Installation
—
CPS-MC341-A1-111 Reference Manual (Hardware)
—
39
—
3.
Cable Connection
1.
Power
Power Cable
Use the power cable described below.
Cable
Twisted pair cable (when using a single wire, twist V+ wire and V- wire)
Cable Diameter
AWG24 - 16(0.2mm
2
- 1.25mm
2
)
Cable Length
Within 3 meters
FG Cable
Use the FG cable described below.
Cable Diameter
AWG18 - 16(0.75mm
2
- 1.25mm
2
)
*Refer to
in the
page 22
for details of the power connector and pin assignment.
Specification of External Power Supply
This product is designed to operate at least with 15watt power supply.
In addition, the power supply must fulfill the following requirements.
Rising time for
up to 12 voltage
2 milliseconds up to 30 milliseconds
Cable
Use copper wires that withstand a temperature of 75 °C or higher.
Recommended power supply is the optional product of the CPS-PWD-15AW12-01.
CAUTION
Removing the connector plug by grasping the cable can break the wire. Always grasp the
connector to remove it.
Tightening torque of the supplied connector is described below.
DEGSON : 0.19 N·m, PHOENIX CONTACT, PTR MESSTECHNIK : 0.25 N·m
Strip off approximately 7mm (plus or minus 0.5mm) of the covered part of a cable to connect
with the connector.
If the maximum output current of the external power supply is smaller than the maximum
consumption current of the product, the abnormal operations might occur due to the inrush
current at the start-up time or the load fluctuation. The aging external power supply could
cause a start-up failure
About a caution mark on the product: Please use copper wires that withstand the
temperature of 75 °C and higher.