperature setpoints
BACnet objects can be used
to write or force the setpoint
to a desired value from
BACnet supervisor.
3
Mode Select
Select the working mode: Cooling
( ), Heating (
)
, or
Ventilating (
)
.
After pressing the MODE
button, press the UP/ DOWN
button to rotate the
selections. Dependent on
Control Type.
4
Fan Auto/
Continuous
Change the Fan mode between
Auto or Continuous On.
When AUTO is displayed,
the fan is handled
automatically. When AUTO is
flashing, the fan is working
under a delay timer. When
FAN icon is spinning but
AUTO is not displayed, the
fan will run continuously until
commanded off.
5
Occupancy Setting
Press SET, Used UP and DOWN
arrows to toggle between the
Occupied and Unoccupied
setting. Use MODE or SET
buttons to apply.
The SET button could be
locked for applications
forbidding user occupancy
state control.