26
Planning
2596995_0_EN_1905
Nortec RS
A
C
B
D
D
C
B
E
D
D
A
Figure 12: Clearances Nortec RS
Table 10: Minimum Clearances for Blower Packs
Steam
Capacity
lb/h (kg/h)
Blower Pack
Speed Setting
Min. Frontal
Clearance –
"A"
in (m)
Min. Overhead
Clearance –
"B"
in (m)
Min. Height
Above Ground
– "C"
in (m)
Suggested
Left Side Clear-
ance – "D"
in (m)
Suggested
Right Side
Clearance –
"D"
in (m)
10 (4.5)
Low
9 (0.23)
12 (0.31)
90 (2.3)
12 (0.31)
High
6 (0.16)
12 (0.31)
15 (6.8)
Low
18 (0.46)
12 (0.31)
High
6 (0.16)
12 (0.31)
20 (9.0)
Low
75 (1.91)
12 (0.31)
High
60 (1.53)
12 (0.31)
30 (13.5)
Low
86 (2.19)
12 (0.31)
High
71 (1.81)
12 (0.31)
45 (20.5)
Low
174 (4.42)
12 (0.31)
High
132 (3.36)
12 (0.31)
65 (30.0)
Low
189 (4.81)
48 (1.22)
30 (0.77)
High
153 (3.89)
12 (0.31)
90 (40.0)
Low
248 (6.30)
84 (2.14)
High
218 (5.54)
12 (0.31)
Data based upon nominal conditions 72 °F (22 °C), 40% RH.
Note: The High speed setting on the blower pack permits shorter absorption distances, whereas the Low setting permits the blower to
run quieter but requires longer absorption distances. Visit
and use the free Condair online program - Humidifier
Engineering and Load-sizing Program (H.E.L.P.) to assist with absorption distance and other calculations.