CIO
DESCRIPTION
31
3.6.3.
CIO active mode parameters
Parameter
name
Set values
range
Meaning of parameter
Auto operation
YES/NO
In case the parameter is set to (YES), CIO operates in the
active mode and the following parameters will influence its
function. In the other case, the following parameter settings
have no influence over CIO function. There are two
exceptions: "NulTime On" and "NulTime" parameters,
which are connected with the functioning of outputs and are
independent of the "Auto operation" parameter.
After-change
report
YES/NO
When set to (YES), CIO generates the report always when
there is a change to any active signal, power supply and
temperature too, by a value higher than hysteresis.
Send to CIO
YES/NO
When set to (YES), the report is sent to a defined remote
CIO block. The remote CIO block settings must be
appropriate.
It is possible to send the report either to a remote CIO
block, or to a remote user interface. Using both options
simultaneously is impossible.
Send to port
YES/NO
When set to (YES), the report is sent to a defined remote
user interface. The protocol settings of the remote CDA70
user interface must be appropriate.
It is possible to send the report either to a remote CIO
block, or to a remote user interface. Using both options
simultaneously is impossible.
Second station
YES/NO
If the parameter is set to (YES), the message is also sent to
the other (the second) remote CDA70. All other set
parameters are the same for both destination addresses.
NulTime On
YES/NO
The parameter affects output I/O signals. If set to (YES),
the value of outputs is correct, if its regular renewal is being
performed from a remote CDA70 in a shorter period than
set in the NulTime parameter. In case the module does not
accept the new output value within the time, the outputs are
set to inactive mode. The method protects connected
technology in case of unwanted communication failure.
In case the parameter is not set (NO), automatic zeroing of
outputs will not be applied.
Parameter function does not depend on the "Auto
operation" parameter setting.
COM
1 to 3
The parameter defines number of source module user
interface according to which source address will be
included in the report.