Operating Instructions
750 W 27 V pickup
CQF 04/2 + Interface M12
BAL9100-0145a-EN
www.conductix.com
translated document
Page 33 of 40
10.2
Normal status
If a device is off (lock) (primary track is active, device is off), the following displays are present:
(Red): “Error” LED
off
+ “Error relay” (contacts 3 - 6) closed
(Orange): “Alert” LED
off
+ “Alert relay” (contacts 3 - 5) open *
(Green): “Status” LED
flashing
+ “Status relay” (contacts 3 - 7) open
(Green): “5V” LED
on
(5V supply available)
(Green): “12V” LED
on
(12V supply available)
When a device is turned on (primary track active and device powered on (release)) and in normal operating condition, the following
displays are present:
(Red): “Error” LED
out
+ “Error relay” (contacts 3 - 6) closed
(Orange): “Alert” LED
off
+ “Alert relay” (contacts 3 - 5) open *
(Green): “Status” LED
on
+ “Status relay” (contacts 3 - 7) closed
(Green): “5V” LED
on
(5V supply available)
(Green): “12V” LED
on
(12 V supply available)
*
= Attention: in addition, a warning can be shown via a closed alert relay and the orange warning LED. This does not necessarily
mean that the device is being operated under incorrect conditions. However, it may be that the device is operating at its limit.
Additional information on the “Alert” topic can be found in the chapter 10.3.
10.3
Signals and their meaning
Alert signals provide detailed information (“on,” “flashing,” “off”) depending on how and in what context (LEDs, relay outputs) they
occur. For details on the respective relay status, please refer to Table 1 and to the respective LED status Table 2.
Note that if the input converter is off or the device is not positioned correctly over the primary track, all LEDs are off and all relay
outputs are open:
(Red): "Error" LED
off
+ "Error relay" (contacts 3 - 6) open
(Orange): “Alert” LED
off
+ “Alert relay” (contacts 3 - 5) open
(Green): "Status" LED
out
+ "Status relay" (contacts 3 - 7) open
(Green): “5V” LED
off
(5 V supply not available)
(Green): “12V” LED
off
(12 V supply not available)