Nortec SAM-e Installation |
40
Atmospheric Nortec SAM-e Condensate Drainage
1
Nortec SAM-e condensate outlet connection is male 3/4”-NPT.
2
Condensate from Nortec SAM-e must be plumbed to a P-trap. Trap must have center-to-
center height of at least 8”, or 2” more than duct static pressure, whichever is greater.
Refer to typical installation drawings.
3
Condensate from P-trap should drain into a funnel with air-gap prior to entering building
drain.
4
Condensate exits at 212°F (100°C). Local codes may require use of a drain water
cooler (part number 1710020 - electronic drain water cooler or 1710010 – self-actuated
drain water cooler). Refer to installation manual that accompanies drain water cooler for
plumbing details.
5
When collecting condensate, ensure that each device has an air-gap prior to entering the
condensate collection system. Failing to incorporate an air-gap may cause backpressure
on Nortec SAM-e and result in poor performance.
6
Some humidifiers allow distributor condensate to be returned to the unit. Refer to
humidifier manual for details.
7
For systems using condensate pumps, a P-trap and air-gap are still required at Nortec
SAM-e outlet. Never connect Nortec SAM-e directly to a pressurized drain line.
Содержание Nortec Mini SAM-e
Страница 1: ...DELETE THIS PAGE AFTER PRINTING OR GENERATING PDF...
Страница 7: ...3 Nortec SAM e Installation Identify your Components...
Страница 8: ...Nortec SAM e Installation 4 Identify your Optional Components...
Страница 11: ...7 Installation Nortec SAM e In Duct...
Страница 12: ...Nortec SAM e Installation 8 Typical Nortec SAM e Installation General Nortec SAM e Assembly Diagram...
Страница 19: ...15 Nortec SAM e Installation Installation in Vertical Duct...
Страница 21: ...17 Nortec SAM e Installation Nortec Mini SAM e Installation Procedures...
Страница 22: ...Nortec SAM e Installation 18 Nortec Mini SAM e Assembly General Installation...
Страница 25: ...21 Nortec SAM e Installation Plumbing...
Страница 28: ...Nortec SAM e Installation 24 Internal Baffle Plate...
Страница 36: ...Nortec SAM e Installation 32...
Страница 37: ...33 Nortec SAM e Installation Atmospheric Steam Lines...
Страница 48: ...Nortec SAM e Installation 44 Figure 8 Long Steam Run...
Страница 49: ...45 Nortec SAM e Installation Atmospheric Steam Lines...
Страница 55: ...51 Nortec SAM e Installation 3 Apply shields to tubes and secure with stainless straps 4 Completed Tube...
Страница 57: ...53 Nortec SAM e Installation 3 Fit shields to tubes 4 Secure with stainless straps...
Страница 58: ...Nortec SAM e Installation 54 5 Completed tube...
Страница 59: ...55 Nortec SAM e Installation Troubleshooting Maintenance Spare Parts...