background image

POW-AD22GY, POW-AD13GY User’s Manual

                                                                                                                                                 

 

7

POW-AD22GY, POW-AD13GY

Installation Method

Mounting the AC-DC Power Supply Unit on the DIN Rail

Mounting procedure

(1) Pushing the fixing hook with a flat-blade

screwdriver renders it into a lock-enabled

condition.

35mm DIN rail

Press here to lift
the fixing hook.

 (2) Hook the AC-DC power supply unit from

the upper part of the DIN rail, and press the

lower part of the unit against the DIN rail.

Side view

(3) The fixing hook is automatically locked,

and the module can be mounted in one-

touch.

Side view

Fixing hook

Removal procedure

(1) Lower the fixing hook for the unit to unlock

it.

35mm DIN rail

(2) With the fixing hook unlocked, pull the

lower part of the unit toward you.

Side view

(3) By lifting the unit, you can easily remove it

from the DIN rail.

 

Side view

Содержание POW-AD22GY

Страница 1: ... company and product names mentioned herein are generally trademarks or registered trademarks of their respective owners Trademarks All company and product names that are referred to in this manual are generally trademarks or registered trade Handling Precautions CAUTION This power supply is dedicated to the F eIT Do not use for the other devices Do not use or store the equipment in a hot or cold ...

Страница 2: ...this series and can install it simply and smartly AC input can prepare 85 132V POW AD13GY and wide range 85 264V POW AD22GY and can unite and choose them as a system In addition a system can be easily built combining F eIT series product FCC PART 15 Class A Notice This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules Th...

Страница 3: ... Incorporate a mechanism so that opening the control panel automatically isolates the power supply 2 Water and dust proofing The control panel is dust and water proof If dust proofing or water proofing is made inadequate insulation may deteriorate increasing the risk of insulation failure The insulation on the POW AD22GY is designed to deal with pollution degree 2 and therefore the unit should onl...

Страница 4: ...hable A dedicated plug as a standard item Screw in type cable connection 2 piece power output connector detachable A dedicated plug as a standard item Screw in type cable connection Name Function DC input port DC output port LED Indicator ON DC output on OFF DC output off Name Function Indication Power LED Power green ...

Страница 5: ...f 25ºC and rated input and output 0mV Max It is change of the 30 minute 8 hours after input voltage impression in the circumference temperature of 25ºC and rated input and output warm up time 700ms Max ACIN 85V Io 100 200ms Max ACIN 85V Io 100 Output holding time 8ms Typ ACIN 100V Io 100 16ms Typ ACIN 200V Io 100 10ms Typ ACIN 85V Io 100 Overcurrent protection Operates at 125 Min of rated current ...

Страница 6: ...C68 2 6 compliant Impact resistance 15G half sine shock for 11ms in X Y and Z directions JIS C004 compliant IEC68 2 27 compliant Grounding Class D grounding previous class 3 grounding Installation location Installing to the DIN rail the control boards etc as the power supply dedicated to the F eIT I O Connectors Item Description Board connector 5 08mm pitch 12 0A rated current Compatible plug Late...

Страница 7: ... hook 2 Hook the AC DC power supply unit from the upper part of the DIN rail and press the lower part of the unit against the DIN rail Side view 3 The fixing hook is automatically locked and the module can be mounted in one touch Side view Fixing hook Removal procedure 1 Lower the fixing hook for the unit to unlock it 35mm DIN rail 2 With the fixing hook unlocked pull the lower part of the unit to...

Страница 8: ...f detachable connectors that are provided as standard items Input unit compatible cables AWG 24 12 Tightening torque 0 5 0 6Nm Output unit compatible cables AWG 28 16 Tightening torque 0 22 0 25Nm The AC DC power supply unit and F eIT Series product can be cable connected using the detachable connector that is provided on either the unit face or the modulet face compatible cables AWG 28 16 Please ...

Отзывы: