Concoa Advantium 16 Скачать руководство пользователя страница 8

 

INSTALLATION INSTRUCTIONS 

 
After mounting the Advantium16 to the wall, wire any monitored devices through the 
conduit connection and to the input terminal blocks (see Figures 3-9).  If using the output 
of the Advantium16 to connect to another alarm or system, attach wires to the output 
terminal blocks (see Figure 10).   

Turn Advantium16 ON by plugging the unit directly into a wall outlet and turning the 
power switch in the inside of the front cover to the ON position.  The system may be 
tested once it is connected to an external device by tripping the external alarm seeing the 
corresponding input LED turn red.  

Figure 3

 

 

 

CONNECTING EXTERNAL INPUT DEVICES TO THE 
ADVANTIUM 16

 

The Advantium 16 is designed to interface with up to 16 external pressure switches or 
any dry contact inputs. The external device wires (+12Vdc out, signal in) are brought in 
through a conduit connector on the left side of the box and connected to terminal blocks 
on the left hand side of the circuit board. Figures 3-9 outline how to connect various 
CONOCA products to the Advantium 16.  

The recommended cable for this assembly is 14-26 AWG wire (Alpha # 1176C or 
equivalent). The length of each cable should be limited to 1500 feet.  

Cut the cable to length. Remove the outer jacket of the cable to expose approximately 3/4 
inch of the internal conductors on both sides of the cable. Strip away 1/4-inch of the 
insulation on each of the conductors 

Note: Older revisions of the 522, 523, 536, 537, 636, 637, and 638 series AutoSwitch 
units are not compatible with the Advantium 16 without a special cable assembly. 
Please contact CONCOA for details. 

 

Содержание Advantium 16

Страница 1: ...ATING INSTRUCTIONS Carefully Read These Instructions Before Operating Carefully Read These Controls Corporation of America 1501 Harpers Road Virginia Beach VA 23454 Telephone 1 800 225 0473 or 757 422...

Страница 2: ...ENVIRONMENTS DO NOT INSTALL THIS PRODUCT IN ANY HAZARDOUS ENVIRONMENT If product appears damaged in any way do not use and request service from CONCOA USER RESPONSIBILITY Service to this product shou...

Страница 3: ...he Advantium 16 6 Connecting Alarm Outputs 11 Setting Remote Alarm Outputs 12 Muting Audible Alarm 14 Real Time Clock 14 Configuration using the WebServer 15 Status Page 15 View Settings Page 16 Chang...

Страница 4: ...tage External Power Supply Universal input voltage 100 240 VAC 50 60Hz Power Consumption 8 watts ALARM OUTPUT RELAY SPECIFICATIONS Contacts Normally Open Normally Closed selectable Dry Contact Contact...

Страница 5: ...contains two relay output signals and a shared common voltage input The Advantium 16 is factory set so that these output signals are brought out through Normally Closed N C contacts Output relay signa...

Страница 6: ...s The Advantium16 uses Normally Closed N C contact signals by default from the external inputs to determine the state of the alarms The normal conditions of these alarms are customizable via the web i...

Страница 7: ...5 MOUNTING REQUIREMENTS Figure 2...

Страница 8: ...to interface with up to 16 external pressure switches or any dry contact inputs The external device wires 12Vdc out signal in are brought in through a conduit connector on the left side of the box an...

Страница 9: ...7 Figure 4...

Страница 10: ...8 Figure 5 Figure 6 Figure 7 See Figure 4 for Available Cable Lengths Cable Ass y 5295349 L Figure 8...

Страница 11: ...9 Figure 9...

Страница 12: ...e Figure 10 below The relay contacts are configurable They are factory set as Normally Closed N C but may be changed to Normally Open N O if needed Refer to the Section Setting Remote Alarm Outputs in...

Страница 13: ...rm from AC power 2 Open the unit by loosening the 6 screws located on the front of the enclosure 3 Figure 11 shows the location of the jumpers on the circuit board for setting the contacts 4 Using Tab...

Страница 14: ...lay Output 4 J16 Relay Output 5 J18 Relay Output 6 J21 Relay Output 7 J23 Relay Output 8 J26 Relay Output 9 J28 Relay Output 10 J31 Relay Output 11 J33 Relay Output 12 J36 Relay Output 13 J40 Relay Ou...

Страница 15: ...In order to re enable the audio alarm press and hold the alarm for five seconds again The speaker will sound once indicating the audio alarm is enabled REAL TIME CLOCK The Advantium 16 has a battery b...

Страница 16: ...GE The Advantium 16 webserver Status screen is essentially a copy of the front panel of the Advantium 16 unit Each of the front panel LED s and labels are represented and colored RED or GREEN based on...

Страница 17: ...splays two system parameters Webserver Software version and FPGA version An export settings button on the page allows for exporting data into a text file This includes all of the Advantium 16 system p...

Страница 18: ...ge shows the current settings for the date time and system ID When utilizing more than one Advantium 16 control system the System ID can be used to differentiate the units in the email subject line Th...

Страница 19: ...is disabled it will be ignored and the LED will be turned off The name of the input is used on the status page and in any generated emails The normal condition of the input indicates the expected cir...

Страница 20: ...onfiguration of output relays To be used an input group must have at least one member If an input group is disabled none of the multi color LEDs for member inputs will blink red when all enter alarm c...

Страница 21: ...should be used to determine whether the output relay exits normal condition If Relay is chosen the numbers at the right of the row 1 16 correspond to the number of the input relay see the Inputs sett...

Страница 22: ...determine whether the e mail alert will be triggered If Relay is chosen the numbers at the right of the row 1 16 correspond to the number of the input relay see the Inputs settings page for configura...

Страница 23: ...tory default security settings To enable security enter a password twice click the desired Security Enabled box and click the set button The cancel button will restore the current settings if any have...

Страница 24: ...f any have been made in the browser but not committed Any change to the IP settings will immediately cause the server to restart therefore please ensure access to the new network location prior to cli...

Страница 25: ...get host To force all mail to be sent via relay regardless of the recipient domain enter the name or address of the relay server in RELAY ADRESS If this setting is blank the SMTP server on the Advanti...

Страница 26: ...obligation and Buyer s sole and exclusive remedy under the above warranties is limited to repairing using new or reconditioned parts or replacing free of charge except for labor if permanently install...

Страница 27: ...25...

Страница 28: ...26 Certified ISO 9001 Controls Corporation of America 1501 Harpers Road Virginia Beach VA 23454 Telephone 1 800 225 0473 or 757 422 8330 Fax 757 422 3125 www concoa com...

Отзывы: