Installation

4.3.5  Positioning and installing the throttle valve

The throttle valve (DK) must be connected directly to the exhaust gas distribution pipe and fixed to 

the supplied pipe clamp on the exhaust gas distribution pipe (see illustration below). The condensate 

discharge connection must point vertically downwards. 

The condensate hose is attached to the condensate connection and run at a constant incline via a trap 

(hose bend ø min. of 200 mm) into an open discharge funnel connected to the building's waste water pipe.

Exhaust gas distribution pipe

Throttle valve

Condensate connection ø15 mm

Trap (min. ø200 mm)

Open discharge funnel

Fig. 13:  Positioning and installing the throttle valve

Содержание GS 130

Страница 1: ...INSTALLATION AND OPERATION MANUAL DVGW certified exhaust gas management system for Condair GS Series II 2596151 C_EN_2010_Condair GS EGMS_IOM Humidification and Evaporative Cooling...

Страница 2: ...ll be reproduced used or disclosed to others without the written authorisation of Condair Group AG except to the extent required for installation or maintenance of recipient s equipment Liability Noti...

Страница 3: ...ust gas distribution pipe 16 4 3 2 Assembling the exhaust gas pipes 17 4 3 3 Positioning and fitting the differential pressure switch 18 4 3 4 Positioning and fitting the draught limiter 20 4 3 5 Posi...

Страница 4: ...AC system Symbol explanation CAUTION The catchword CAUTION used in conjunction with the caution symbol in the circle designates notes in this installation manual that if neglected may cause damage and...

Страница 5: ...d by the manufacturer It is assumed that all people entrusted with working on the DVGW certified exhaust gas management system are familiar with and comply with health and safety at work and accident...

Страница 6: ...from the building with the gas leak Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department DANGER Risk of electric shock The Condair GS is mains powered...

Страница 7: ...W certified exhaust gas management system is intended exclusively for discharging the exhaust gases from the gas fired Condair GS steam air humidifier into the exhaust air of an AC system within the s...

Страница 8: ...tic diagram 2 1 3 3 4 5 6 7 8 9 10 11 12 13 15 14 16 Air conditioning incoming air Air conditioning exhaust air Fig 1 Schematic diagram 1 DVGW certified exhaust gas management system 2 Gas fired steam...

Страница 9: ...eam air humidifier must be in the same room as the air conditioning system exhaust air installation In order to guarantee a sufficient air after flow there must be an opening in the room to the outsid...

Страница 10: ...3075 4100 6150 9225 12300 Permissible negative pressure range system limits Position of the throttle valve Maximum negative pressure Exhaust air Minimum negative pressure Exhaust air 9 fully open 1200...

Страница 11: ...4 stainless steel Pipe diameter Part No Standard set 8 m 2 Condair GS 23 Condair GS 45 Condair GS 65 100 mm 1 2598918 Condair GS 90 Condair GS 130 100 mm 2598920 Condair GS 195 Condair GS 260 150 mm 2...

Страница 12: ...3 130 2597051 GS 195 260 2597718 Throttle valve 100 mm with condensate port 1 GS 23 130 2597052 GS 195 260 2597723 Pipe clip lip seal pre installed on pipe parts 14 GS 23 130 2597054 2597055 GS 195 26...

Страница 13: ...duct 100 5 GS23 130 2569548 1 1 150 5 GS195 260 2599066 1 100 10 1070 mm GS23 130 2569549 1 1 150 10 1070 mm GS195 260 2599067 1 100 15 1385 mm GS23 130 2569550 1 1 150 15 1385 mm GS195 260 2599068 1...

Страница 14: ...idifier min 3 1 Condensate trap 2 Differential pressure switch KS C2 3 Measurement connection for pressure gauge 4 Draught limiter Z180 5 Throttle valve DK 6 Exhaust gas distribution pipe AVR 7 Flow m...

Страница 15: ...re gauge 4 Draught limiter Z180 5 Throttle valve DK 6 Exhaust gas distribution pipe AVR 7 Flow monitor IN511 8 Ceiling or wall support 9 Exhaust air fan 10 Outlet with trap compulsory for exhaust air...

Страница 16: ...e duct wall and drill the hole Diameter of hole Condair GS 23 45 110 mm 1 Condair GS 65 110 mm 1 Condair GS 90 130 110 mm 1 Condair GS 195 260 160 mm 1 1 absolutely necessary Fig 4 Drilling the feedth...

Страница 17: ...4 Push the pipe clamp over the rubber seal and tighten Important information about the design of the exhaust gas pipe Only use the installation material contained in the delivery schedule A condensat...

Страница 18: ...h a way that the connection piece for the differential pressure switch is positioned if possible in the middle of the Condair GS exhaust gas connection and the draught limiter There must be a minimum...

Страница 19: ...note and follow the instructions in this manual Fig 8 Fitting the differential pressure switch 1 Fix the differential pressure switch bracket onto the measurement pipe support with two screws 2 Snap...

Страница 20: ...st be fitted as close as possible to the Condair GS exhaust gas connection There must be minimum distances of 2 m from the Condair GS exhaust gas connection and 1 m from the differential pressure swit...

Страница 21: ...ual 1 Fit the T pipe P AF into the exhaust gas pipe and align the pipe socket vertically with a spirit level Fig 10 Fitting the T pipe 2 Insert the draught limiter into the pipe connections and align...

Страница 22: ...22 Installation 2596151 C_EN_2010_Condair GS EGMS_IOM 3 Turn the locking screw to the left until it stops in order to release the draught air valve Fig 12 Releasing the draught limiter Locking screw...

Страница 23: ...pipe see illustration below The condensate discharge connection must point vertically downwards The condensate hose is attached to the condensate connection and run at a constant incline via a trap ho...

Страница 24: ...Installing the flow monitor Note Separatefittinginstructionsareenclosedfortheflowmonitor Pleasenoteandfollowtheinstructions in this manual Fig 14 Installing the flow monitor 1 Mark the position of th...

Страница 25: ...C 1 2 3 4 5 6 7 8 J1 A2 CH2 A1 CH1 K1 B1 B2 B3 0 10 mADC 2 20 mADC 0 20 mADC 4 20 mADC 0 10 VDC 2 10 VDC 0 5 VDC 1 5 VDC A3 S1 JP3 5 Vdc max 500 mA JP4 24 Vdc max 150 mA 24 VAC SL CH1 CH2 24 VDC 10 VD...

Страница 26: ...e sensitive to electrostatic discharges In order to protect these components measures must be taken to prevent electrostatic discharge ESD protection for all installation work 5 3 Connecting the diffe...

Страница 27: ...Bk Gr Bk R M R Bk R M Drain Valve optional Bk 2 Burner Units Only R Y Gr Y R Bk 2 Burner Units Only Gr Y Gr Y Gr 120 V Bl Bl Br Gr Y Gas Valve 1 _ Rectifier R Bk Br R JP1 SETTINGS 1 2 3 1 2 3 Standar...

Страница 28: ...R Bk Bk R Bk Gr Bk R Gr Bk Gr Bk R M R Bk R M Drain Valve optional Bk 2 Burner Units Only R Y Gr Y R Bk 2 Burner Units Only Gr Y Gr Y Gr Bl Bl Br Gr Y Gas Valve 1 Br R JP1 SETTINGS 1 2 3 1 2 3 Standar...

Страница 29: ...18 Supplementary Wiring Diagram Condair GS 195 260 Legend Wiring Diagrams A1 External humidity controller or humidity sensor signal CH1 A2 External humidity limiter controller or humidity limiter sen...

Страница 30: ...they will go see instructions for the draught limiter 6 Start the exhaust air system and ramp up to maximum power 7 Using the throttle valve set the negative pressure to 100Pa check with a pressure ga...

Страница 31: ...up no longer falls below 20 Pa Then steps 5 7 must be repeated until the system is balanced and works without any problems in the permissible negative pressure range of 20 Pa to 100 Pa 10 Seal the po...

Страница 32: ...itch is open while the humidifier is operating Shouldtheairprovingswitchopenduring operation the controller will interrupt all ignition modules and activate the blow ers at 100 After a several seconds...

Страница 33: ...Notes...

Страница 34: ...Notes...

Страница 35: ......

Страница 36: ...Condair Group AG Gwattstrasse 17 8808 Pf ffikon SZ Sitzerland Phone 41 55 416 61 11 Fax 41 55 588 00 07 info condair com www condairgroup com CONSULTING SALES AND SERVICE CH94 0002 00...

Отзывы: