9400

Series

Relief

Valve

Table 1

Part 

Number

Material

Seat

Pressure 

Range

Flow at 10% Pressure 

Differential

830-9414 Brass

Neoprene   80-120 PSIG   1,263 SCFH (N2 100 PSIG)

830-9413 Brass

Viton

270-600 PSIG 12,864 SCFH (N2 420 PSIG)

830-9412 Brass

Viton

130-310 PSIG   6,960 SCFH (N2 220 PSIG)

FIELD ADJUSTMENT

Note: The safety relief device should not be used as a control valve to regulate 
the system operating pressure. Frequent activation will cause seat leak and 
require excessive maintenance.

DO NOT ADJUST WHILE UNDER PRESSURE.

1.  Maintain system-operating pressure at least 5-10% below the set pressure 

of the relief valve. Operating too close to the valve set pressure will cause 
seat leak and will shorten the time between valve maintenance.

2.  To adjust the cracking pressure,  a field test bench maybe constructed 

using the following parts as shown in Figure 2 below:
a.   492-1312-01-580  0-750 PSIG regulator
    601-3312-01-580  0-150 PSIG regulator
b.   529-0022-01-001  Reducing adapter
c.   533-9002   

Needle valve

d.   830-5385   

Brass ¼” tee

Figure 2

Figure 1

Содержание 830-9412

Страница 1: ...1 800 225 0473 or 757 422 8330 Fax 757 422 3125 www concoa com 830 9412 830 9413 830 9414 Relief Valves December 2009 Supercedes Septemeber 2004 INSTALLATION AND OPERATION INSTRUCTIONS Certified ISO...

Страница 2: ...ther than CONCOA or a service facility designated by CONCOA CUSTOMER SERVICE In the event of equipment failure call CONCOA Customer Service Please be prepared to provide the model number and serial nu...

Страница 3: ...e Frequent activation will cause seat leak and require excessive maintenance DO NOT ADJUST WHILE UNDER PRESSURE 1 Maintainsystem operatingpressureatleast5 10 belowthesetpressure of the relief valve Op...

Страница 4: ...t the desired pressure go to step eleven 11 If further adjustment is required proceed to step ten 10 10 Repeat steps four 4 through nine 9 until the desired cracking pressure is obtained 11 Valve is r...

Страница 5: ...e outlet connection so as to prevent backpressure when relieving The piping termination point must be in a safe location and away from ignition sources The termination point must be positioned to prev...

Страница 6: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 7: ...other than Controls Corporation of America or if the equipment has been subject to abuse misuse negligence or accident Controls Corporation of America s sole and exclusive obligation and Buyer s sole...

Страница 8: ...Certified ISO 9001 ADI 9902 B Controls Corporation of America 1501 Harpers Road Virginia Beach VA 23454 To Order Call 1 800 225 0473 or 757 422 8330 Fax 757 422 3125 www concoa com...

Отзывы: