Connection Method
Connecting the I/O cables to the AC-DC power supply unit
Cables are connected to the AC-DC power supply unit by means of detachable connectors that are
provided as standard items.
(Input unit: compatible cables: AWG 24 - 12. Tightening torque: 0.5 - 0.6Nm)
(Output unit: compatible cables: AWG 28 - 16. Tightening torque: 0.22 - 0.25Nm)
The AC-DC power supply unit and F&eIT Series product can be cable-connected using the detachable
connector that is provided on either the unit face or the modulet face (compatible cables:
AWG 28 - 16).
Please use the clothing of a cable, turning to it about about 7mm.
CAUTION
Because the AC-DC power supply unit generates heat, a minimum spacing of 2.0 cm should be
provided between the POW-AD22GY or POW-AD13GY and any adjoining units, and care should
be taken so that the ventilation holes are not covered.
List of Options
FAN Unit
-
FAN-FIT
FAN Unit
For 52.4mm-width unit or module