NOTE!
Please leave switch in “OFF“ position when not functioning.
Connection of the fault message output:
If the DIP switch 3 is set to “ON“, the alarm relay is activated during high water.
An external alarm device can then be switched via terminals X5-2 and X5-3.
ATTENTION!
Close the cover of the electrical connection compartment before connecting the mains
plug to the power supply.
11 Level control switch settings
KS “C“ (bottom)
rises high
no function - pump readiness /
dry-running protection
Important note:
KS “C“ must be raised so that for
KS “B“ the pump start can be enabled
automatically.
KS “B“ (middle)
rises high
Pump 1 switches on
NOTE:
If necessary a switch-on delay of
15 seconds can be activated for
pump 2 (DIP switch 2 “OFF“).
Pump 2 switches on
KS “A“ (top)
rises high
alarm is triggered
KS “A“ (up)
goes down
alarm is switched off
KS “B“ (middle)
goes down
no function
KS “C“ (bottom)
goes down
turns off the pump (s
A
B
C
24
Commissioning | Level control switch settings