closing, 1 extra second at the maximum power or at the power selected 
with the “FORCE” trimmer, in such a way as to ensure positive engagement 
of the gate lock, if installed. If you wish to enable the Slam Lock function 
at maximum power, proceed as follows: make sure you have enabled 
Extended Menu 1, use the SELECT key to select blinking LED L6 and then 
press the SET key: LED L6 becomes steady on and programming will be 
completed. If you wish to enable the Slam Lock function at the power set 
with the “FORCE” Trimmer, repeat the operation described by pressing the 
SELECT key twice (LED L6 will blink rapidly) rather than once. Repeat the 
procedure if you wish to restore the initial configuration.

7. PREFLASHING/COURTESY LIGHT:

The control unit is factory set with the Preflashing and Courtesy Light 
functions disabled. If you wish to enable the Preflashing function proceed 
as follows: make sure you have enabled Extended Menu 1, use the SEL key 
to select blinking LED L7 and then press the SET key: the LED becomes 
steady on and programming will be completed. If you wish to enable the 
Courtesy Light function, repeat the operation described above, pressing 
the SET key twice (the LED will blink rapidly) rather than once. Repeat the 
procedure if you wish to restore the initial configuration.

Preflashing Operation: 

The 24 V~ 4W max. Flashing Light output will 

always switch on 3 seconds before the gate starts the closing operation.

Courtesy Light Operation:

 The 24 V~ 4W max. Courtesy Light output 

will switch on for 3 minutes whenever an opening command is transmitted

EXTENDED MENU 2

The control unit is factory set to allow direct selection exclusively of the main 
menu functions. If you wish to enable the functions described in Extended 
Menu 2, proceed as follows: select blinking LED no. 8 and press SET 
twice. The LED will start blinking alternately 1 1 0 1 1 0 1 1 0. This means 
there is a period of 30 seconds to select the functions in Extended Menu 2 
using the SELECT and SET keys and then, after a further 30 seconds, the 
control unit will revert to the main menu.

L1

SOFT STOP

ON

OFF

L2

SOFT START

ON

OFF

L3

DS 1 IN OPEN

ON

OFF

L4

HOLD-TO-RUN

ON

OFF

L5

FOLLOW ME

ON

OFF

L6

PAUSE FLASHING

ON

OFF

L7

ALWAYS CLOSE

ON

OFF

LEV

MENU

2 FLASHES

1. SOFT STOP:

The control unit is factory set with the Soft Stop function disabled. If you 
wish to enable the function, proceed as follows: ensure you have enabled 
Extended Menu 2 and then use the SEL key to select blinking LED L1 
and press the SET key; at the same time LED L1 becomes steady on and 
programming will be completed. With this function enabled at the end of the 
movement the control unit will reduce operator force to zero gradually in a 
2 second interval. Repeat the procedure if you wish to restore the previous 
configuration.

2. SOFT START:

The control unit is factory set with the Soft Start function disabled. If you 
wish to enable the function, proceed as follows: ensure you have enabled 
Extended Menu 2 and then use the SEL key to select blinking LED L2 
and press the SET key; at the same time LED L2 becomes steady on 
and programming will be completed. With this function enabled at the start 
of each movement the control unit will regulate start-up of the operator, 
gradually increasing the force from the minimum to the value set by the 
“FORCE” trimmer during the first 2 seconds of operation. Repeat the 
procedure if you wish to restore the previous configuration.

Note:

 when the Soft Start function is enabled the control unit automatically 

disables the Starting Torque function, while if Soft Start is disabled then 
Starting Torque is automatically enabled.

3. DS 1 also in opening:

The control unit allows the operation of input DS1 to be modified. If you 
want  DS 1 to operate also during opening (momentary stopping of the 
gate, as soon as the photocell is freed the control unit resumes the opening 
movement), proceed as follows: ensure you have enabled Extended Menu 
2 and then press the SEL key to select blinking LED L3 and press the SET 
key: LED L3 becomes steady on and programming will be completed.

as follows if you wish to enable the function: make sure you have enabled 
extended Menu 1, use the select key to select blinking LED L1 and then 
press the SET key; at the same time LED L1 will become steady on and 
programming will be completed.
Repeat the procedure if you wish to restore the previous configuration.

2. PED MOT. T. (Programming of pedestrian opening motor time of 
max 4 minutes):

The control unit is factory set with Motor Time (Pedestrian opening) of 10 
seconds without any deceleration.
If the pedestrian motor time must be changed, programming must be 
carried out with the gate closed as follows: ensure you have enabled 
Extended Menu 1, use the SELECT key to select blinking LED L2 and 
then press the SET key momentarily. The Operator will start the Opening 
cycle; when the gate reaches the desired initial deceleration position press 
the SET key again: LED L2 will start blinking more slowly and the Operator 
performs the deceleration; when the desired position is reached press the 
SET key to terminate the Opening cycle. At this point LED L2 returns to the 
normal blinking speed and the Operator restarts in the Closing movement; 
repeat the operations described above for the Closing movement.
If you do not require the control unit to perform the deceleration, during 
programming, when the opening and closing cycle has been completed 
press the SET key twice consecutively rather than just once.
During programming, instead of the SET key on the control unit you can use 
the button on the remote, providing the remote has been saved beforehand

3. DECELERATION:

As indicated above, the control unit allows a deceleration stage to be 
programmed during opening and closing, while with the Automatic 
Programming function the deceleration stage is included automatically. 
However, if no deceleration is required, this stage can be inhibited. In this 
manner, when using Automatic Programming the Deceleration stage will 
no longer be included, while if the Operator Times Programming function 
is used the option of specifying a deceleration stage during opening and 
closing will no longer be available. If, before excluding the deceleration 
stage it had already been programmed using the Operator Times 
Programming function, programming must be repeated from the beginning. 
If the deceleration stage is to be excluded proceed as follows: make 
sure you have enabled Extended Menu 1, use the SELECT key to select 
blinking LED L3 and then press the SET key: LED L3 becomes steady on 
and programming will be completed. Repeat the procedure if you wish to 
restore the previous configuration.

4. REMOTE CODE PGM (Remote Programming of Radio remote 
controls):

The control unit allows the transmission code to be programmed remotely 
without acting directly on the control unit SELECT key.
Remote programming of a Radio remote control is performed as follows: 
send, continuously for a time in excess of 10 seconds, the code of a 
previously saved remote; at the same time the control unit switches 
to programming mode as described above for the CODE LED in the 
main menu. If a pedestrian code previously stored in the control unit is 
transmitted continuously, the control unit switches to programming of a 
new pedestrian code. The control unit is factory set with transmission code 
remote programming disabled; proceed as follows if you wish to enable the 
function: make sure you have enabled extended Menu 1, use the SELECT 
key to select blinking LED L4 and then press the SET key; at the same time 
LED L4 will become steady on and programming will be completed. Repeat 
the procedure if you wish to restore the previous configuration.

5. RELEASE STROKE:

The control unit is factory set with the Release Stroke function disabled. To 
enable the Release Stroke function at maximum power, proceed as follows: 
make sure you have enabled Extended Menu 1, use the SELECT key to 
select blinking LED L5 then press the SET key, LED L5 becomes steady on 
and the programming procedure will be completed. If you wish to enable 
the Release Stroke function at the power set with the “FORCE” trimmer, 
repeat the procedure described above, press the SELECT key twice (LED 
L5 will blink rapidly) rather than just once. Repeat the procedure if you wish 
to restore the initial configuration.
This procedure makes it possible to facilitate release of the gate lock and 
thus allow correct execution of the opening stroke. With this function, before 
starting the opening stroke the control unit sends a closing command for 2 
seconds with the thrust force associated with the selection made.

6. SLAM LOCK:

The control unit is factory set with the Slam Lock function disabled. This 
function consists in adding, in the presence of a deceleration stage during 

Содержание CU-24V-1M

Страница 1: ...USER S MANUAL Control unit comunello com ISTRUZIONI D USO E DI INSTALLAZIONE INSTALLATIONS UND GEBRAUCHSANLEITUNG INSTRUCIONS D UTILISATION ET D INSTALLATION INSTRUCCIONES DE USO Y DE INSTALACION Cod...

Страница 2: ...ON OFF L5 RELEASE STROKE ON OFF L6 SLAM LOCK ON OFF L7 COURTESY LIGHT ON OFF LEV LEV 1 FLASH ID LED L1 SOFT STOP ON OFF L2 SOFT START ON OFF L3 DS 1 IN OPEN ON OFF L4 HOLD TO RUN ON OFF L5 FOLLOW ME...

Страница 3: ...C 24V SLIDING GATE CU 24V 1M ID Description Cable type Lenght 1m to 20m Lenght 20m to 50m 1 Main power supply FG7 CEI 20 22 CEI EN 50267 2 1 2x1 5mm2 2x2 5mm2 2 Flashing light 2x0 5mm2 2x1 0mm2 4A 6A...

Страница 4: ...RSA CHIUDI N C END CLOSE N C FOTOCELLULA DS N C ATTIVA IN CHIUSURA PHOTCELL DS N C ACTIVE IN CLOSING FOT GND STOP GND GND FCA DS1 GND PP ANT ANT FCC CN2 LAMPEGGIANTE FLASHING LIGHT 24V 4W CN1 M MOTORE...

Страница 5: ...reserved ITALIANO FORT like below Led opening direction OFF OPENS TO THE RIGHT Inner side view OPENING DIRECTION 1 MOTOR CONFIGURATION FORT FORT like below Led opening direction ON OPENS TO THE LEFT I...

Страница 6: ...SALIENT DO NOT CHANGE the configuration Opens to the left closes to the right left profile view as in the image SALIENT BLACK ON M1 RED ON M1...

Страница 7: ...directives 2004 108 EC Directive EMC Directive 2006 95 CE Directive and that all the rules and or technical specifications shown below have been applied EN61000 6 2 EN61000 6 3 EN62233 2008 EN301489 1...

Страница 8: ...The rear of the box is equipped with knockouts for wall fixing knockouts for fixing holes using anchor bolts or holes for fixing with screws Take all the measures required to ensure the installation p...

Страница 9: ...ttons are used to control the gate operation is as follows the first command opens the gate until motor time or until the gate reaches its opening limit position the second command closes the gate if...

Страница 10: ...the latter will be controlled thus effectively relinquishing the security of the rolling code system 4 CONDO The Condominium function means that during the opening movement or during the pause time th...

Страница 11: ...become steady on and programming will be completed Repeat the procedure if you wish to restore the previous configuration 2 PED MOT T Programming of pedestrian opening motor time of max 4 minutes The...

Страница 12: ...upward each additional LED corresponds to a higher power level Use the SEL key to scroll through the different power levels for each selected power level the top LED will blink for example selecting l...

Страница 13: ...FRATELLI COMUNELLO S P A AUTOMATION GATE DIVISION Via Cassola 64 C P 79 36027 Ros Vicenza Italy Tel 39 0424 585111 Fax 39 0424 533417 info comunello it www comunello com...

Отзывы: