Содержание Nortec Mini SAM-e

Страница 1: ...DELETE THIS PAGE AFTER PRINTING OR GENERATING PDF...

Страница 2: ...Includes installation operation maintenance and troubleshooting information for your Nortec SAM e and Nortec Mini SAM e Short Absorption Manifold 1507619 L 15 Jan 2020 Important Read and save these in...

Страница 3: ...D except to the extent required for installation or maintenance of recipient s equipment All references to the Condair name should be taken as referring to CONDAIR LTD Liability Notice Condair does no...

Страница 4: ...e with Pressurized Steam 29 Nortec SAM e with Atmospheric Steam 31 Nortec Mini SAM e with Atmospheric Steam 33 Atmospheric Steam Lines 34 Plumbing 34 Atmospheric Nortec SAM e Steam Lines 39 Length of...

Страница 5: ...s which could block steam output should be connected to the steam outlet Steam lines must be installed so that no restriction can produce backpressure in the humidifier CAUTION Servicing Disconnect ma...

Страница 6: ...s related to steam supply may result in excess moisture or water collecting in steam tube pipe with the potential for water damage To ensure protection against water damage best practice includes eith...

Страница 7: ...3 Nortec SAM e Installation Identify your Components...

Страница 8: ...Nortec SAM e Installation 4 Identify your Optional Components...

Страница 9: ...Manual Nortec SAM e In Duct Section 2 Follow steps 1 8 Nortec SAM e Vertical Duct Installation Section 4 Follow steps 1 8 Then refer to Section 3 Nortec mini SAM e Section 5 Follow steps 1 2 This sec...

Страница 10: ...Steam 6B Nortec mini SAM e Pressure Steam 6C Nortec SAM e Atmospheric Steam 6D Nortec mini SAM e Atmospheric Steam Steam Lines Section 7 Nortec SAM e Insulation Section 8 8A Nortec SAM e Retrofit 8B N...

Страница 11: ...7 Installation Nortec SAM e In Duct...

Страница 12: ...Nortec SAM e Installation 8 Typical Nortec SAM e Installation General Nortec SAM e Assembly Diagram...

Страница 13: ...n support brackets to header using 5 16 washers and 5 16 nylon lock nuts 2 Place header on duct floor and drill 4 x 1 2 12 7 mm holes through floor Secure header to floor using fasteners by others Use...

Страница 14: ...10 3 Insert tube into insertion stop washer and then into grommet Wetting grommet with water will make assembly easier Ensure nozzles face the sides of the duct perpendicular to air flow 4 Assemble re...

Страница 15: ...11 Nortec SAM e Installation 5 Attach tube support bracket using supplied 1 4 lock washer and 1 4 hex screws 6 No mounting frame proceed to step 6A Mounting frame proceed to step 7...

Страница 16: ...M e Installation 12 6A If no mounting frame is supplied Attach bracket flanges to tube support bracket using 5 16 screws washers and nylon lock nut Bolt flanges to duct wall using field supplied 1 2 f...

Страница 17: ...13 Nortec SAM e Installation 7 Slide frame sides into frame base 8 Attach Frame Pivot using 5 16 bolt washer and nylon lock nut Side View...

Страница 18: ...the top rail between The other end of the seismic brace secures to the ceiling of the air handler with minimum 2 x 5 16 diameter grade 5 screws per span of seismic brace With the hardware kit that ac...

Страница 19: ...15 Nortec SAM e Installation Installation in Vertical Duct...

Страница 20: ...tion 16 Vertical Duct Installation for Nortec SAM e 1 Complete assembly following Steps 1 through 8 on pages 9 through 13 Install complete assembly into duct at 10 angle Fasten to duct walls using fie...

Страница 21: ...17 Nortec SAM e Installation Nortec Mini SAM e Installation Procedures...

Страница 22: ...Nortec SAM e Installation 18 Nortec Mini SAM e Assembly General Installation...

Страница 23: ...supplied template to cut holes for steam and condensate parts Attach header to duct using field supplied fasteners 2 Insert steam tubes with Insertion stop washers ensuring nozzles are perpendicular...

Страница 24: ...m tubes with Insertion stop washers ensuring nozzles are perpendicular to airflow Using water to wet the rubber grommets will facilitate installation Seal all ductwork 3 Attach tube support bracket us...

Страница 25: ...21 Nortec SAM e Installation Plumbing...

Страница 26: ...When pressurized steam enters Nortec SAM e pressure drops down to almost atmospheric pressure Therefore it must be drained atmospherically and the use of a condensate pump rated for 212 F must be used...

Страница 27: ...nsate from Nortec SAM e to be returned to atmospheric floor drain When pressurized steam enters Nortec SAM e pressure drops down to almost atmospheric pressure Therefore it must be drained atmospheric...

Страница 28: ...Nortec SAM e Installation 24 Internal Baffle Plate...

Страница 29: ...wn to almost atmospheric pressure Therefore it must be drained atmospherically and the use of a condensate pump rated for 212 F must be used to raise condensate to a higher elevation or return to a pr...

Страница 30: ...ic floor drain When pressurized steam enters Nortec SAM e pressure drops down to almost atmospheric pressure Therefore it must be drained atmospherically and the use of a condensate pump rated for 212...

Страница 31: ...d condensate main Condensate from Nortec SAM e to be returned to atmospheric floor drain When pressurized steam enters Nortec SAM e pressure drops down to almost atmospheric pressure Therefore it must...

Страница 32: ...c Mini SAM e pressure drops down to almost atmospheric pressure Therefore it must be drained atmospherically and the use of a condensate pump rated for 212 F must be used to elevate condensate to a hi...

Страница 33: ...n Nortec SAM e with Atmospheric Steam Atmospheric Plumbing Atmospheric steam inlet Use Condair supplied steam hose and gear clamps Drain 1 Air Gap To Prevent Back Flow 6 min 8 min 2 plus duct static p...

Страница 34: ...4 NPT Reducer Supplied By Others 1 Air Gap To Prevent Back Siphonage Atmospheric steam inlet Use Condair supplied steam hose and gear clamps To drain 1 2 NPT Cold water inlet 3 4 NPT Manual dump valv...

Страница 35: ...AM e with Atmospheric Steam Nortec Mini SAM e with Atmospheric Steam Atmospheric steam inlet Use Condair supplied steam hose and gear clamps Drain 1 Air Gap To Prevent Back Siphonage 6 min 8 min 2 plu...

Страница 36: ...Nortec SAM e Installation 32...

Страница 37: ...33 Nortec SAM e Installation Atmospheric Steam Lines...

Страница 38: ...ward 3 See material recommended for use in below chart To eliminate metal corrosion Condair does not recommend the use of steel piping 4 Consult below charts for steam and condensate sizing guidelines...

Страница 39: ...8 0 06 15 ft EL 005 5 3 4 7 8 0 06 7 ft EL 010 10 3 4 7 8 0 06 12 ft EL 020 20 3 4 7 8 0 06 17 ft EL 030 30 3 4 7 8 0 06 22 ft EL 050 50 1 1 2 1 3 4 0 11 43 ft EL 075 75 1 1 2 1 3 4 0 11 47 ft EL 100...

Страница 40: ...el tube diameter wall thickness 0 065 Steam loss per foot in condensation lb ft Steam line maximum equivalent length GS 100 100 1 1 2 1 3 4 0 11 90 ft GS 200 200 3 3 0 16 90 ft GS 300 300 3 3 0 16 180...

Страница 41: ...am loss per foot in condensation lb ft Steam line maximum equivalent length SE 050 1 50 1 1 2 1 3 4 0 11 37 ft SE 100 1 100 1 1 2 1 3 4 0 11 90 ft SE 175 1 175 3 3 0 16 90 ft SE 250 1 250 3 3 0 16 180...

Страница 42: ...m line maximum equivalent length RS 010 10 1 1 2 1 3 4 0 11 12 ft RS 015 15 1 1 2 1 3 4 0 11 15 ft RS 020 20 1 1 2 1 3 4 0 11 18 ft RS 030 30 1 1 2 1 3 4 0 11 27 ft RS 045 45 1 1 2 1 3 4 0 11 43 ft RS...

Страница 43: ...80 ft Valve in full open position Material for Steam Lines Table 6 Effective length of Typical Steam Line Fittings Material Type Note Copper MED L Tube Recommended Stainless steel Tube wall thickness...

Страница 44: ...f a drain water cooler part number 1710020 electronic drain water cooler or 1710010 self actuated drain water cooler Refer to installation manual that accompanies drain water cooler for plumbing detai...

Страница 45: ...pipe Figure 3 Condensate Traps MAIN RULES FOR ATMOSPHERIC STEAM LINES Steam lines must be sloped Condensate must be trapped Use full size T for traps Steam lines must not have any restrictions that co...

Страница 46: ...Nortec SAM e Installation 42 Figure 4 Distributor Above Humidifier Copper Steam Line Figure 5 Distributor Above Humidifier Hose...

Страница 47: ...43 Nortec SAM e Installation Figure 6 Steam Distributor Below Humidifier Hose Figure 7 Steam Distributor Below Humidifier and Obstruction Hose...

Страница 48: ...Nortec SAM e Installation 44 Figure 8 Long Steam Run...

Страница 49: ...45 Nortec SAM e Installation Atmospheric Steam Lines...

Страница 50: ...manifold by steam tubes Field Retrofit of Insulation 1 Unpack insulation covers Inspect insulating covers for shipping damage covers should be straight After tubes and headers have been inspected ins...

Страница 51: ...in 36 in 42 in 48 in 6 2 18 2 24 2 30 2 36 2 42 2 48 2 54 2 60 2 2 66 4 72 2 2 78 4 84 2 2 90 4 96 2 2 102 4 108 2 4 114 6 120 4 2 126 2 4 132 6 138 4 2 Quantity of Insulating Covers Required to Cove...

Страница 52: ...or Nortec SAM e Dual Inlet expand insulation to fit over header and slide on Additionally expand smaller metal cover for inlet leg and slide on If inlet leg insulation conflicts with inlet adapter tri...

Страница 53: ...49 Nortec SAM e Installation Nortec SAM e Insulation Retrofit 1 Install header wrap around header 2 Tuck header wrap underneath rubber grommets and secure with stainless wraps at each end...

Страница 54: ...SHIELD TO CREATE OVERLAP DETAIL D USE TIE WRAP2538347 TO SECURE IN PLACE D ALWAYS PLACE TIE WRAPS AT THE ENDS OF THE SHILED 1 2 INCH IN WHEN 3 TIE WRAPS ARE NEEDE POSITION ONE IN THE APPROXIMATE MIDDL...

Страница 55: ...51 Nortec SAM e Installation 3 Apply shields to tubes and secure with stainless straps 4 Completed Tube...

Страница 56: ...Nortec SAM e Installation 52 Nortec Mini SAM e Insulation Retrofit 1 Connect Top and Bottom heat shields together snap fit 2 Completed header...

Страница 57: ...53 Nortec SAM e Installation 3 Fit shields to tubes 4 Secure with stainless straps...

Страница 58: ...Nortec SAM e Installation 54 5 Completed tube...

Страница 59: ...55 Nortec SAM e Installation Troubleshooting Maintenance Spare Parts...

Страница 60: ...nce Inspect Nortec SAM e at start up 1 For humidifier maintenance schedule refer to Installation Operation and Maintenance Manual for your humidifier Spare Parts Kit Part Kit description Quantity in K...

Страница 61: ...l purchase price for the product Any further warranty must be in writing signed by an officer of THE COMPANY THE COMPANY s limited warranty on accessories not of the companies manufacture such as cont...

Страница 62: ...U S A 2700 90th St Sturtevant WI 53177 835 Commerce Park Dr Ogdensburg NY 13669 2209 CANADA 2740 Fenton Road Ottawa Ontario K1T 3T7 TEL 1 866 667 8321 EMAIL na info condair com WEBSITE www condair com...