Power Meter
–
POM200
User Manual v1
www.compressedairalliance.com
8
Altitude
3000m Max
IP degree of protection
IP20 conforming to IEC 60629
Alarm
Setting
Voltage and current, each phase, AVG
Output form
Buzzer, Relay
Instantaneous rms Values
Voltage
U, UTH2, UTH3, UTH4 (Per Phase, AVG)
Current
I, ITHD2, ITHD3, ITHD4 (Per Phase, AVG)
Power
P, FQ, S, PF (Per Phase, SUM)
Energy
EP, EFQ, ES, Freq (Per Phase, SUM)
over 999.9GWh, value resets
UTHD (%)
UTHD, THD2, THD3, THD4 (Per Phase, AVG)
ITHD (%)
ITHD, THD2, THD3, THD4 (Per Phase, AVG)
Update Rate
Data acquisition rate
400ms
Display update rate
0.5s
Energy storage interval
10mis (default)
(prevent losing energy when power off)
Calibration
Current
Per phase, all
Voltage
Per phase, all
Power factor
Per phase, all
EMC
Electrostatic discharge
Level IV (IEC61000-4-2)
Immunity to radiated
fields
Level III (IEC61000-4-3)
Immunity to fast
transients
Level IV (IEC61000-4-4)
Содержание POM200
Страница 1: ...www compressedairalliance com 1 User Manual Power Meter Din Rail with Display Model POM200...
Страница 10: ...Power Meter POM200 User Manual v1 www compressedairalliance com 10 Power Meter Dimensions 71 mm 2 8 95 mm 3 7...
Страница 19: ...Power Meter POM200 User Manual v1 www compressedairalliance com 19 3PH4W no VT...
Страница 20: ...Power Meter POM200 User Manual v1 www compressedairalliance com 20 3PH4W with VT...
Страница 21: ...Power Meter POM200 User Manual v1 www compressedairalliance com 21 3PH3W no VT 3PH3W with VT...
Страница 22: ...Power Meter POM200 User Manual v1 www compressedairalliance com 22 1PH3W 1PH2W...
Страница 23: ...Power Meter POM200 User Manual v1 www compressedairalliance com 23 Input Output Wiring diagram...