Concoa 547 Series Скачать руководство пользователя страница 8

8

connections (if compatible with the application) which indicates leaks by bubbling. To further check for leaks, 

or if the leak detection solution can not be used, close the cylinder valve for a period of time (recommended 

24 hours), and observe the high pressure gauge for a drop in pressure. If so indicated, recheck the CGA 

connection and all other high-pressure port connections.

6.  Never attempt to fix a leak under pressure. If leaks are detected, depressurize the system and retighten 

the connection. Begin again at step 3.

7. Slowly turn the line regulator knob clockwise. This will increase the pressure of the line.  Adjust to the 

desired working pressure and again check for leaks using the methods described above.

OPERATION

The arrow on the priority valve always points to the primary side; the bank opposite the primary side is 

considered the reserve side.  Starting with the arrow pointing to the right side, gas will flow from the right side 

cylinder.  As the gas in the primary side is depleted, the gas pressure will drop on the gauge of the primary 

regulator. When the pressure drops to the pressure setting of the reserve side regulator, flow will begin from 

the reserve cylinder; the inlet pressure on the primary side will stablize. This is called a changeover. At this 

point, the gas pressure on the reserve side (preset regulator) will drop.  This indicates that its time to change 

the cylinders on the primary side.  Before removing the nearly depleted primary cylinder, the priority valve 

should be rotated 180°. This makes the reserve cylinder the primary source. Remove the depleted cylinder 

and replace with a full cylinder. Before removing the cylinder be sure to close the cylinder valve and any 

other valves that connect the cylinder to the system.  Do not open any cylinder valves until all cylinders are 

replaced. The full, replacement cylinder is now the reserve cylinder. Note: while changing cylinders on one 

side, there will be no interruption in flow.  A depleted cylinder will have the following gas pressure remaining:

Model Number

547 1XXX

547 1XXX*

547 EXXX

547 2XXX

547 3XXX

547 4XXX

Cylinder Pressure

250-350 PSIG   

17-24 BAR

1050-1150 PSIG*  

  72-79 BAR*

1250-1500 PSIG 

 86-103 BAR

1800-2300 PSIG 

124-159 BAR

2800-3300 PSIG 

 193-228 BAR

3800-4300 PSIG 

262-297 BAR

*higher switch select setting for 5471XXX models

Gas will continue to flow from the primary side until the outlet pressure of the primary regulator matches the 

pressure setting of the reserve regulator. (The pressure setting of the priority valve regulator changes when 

the knob is turned 180°).  When the gas pressure stops dropping on the primary side regulator and starts 

to drop on the reserve side regulator, it is time to change the primary cylinder. The knob is rotated 180° to 

the reserve side changing priority before the depleted cylinder is changed.  It is helpful to maintain a log of 

cylinder pressure, noting which direction the arrow is pointing on the priority valve.  When the pressure gauge 

is very low and the reserve side indicates that gas has begun to flow from the reserve cylinder, it is time to 

rotate the knob and attach a full cylinder in reserve.

If the knob is not rotated before the empty cylinder is changed, two things can happen. First, gas may flow 

from the changed cylinder to the existing cylinder.  This is because the pressure setting of the regulator  on 

the primary side allows the regulator main valve to remain open.  Second, when the cylinder is changed, 

gas will begin to flow from the new cylinder, stopping flow from the existing cylinder. This means the existing 

cylinder may be partially empty.  After several cycles, it is possible that the reserve cylinder may empty 

shortly after a switchover occurs.  Always remember to rotate the knob on the priority valve regulator before 

changing a depleted cylinder.

To change 5471XXX models with switch select to higher switching pressure settings to achieve maximum 

outlet pressures of 800 psig. Locate the set screw that limits the travel of the right side selector knob, it is 

located on the side of the knob and is screwed into a slot in the knob. When set for the lower factory default 

switching pressure it is located closer to regulator body in that slot. Remove the set screw and rotate the 

right side selector knob clockwise two full rotations. Reinstall the set screw. With the arrow pointing to the 

Содержание 547 Series

Страница 1: ...nd Comply with These Instructions Controls Corporation of America 1501 Harpers Road Virginia Beach VA 23454 To Order Call 1 800 225 0473 or 757 422 8330 Fax 757 422 3125 www concoa com February 2016 A...

Страница 2: ...um inlet only With 547 XXX4 models an optional universal voltage remote alarm provides an audible and visual warning that a changeover is about to occur Pressing a button on the front of the remote al...

Страница 3: ...conditions and gas service Things to consider before removing the system from the box 1 Know the properties and special handling requirements of the gas being used Many specialty gases are quite dange...

Страница 4: ...lways rotate the priority valve 180 so that the arrow on the knob is pointing to the in use full side of the switchover CAUTION Always close all manifold station and cylinder valves on the nearly empt...

Страница 5: ...the cylinder decreases Manifolds installed in open locations should be protected from weather conditions During winter protect the manifold from ice and snow In summer shade the manifold and cylinders...

Страница 6: ...ad as shown in Figure 3 make sure the tape does not overlap the end of the fitting As the tape is wrapped in the direction of the thread spiral pull tightly on the end of tape so that the tape conform...

Страница 7: ...to avoid squashing the gasket into the gas line Keep extra gaskets on hand c Never use oil or grease on regulator or cylinder fittings as it may contaminate pure gases or create a fire hazard Installi...

Страница 8: ...X 547 3XXX 547 4XXX Cylinder Pressure 250 350 PSIG 17 24 BAR 1050 1150 PSIG 72 79 BAR 1250 1500 PSIG 86 103 BAR 1800 2300 PSIG 124 159 BAR 2800 3300 PSIG 193 228 BAR 3800 4300 PSIG 262 297 BAR higher...

Страница 9: ...ght side switching pressures MAINTENANCE On regular intervals the system should be checked for leaks and proper function see trouble shooting Any leaks in the system should be corrected immediately Th...

Страница 10: ...OA Do the following before shipping 1 Adequately package the system If possible package in the original shipping container 2 Ship prepaid 3 Include a statement of the observed deficiency 4 Indicate th...

Страница 11: ...obligation and Buyer s sole and exclusive remedy under the above warranties is limited to repairing using new or reconditioned parts or replacing free of charge except for labor if permanently install...

Страница 12: ...12 Controls Corporation of America 1501 Harpers Road Virginia Beach VA 23454 To Order Call 1 800 225 0473 or 757 422 8330 Fax 757 422 3125 www concoa com ADI 5470 B Certified ISO 9001...

Отзывы: