Net Configuration
By default, all System 2500 units are configured as standalone unit. To setup a network, a master and a
minimum of one slave unit are required. The following modes are supported:
Mode
OFF, Slave, Master
Master poll
slave(s) heartbeat polling time
Slave poll
master heartbeat polling time
Network sensors
Sensor used for all networked units.
Internal: Each unit shall use its own sensors
Master: Each unit shall use master sensors
Average: Sensors from all networked units are used as averaging
Figure 23. Network configuration
Scan
Use network scan function to discover all connected systems through their IP addresses. All
system must be connected to the same network. If a scan is successful, all of the IP addresses
get indexed and their current online/offline status are also reflected in the network mapping.
Figure 24. Network scan
Note: Total units value must reflect all the configured system.