Concoa 547 Series Скачать руководство пользователя страница 9

9

left note the pressure reading on the right side gauge that is installed in the test port see figure 4, it should 

be approx. 1050 psig then rotate the arrow clockwise to the right and note the pressure reading on the right 

side gauge again it should read 1250 psig approx. Note what those two pressures are and determine the 

mean between those two pressures it should be approx. 1150 psig. On the left preset regulator there is a 

nut and lock washer fixing the adjusting screw. Remove the nut and lock washer, rotate the adjusting screw 

in clockwise to increase the setting of the left side regulator to be equal to the mean of the right side two 

pressure settings (approximately 1150 psig) it should require approximately between 1 to 2 turns to set that 

pressure as indicated on the left side gauge installed in the test port located on the left side regulator. 

Reinstall the lock washer and nut to fix the left side pressure setting. Cycle the unit thru simulated switchovers 

by  closing  the  inlet  isolation  valves  while  flowing  gas  downstream  to  ensure  the  set  pressures  are  fixed 

properly. Note that the pressures will drop slightly (approx. 30 psig) from static to flowing condition this is 

normal. If left side pressure needs to be reset do so ensuring it falls in the approximate middle or mean of the 

two right side switching pressures.

MAINTENANCE

On regular intervals, the system should be checked for leaks and proper function (see trouble shooting). 

Any leaks in the system should be corrected immediately. The pigtail check valve should also be checked 

for leaks when a depleted cylinder is removed. NOTE:  the system inlet and pigtail should be pressurized 

when check- ing for leaks.  At no time should the preset regulator’s or priority valve regulator’s pressure 

settings be changed.

Typical symptoms listed below indicate regulator malfunctions  needing repair.  Replace immediately with a 

clean, repaired and tested, or new system.

1.  Gas leakage at the line regulator outlet when the adjusting screw of the line regulator is completely 

backed out.

2.  With no flow through the system (downstream valves closed and adjusting screw in) line pressure 

steadily increases above set pressure.

3.  Gas leakage from spring case (adjusting screw/knob end of regulator).

4.  Gas leakage from any joint.

5.  Excessive drop in working pressure with regulator flowing gas.

6.  Gas leakage from gauge

7.  Gauge does not return to zero when not under gas pressure

8.  Gauge does not consistently repeat the same reading.

10. The system makes a noise or hums.

 

both inlet gauges at the same time), please contact a CONCOA customer service personnel. Please be 

prepared to give the following:

Model number

Gas service

Inlet pressure and type of gas supply

Outlet pressure

Approximate gas usage

NOTE: Maximum rated flow for these systems is 4000 SCFH.

TROUBLE SHOOTING

Содержание 547 Series

Страница 1: ...nd Comply with These Instructions Controls Corporation of America 1501 Harpers Road Virginia Beach VA 23454 To Order Call 1 800 225 0473 or 757 422 8330 Fax 757 422 3125 www concoa com February 2016 A...

Страница 2: ...um inlet only With 547 XXX4 models an optional universal voltage remote alarm provides an audible and visual warning that a changeover is about to occur Pressing a button on the front of the remote al...

Страница 3: ...conditions and gas service Things to consider before removing the system from the box 1 Know the properties and special handling requirements of the gas being used Many specialty gases are quite dange...

Страница 4: ...lways rotate the priority valve 180 so that the arrow on the knob is pointing to the in use full side of the switchover CAUTION Always close all manifold station and cylinder valves on the nearly empt...

Страница 5: ...the cylinder decreases Manifolds installed in open locations should be protected from weather conditions During winter protect the manifold from ice and snow In summer shade the manifold and cylinders...

Страница 6: ...ad as shown in Figure 3 make sure the tape does not overlap the end of the fitting As the tape is wrapped in the direction of the thread spiral pull tightly on the end of tape so that the tape conform...

Страница 7: ...to avoid squashing the gasket into the gas line Keep extra gaskets on hand c Never use oil or grease on regulator or cylinder fittings as it may contaminate pure gases or create a fire hazard Installi...

Страница 8: ...X 547 3XXX 547 4XXX Cylinder Pressure 250 350 PSIG 17 24 BAR 1050 1150 PSIG 72 79 BAR 1250 1500 PSIG 86 103 BAR 1800 2300 PSIG 124 159 BAR 2800 3300 PSIG 193 228 BAR 3800 4300 PSIG 262 297 BAR higher...

Страница 9: ...ght side switching pressures MAINTENANCE On regular intervals the system should be checked for leaks and proper function see trouble shooting Any leaks in the system should be corrected immediately Th...

Страница 10: ...OA Do the following before shipping 1 Adequately package the system If possible package in the original shipping container 2 Ship prepaid 3 Include a statement of the observed deficiency 4 Indicate th...

Страница 11: ...obligation and Buyer s sole and exclusive remedy under the above warranties is limited to repairing using new or reconditioned parts or replacing free of charge except for labor if permanently install...

Страница 12: ...12 Controls Corporation of America 1501 Harpers Road Virginia Beach VA 23454 To Order Call 1 800 225 0473 or 757 422 8330 Fax 757 422 3125 www concoa com ADI 5470 B Certified ISO 9001...

Отзывы: