LCD, LED AND SOUND INDICATIONS

 

 
The Smoke Screen provides onboard status monitoring via an LCD, a multicolour LED and a sounder.  Indications displayed are: 
 

LCD Message 

LED Colour 

Buzzer Sound 

Relay status change 

Indication Meaning 

Heating up 

 

permanent. 

Nil. 

Nil. 

Smoke Screen heating to 
operating temperature. 

Heating Completed 

 

permanent. 

Nil. 

Nil. 

Smoke Screen ready to 
operate. 

Charging Battery 

 

flash once every 5 sec.  Nil. 

Nil. 

Battery charging. 

Alarm Set 

 

permanent. 

Nil. 

Nil. 

Smoke Screen has received 
a “Set” input from the Alarm 
Panel. 

-- 

 

flash. 

1 beep every 0.5 sec. 

Verification output n/c to open. 

Smoke Screen producing 
smoke. 

Thermal Fault 

 

permanent. 

1 long / 3 short beeps every 3 
mins. 

Status output n/c to open. 

Temperature too high or 
sensor failure. 

Heater Fault 

 

flash once every 5 sec.  1 long 2 short beep every 3 min. 

Status output n/c to open 

Smoke Screen not heating at 
the correct rate within 30 min 
of power on. 

Empty Fluid 

 

flash once every 5 sec.  1 long beep every 3 min. 

Liquid output n/c to open. 
Status output n/c to open. 

Fluid less than 10ml or no 
Bladder installed. 

Low Fluid 

 

flash once every 5 sec.  1 short beep every 5 min. 

Liquid output n/c to open. 

Fluid less than 50%. 

Battery Fault 

 

flash once every 5 sec.  3 short beep every 5 min. 

Battery output n/c to open. 

Battery lower than 18V or 
battery removed > 2 min. 

Tamper Fault 

 

flash once every 5 sec.  2 short beep every 5 min. 

Tamper status n/c to open. 

One or more of the access 
panels, or the external 

tamper if dip set to “off”, are 
open. 

Mains Fault 

 

flash once every 5 sec.  1 long 1 short beep every 3 min. 

Status output n/c to open. 

Main power failure. 

System Fault 

Any 

 

Any 

Status output n/c to open. 

Critical system fault. 

Service Mode Setting 

 

alternate flash. 

Nil. 

Nil. 

Smoke Screen in Service 
Mode. 

 

Once resolved, fault indications can be cleared by removing and restoring all power, mains and battery, from the Smoke Screen. 

 

Содержание Sentinel S70

Страница 1: ...Page 1 of 16 SENTINEL S70 INSTALLATION AND OPERATION MANUAL Version 16 December 2013 CAN T SEE IT CAN T STEAL IT ...

Страница 2: ...l help Once again thank you for your decision we hope that it s one that never needs to be tested Carl Gibbard Managing Director HOW DOES YOUR SMOKE SCREEN WORK Your Smoke Screen heats a non toxic fluid under pressure to create smoke or more accurately a thermally generated fog that obscures visibility to discourage intruders from entering your premises This fog is very persistent and will stay su...

Страница 3: ...ting 6 Nozzle changing 7 Controlling the smoke 7 Circuit board layout 8 Generic connection diagram 8 Energy saving mode 9 Service mode 9 Turbo smoke mode 9 Tamper 9 Fluid management 9 Battery management 10 Programming 11 Operation 12 Testing 12 LCD LED and sound indications 13 Action after every activation 14 Servicing and fluid replenishment 14 FAQ 14 Installer notes 15 ...

Страница 4: ...ng schematic STANDARD INSTALLATION A standard installation is configured in the following way The Smoke Screen wall or ceiling mounted in the appropriate location A Hold off PIR or similar device located within the same area as the Smoke Screen providing a confirmation signal to the Smoke Screen to start smoke production A Set command supplied by an Alarm Control Panel or equivalent in the form of...

Страница 5: ... Screen is 2 5 metres above the floor over the area to be protected and using a straight nozzle The maximum mounting height above floor level is 3 metres and there should be no obstacle within 1 metre of the smoke output nozzle INSTALLATION PROCEDURE 1 Site the Smoke Screen and fix the bracket to the wall or ceiling as appropriate 2 For wall mounting leave minimum 150mm clearance to ceiling 3 Fast...

Страница 6: ...er must fit the Smoke Screen using appropriate fasteners Suspension Kit All M8 Uni strut 1 x 1 metre Threaded bar 2 x 1 metre Fixings 2 x 38mm washer 4 x 25mm washer 6 x full nut 2 x drop in anchor 2 x channel nuts Wall mounting Wall mounting is achieved using a simple wall bracket 1 The bracket should be attached to a suitable wall Use appropriate fixings to secure the bracket to the wall We reco...

Страница 7: ... Smoke Screen Alarm Set Trigger and Hold Off that should be connected to clean contacts For the Smoke Screen to produce smoke all 3 sets of connections must be open circuit this can be changed to closed see Invert Trigger Mode in the Programming section If one set of connections is closed circuit then the Smoke Screen is prevented from producing smoke Hence the production of smoke is controlled us...

Страница 8: ...tus Output Liqud Status Battery Output Tamper Status Hold Off 100mA Output Tamper Verificatio n Output 100 mA Output Loop tamper pins or select Dip 3 to On if not connected to a device Verification changes state w hen the S70 fires n c and n o show n are w hen the S70 is not firing DC output for additional device Total S70 output must not be greater than 100mA DC output for additional device Total...

Страница 9: ... Block C A tamper open state provides only an indication of the event it does not automatically activate the Smoke Screen or prevent it from activation FLUID MANAGEMENT Fluid capacity There are 2 sizes 500ml or 1000ml of transparent bag containing Smoke Fluid for the Smoke Screen It can also be operated with an external 5000ml bottle please contact Concept Smoke Screen if you wish to use this faci...

Страница 10: ... second activation The Smoke Screen is capable of activating in the event of a battery fault or if the batteries are not fitted in the latter case to avoid battery fault indications the facility should be disabled see section under Programming The Smoke Screen is supplied with a set of batteries but they are not fitted on delivery Replacement batteries may be obtained from your Smoke Screen instal...

Страница 11: ...er the Section LCD LED and Sound indications Setting Smoke Time In the Setting Smoke Time display press to show the current smoke time set Use the and buttons to move up and down to select a time between 5 and 360 seconds in 5 second intervals Press to save the new setting and return to the higher level menu Press to return to the higher level menu without saving changes The delivery Smoke Time Se...

Страница 12: ... the LCD and the LED indicator will flash yellow once every 5 seconds a tamper indication will not on its own prevent the Smoke Screen from producing smoke When the Smoke Screen reaches the correct working temperature and a full Smoke Fluid Bag has been correctly installed the LED Indicator will go Green and the LCD Display will show the date and time Stopping smoke If the Hold Off is closed durin...

Страница 13: ... n c to open Smoke Screen not heating at the correct rate within 30 min of power on Empty Fluid flash once every 5 sec 1 long beep every 3 min Liquid output n c to open Status output n c to open Fluid less than 10ml or no Bladder installed Low Fluid flash once every 5 sec 1 short beep every 5 min Liquid output n c to open Fluid less than 50 Battery Fault flash once every 5 sec 3 short beep every 5...

Страница 14: ...nished by an engineer certified by the manufacturer If you are unsure ask the engineer for his certification ID card It is recommended that the Smoke Screen is checked and the fluid changed annually by the installer or Concept Smoke Screen Always ensure that the Smoke Screen has sufficient fluid or it will not produce smoke when needed It is recommended that the installer or Concept Smoke Screen a...

Страница 15: ...Page 15 of 16 INSTALLER NOTES ...

Страница 16: ...Page 16 of 16 Concept Smoke Screen Limited 1 2 North End Swineshead Lincolnshire PE20 3LR United Kingdom Tel 44 0 1205 821111 Fax 44 0 1205 820316 Email info smoke screen co uk www smoke screen co uk ...

Отзывы: