OPERATION 

Continued

Voltage Across Sensing Resistor

I         Loop Current in Milliamperes
R         Resistance in Ohms
V         Voltage in Volts

V = I X R / 1000                        Formula 2

Maximum Loop Resistance for 4 - 20 mA Output
Transmitter

Rmax      Maximum Loop Resistance
Vsup      Supply Voltage

Rmax = (Vsup - 10 V) / 20 mA            Formula 3

Gain & Zero Adjustments

Gain & Zero are set using switch 1.  See Figure 3.  Set-
tings are stored in EEPROM and are retained when power
is removed. Adjust Zero first to produce 4.08 mA output
0.5% of full scale).  After  Zero is set input  99 switch
closures  and  adjust the Gain (Span)  to produce 19.92
mA (99.5% of full scale).  Follow instructions exactly or
settings may not be stored permanently.

Switch 1 Controls
      
1

Set Output to full scale

      2

Ramp / One Shot Mode

      3

Set One One Shot Time Period

U   4

Increase parameter

D   5

Decrease parameter

Z    6

Select Zero adjust

G   7

Select Gain adjust

R    8

Reset

Zero Adjust
1.   Move R  to ON
2.   Move U to ON
3.   Move D to ON
4.   Move R to OFF
5.   Move U to OFF
6.   Move D to OFF
7.   Move Z to ON
8.   Move U or D  ON  & OFF as required
9.   Move U or D to OFF
10.  Move Z to OFF.

Gain  Adjust
1.   Move R  to ON
2.   Move U to ON
3.   Move D to ON
4.   Move R to OFF
5.   Move U to OFF
6.   Move D to OFF
7.   Move SW 1 to ON
10.   Move G to ON
11. Move U or D  ON & OFF as required
12. Move U or D to OFF
13. Move G to OFF.
14. Move SW1 to OFF

Rain Detector Time Period Transfer Function

T         Time in Minutes
I         Loop Current in Milliamperes

T =  (I - 4mA) / 16   X 80 minutes                    Formula 4

Example:
I    -    8 mA
T  = (8mA - 4mA) /16  X  80 minutes = 20 minutes

One Shot Time Period Adjust
1.   Move R  to ON
2.   Move U to ON
3.   Move D to ON
4.   Move R to OFF
5.   Move U to OFF
6.   Move D to OFF
7.   Move SW 3 to ON
8.   Move U or D  ON & OFF as required
9.   Move U or D to OFF
10. Move SW3 to OFF

Note: Normal program execution is suspended while
parameters are stored.  Allow ten seconds for output to
stabilize after final step of calibration.

Switch 1 loads the rainfall counter to assist in calibration.
Closing Switch 1 loads 99 bucket tips.

Содержание A70-R

Страница 1: ...nfall Transmitter Instruction Manual Document 1142H ISO 9001 Registered Comptus Inc 342 Lyndeboro Rd New Boston NH USA Phone 603 487 5512 Fax 603 487 5513 E mail sales comptus com Comptus Inc ISO 9001...

Страница 2: ...t If bucket tips occur faster than the selected time period the output will remain continuously at full scale Running average and other signal output formats are available Contact Comptus for addition...

Страница 3: ...eries with the 4 20 mA loop and derives its power from the loop Each display in the loop introduces a 2 5 volt drop A 24 Vdc source of excitation is recom mended for applications involving the A70 LPD...

Страница 4: ...20 0103 22 0165 24 0262 Figure 4 Graph of Maximum Loop Resistance Figure 3 Component Layout voltage E xcitation M inim um E xcitation V oltage 10 14 18 22 26 300 100 0 200 R esistance T otal L oop 60...

Страница 5: ...R METER OR COMPUTER X3 1 X3 2 X2 1 X2 2 X1 1 X1 2 HOT NEU GND A70 E POWER SUPPLY AC MAINS Figure 5 Transmitter Connection Diagram Figure 6 Multiple Transmitters Sharing One Power Supply NO POLARITY RA...

Страница 6: ...he loop current from the Transmitter in ramp mode increases in a staircase like manner 1 for each 01 inch of rain See Figure 7 When 1 inch of rainfall is accumulated output signal is 20 mA the output...

Страница 7: ...n mA An output of 8 mA indicates a 20 minute time period in rain detector mode Figure 8 Rain Detector Mode Transfer Function Figure 9 Rain Detector Timer Calibration 4 Current 12 8 mA 20 16 Loop Bucke...

Страница 8: ...Zero Adjust 1 Move R to ON 2 Move U to ON 3 Move D to ON 4 Move R to OFF 5 Move U to OFF 6 Move D to OFF 7 Move Z to ON 8 Move U or D ON OFF as required 9 Move U or D to OFF 10 Move Z to OFF Gain Adj...

Страница 9: ...ml 0 2 mm 6 48 ml 0 01 inch 8 24 ml 1 Wet rain gage surfaces 2 Refer to Table 2 Pour water into gage at rate of approximately 0 5 ml second 3 Check that bucket tips within 2 as averaged over 5 tips of...

Страница 10: ...r piece of equipment This does two things First it requires you to organize the situation so it can be explained to another Secondly it may turn out that you are so familiar with the situation that yo...

Страница 11: ...s any other liability in connection with the sale of its products THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE SOME STATES DO NOT ALL...

Страница 12: ...12 342 Lyndeboro Rd New Boston NH USA Phone 603 487 5512 Fax 603 487 5513 E mail sales comptus com Comptus Inc ISO 9001 Registered...

Страница 13: ...Lyndeboro Rd New Boston NH USA Phone 603 487 5512 Fax 603 487 5513 E mail sales comptus com Comptus Inc ISO 9001 Registered IMPORTANT Please check your order on re ceipt to be certain all listed acce...

Страница 14: ...14 342 Lyndeboro Rd New Boston NH USA Phone 603 487 5512 Fax 603 487 5513 E mail sales comptus com Comptus Inc ISO 9001 Registered...

Отзывы: