Compressed Air Alliance POM200 Скачать руководство пользователя страница 11

 

 

 

Power Meter 

 POM200 

User Manual v1 

 

www.compressedairalliance.com  

11 

Rogowski Coil Specifications 

 

500 Amps 

1,000 Amps 

3,000 Amp 

Coil Length 

200 mm or 7.87”

 

350 mm or 13.78”

 

510 mm or 20.08”

 

Window Size 

50 mm or 1.97”

 

100 mm or 3.94”

 

150 mm or 5.91”

 

Ratio  

Calibrated: 

85mV / kA@50Hz / 100mV / kA@50Hz 

Uncalibrated: 

110mV / kA@50Hz 

Read Accuracy  

Calibrated: 

<0.5% (central position, 25

Uncalibrated: 

< 5% tolerance (central position, 25

Maximum Current 
Measurable 

100kA 

Coil Resistance 

from 100 to 250 Ω

 

Position Error 

±1% maximum 

Phase error 

≤0.5°

 

Shielded 

00% coil, 100% output cable 

Couplings 

PA6 UL 94 V-O rated 

Voltage Insulation 

Coil: 3000V 

Signal cable: 1000V 

Compliance 

LVD EN 61010-1:2010 

EMC EN 61326-1:2013 

Safety 

1000V CATIII ,600V CATIV 

Materials 

Coil & cable: Thermoplastic rubber, flame retardant UL 94 

V-0 rated 

Lead Length 

5 meters 

Operation 
Temperature 

-20

 to +70

 

-4°F to 158°F 

Storage Temperature 

-30

 to +90

 

-22°F to 194°F 

Installation Type 

Temporary or permanent installation 

Warranty 

12 months 

Содержание POM200

Страница 1: ...www compressedairalliance com 1 User Manual Power Meter Din Rail with Display Model POM200...

Страница 2: ...iralliance com 2 Table of Contents Notices 3 Warnings 3 Multi Function Power Meter 4 Specifications 5 Installation Mechanical 13 Installation Electrical 15 Operating Instructions 25 Warranty 37 Need h...

Страница 3: ...stall or use the product you accept that you have read understood and complied with this manual Compressed Air Alliance endeavours to make the content of this manual correct but is not responsible for...

Страница 4: ...e understanding of energy usage eg spikes variation usage Identify phase and voltage issues Identify power factor and harmonic issues Compare and challenge your energy bill Improve efficiency and redu...

Страница 5: ...play size 39 m x 32 mm 1 5 x 1 3 Display resolution 220 x 170 dots Available clamp sensors Rogowski coil 500A or 1 000A or 3 000A Sampling rate 8 000 samples per second Harmonic 52th Max Dimensions 76...

Страница 6: ...i coil specification 85mV kA 50Hz 0 5 Voltage 0 2 from 100V to 500V L L and L N Power factor 0 005 from 10 to 120 Active Apparent Power IEC62053 22 Class 0 5 Reactive power IEC62053 21 Class 2 Frequen...

Страница 7: ...monics Communication RS485 Modbus RTU Connection Screw terminals 2 5mm2 0 1 Interval 5 08mm 0 2 Digital Output 1 digital output 2 ports controlled by Modbus 2 5kVrms insulation Maximum Switching Power...

Страница 8: ...PF Per Phase SUM Energy EP EFQ ES Freq Per Phase SUM over 999 9GWh value resets UTHD UTHD THD2 THD3 THD4 Per Phase AVG ITHD ITHD THD2 THD3 THD4 Per Phase AVG Update Rate Data acquisition rate 400ms Di...

Страница 9: ...ted emissions Class B EN55022 Standard compliance EN 62052 11 EN61557 12 EN 62053 21 EN 62053 22 EN 62053 23 EN 50470 1 EN 50470 3 EN 61010 1 EN 61010 2 EN 61010 031 Modbus RS485 Communication Transmi...

Страница 10: ...Power Meter POM200 User Manual v1 www compressedairalliance com 10 Power Meter Dimensions 71 mm 2 8 95 mm 3 7...

Страница 11: ...ance central position 25 Maximum Current Measurable 100kA Coil Resistance from 100 to 250 Position Error 1 maximum Phase error 0 5 Shielded 00 coil 100 output cable Couplings PA6 UL 94 V O rated Volta...

Страница 12: ...00 Amp A Windows size A 50 mm 105 mm 155 mm B Windows size B 60 mm 100 mm 150 mm C Coil Outer Diameter 66 mm 121 mm 171 mm D Coil section 8 mm E Lead Cable Total Length 5 meters F Coil length 200 mm 3...

Страница 13: ...ead to malfunctions and may damage the product or system The system must be disconnected from any power supply during maintenance work Certain parts of the product may carry hazardous live voltage e g...

Страница 14: ...with the main power supply disconnected Local and national regulations must be fully observed Step 1 Locate clip on the Rogowski Coil base unit Step 2 Unscrew clip and pull out coil from base unit St...

Страница 15: ...njuries or even death The user shall take all measures necessary to protect against electrical shock Notes Always check the wires to make sure they are wired correctly Consider all local and national...

Страница 16: ...put positive A phase current Current I Input 2 I32 A phase current input negative 3 I22 B phase current input positive B phase current 4 I21 B phase current input negative 5 I12 C phase current input...

Страница 17: ...com 17 Port Number Port Name Port Function Remarks 11 Vn N phase voltage input Voltage V input 12 V3 C phase voltage input 13 V2 B phase voltage input 14 V1 A phase voltage input 15 NC Not connected N...

Страница 18: ...ent It may also void the warranty Before installing the power meter make sure it is rated for your system refer to Specification section Notes Rcoil Rogowski coil secondary output voltage can not be o...

Страница 19: ...Power Meter POM200 User Manual v1 www compressedairalliance com 19 3PH4W no VT...

Страница 20: ...Power Meter POM200 User Manual v1 www compressedairalliance com 20 3PH4W with VT...

Страница 21: ...Power Meter POM200 User Manual v1 www compressedairalliance com 21 3PH3W no VT 3PH3W with VT...

Страница 22: ...Power Meter POM200 User Manual v1 www compressedairalliance com 22 1PH3W 1PH2W...

Страница 23: ...Power Meter POM200 User Manual v1 www compressedairalliance com 23 Input Output Wiring diagram...

Страница 24: ...Power Meter POM200 User Manual v1 www compressedairalliance com 24 Rogowski Coil Connection Rogowski coil specification 85mV kA 50Hz 0 5...

Страница 25: ...epending on which measurement option is selected 5 Navigation Buttons Navigation Moving Left and Right Long press press and hold the up button to move left Long Press press and hold the down button to...

Страница 26: ...nu from any screen or to exit a screen press the Menu Quit button To view measurement data Step 1 From the Main menu press the Up or Down buttons to move to the Data Menu Step 2 Click Enter to access...

Страница 27: ...press the Up or Down buttons to move up or down Short press Enter to access the secondary menu Voltage U Voltage measurement options from top to bottom U voltage UTH2 2 harmonics UTH3 3 harmonics volt...

Страница 28: ...I2 0 DI1 0 ETF1 DI2 0 DI1 1 ETF2 DI2 1 DI1 0 ETF3 DI2 1 DI1 1 Not Available Voltage Harmonics UTHD UTHD menu options Uthd total harmonics voltage distortion THD2 2 harmonics voltage distortion THD3 3...

Страница 29: ...ep 2 Click enter to access the System Settings To return to the main menu from any screen or to exit a screen press the Menu Quit button Set Menu System Setting Menu Options Wire Set the Mode eg 3PH3W...

Страница 30: ...tem 1PH2W_LL 1 phase 2 wire L_L system 1PH2W_LN 1 phase 2 wire L_N system 1PH3W_LLN 1 phase 2 wire L_L_N system Vcon select voltage connection type DirectCon Direct voltage connection 3VT 3 Voltage se...

Страница 31: ...Sec mV is the corresponding output of Rogowski coil For example Coil ratio 85mV kA 50Hz Default Ratios Rcoil Pri 1 000A Rcoil Sec 85mV If you want to change to 100A rated change the Rcoil Pri to 100A...

Страница 32: ...ssword is 1000 If you need to change the password Long press the Up or Down button to move to the next previous number Short press the Up or Down button to change the highlighted number Click Enter to...

Страница 33: ...for that option UMax Sub Menu Screen In the max min voltage Umax Umin and max min current Imax Imin sub menus you can set the max or min values for current and voltage and choose whether to enable th...

Страница 34: ...press the Up or Down buttons to move to the Cal Menu Step 2 Click Enter to access the Calibration Menu Note the default password is 1000 To return to the main menu from any screen or to exit a screen...

Страница 35: ...ic phase A B or C or if you want to calibrate all phases Click Enter to accept the change Calibrate Voltage U To calibrate Voltage Short press the Up or Down button to cycle through calibration option...

Страница 36: ...see the model number of the power meter the firmware version and the serial number To access the Information screen Step 1 From the Main menu press the Up or Down buttons to move to the Info Menu Step...

Страница 37: ...f warranty The following damage is excluded from this warranty Improper use and non adherence to the user manual Use of unsuitable accessories External influences e g damage caused by vibration damage...

Страница 38: ...o 1200 2400 4800 9600 etc Error detection CRC16 cyclic redundancy check Modbus communications settings Before communicating with the device using Modbus RTU protocol use the Power Meter s Display to c...

Страница 39: ...e Function Name Behaviour Decimal Hexa decimal 3 03H Read Holding Registers Read present HEX from one or more registers 16 10H Write Multiple Registers Write present HEX on multiple registers Register...

Страница 40: ...6 16 bit unsigned integer 0 to 65535 Int16 16 bit signed integer 32768 to 32767 UInt32 32 bit unsigned integer 0 to 4 294 967 295 UInt64 64 bit unsigned integer 0 to 18 446 744 073 709 551 615 UTF8 8...

Страница 41: ...ts Command Register Number 16 bits Data Length 8 bits Command Register Value 16 bits X N CRC 16 bits 1 247 16 High 8 bits Low 8 bits High 8 bits Low 8 bits N 2 Command Parameter Low 8 bits High 8 bits...

Страница 42: ...s High 8 bits Low 8 bits High 8 bits Low 8 bits Function code 0x10 16 Operation Function code 0x10 16 is used to configure the meter Request data format No Alias Type Range decimal Description 1 Salve...

Страница 43: ...Numbers UInt16 1 123 Big Endian 5 CRC 16 Check UInt16 Little Endian Attention Function code 0x10 16 can only write data to Command Register that is only registers starting from 300 can be written dat...

Страница 44: ...ing order 9 CRC 16 Check UInt16 50093 C3AD Little Endian Sending order Request data send as follows 01 10 01 2C 00 02 04 03 ED 00 01 AD C3 If the configured data is right the meter will response data...

Страница 45: ...UInt8 3 3 Registers Start address UInt16 Big Endian Sending order 4 Registers Numbers UInt16 1 125 Big Endian Sending order 5 CRC 16 Check UInt16 Little Endian Sending order Response data format No Al...

Страница 46: ...3 4 Registers Numbers UInt16 6 0x0006 5 CRC 16 Check UInt16 46647 0xB637 Request data send as follows 01 03 08 63 00 06 37 B6 Response data as follows 01 03 0C 43 5C 00 00 43 5D 00 00 43 5E 00 00 14 A...

Страница 47: ...t16 Little Endian Exception code of MODBUS Code hexadecimal Name Meaning 0x01 ILLEGAL FUNCTION The function code received in the query is not an allowable action for the meter 0x02 ILLEGAL DATA ADDRES...

Страница 48: ...e W 1 UInt16 1 12 Month Write W 1 UInt16 1 31 Day Write W 1 UInt16 0 23 Hour Write W 1 UInt16 0 59 Minute Write W 1 UInt16 0 59 Second Set Communications Command Number Action R W Size Type Units Rang...

Страница 49: ...3PH3W 4 1PH3W_LLN Write W 1 UInt16 Hz 50 60 Nominal Frequency VT Primary Write W 2 UInt32 V 0 VT Secondary RealValue 1000 Write W 2 UInt32 V 0 CT Primary Write W 2 UInt32 A 0 CT Secondary RealValue 10...

Страница 50: ...Set Digital Output Command Number Action R W Size Type Units Range Description 1005 Write W 1 UInt16 0 1 1 Relay output on 0 Relay output off Choose Tariff Command Number Action R W Size Type Units R...

Страница 51: ...Reset Tariff 1 2 3 4 Reset Peak Demand Command Number Action R W Size Type Units Range Description 2002 Write W 1 UInt16 1 1 Reset Peak Demand Modbus Register List Meter Register Alias Register Addre...

Страница 52: ...ions Register Alias Register Address Action R WC Size Type Units Description Address 80 R WC 1 UInt16 1 to 247 Baud Rate 81 R WC 1 UInt16 0 1200 1 2400 2 4800 3 9600 4 19200 5 38400 6 57600 Parity 82...

Страница 53: ...lue 1000 Rcoil Primary 100 R WC 2 UInt32 A Rcoil Secondary 102 R WC 2 UInt32 mV RealValue ReadValue 1000 Voltage Connection 104 R WC 1 UInt16 0 Direct Connect 1 3 VT Current Connection 105 R WC 1 UInt...

Страница 54: ...ted Command 424 R 1 UInt16 Command Result 425 R 1 UInt16 0 Valid Operation 80 Invalid Command 81 Invalid Parameter 82 Invalid Number of Parameters 83 Operation Not Performed Basic Data Power factor fr...

Страница 55: ...DPF Avg 2014 R 2 Float32 Average Of DPF1 DPF2 DPF3 Frequency Freq1 2016 R 2 Float32 Hz Phase 1 Frequency Freq2 2018 R 2 Float32 Hz Phase 2 Frequency Freq3 2020 R 2 Float32 Hz Phase 3 Frequency FreqAv...

Страница 56: ...x I1THDy 2035 R 2 Float32 Phase 1 y times harmonics current distortion I2THDy 2037 R 2 Float32 Phase 2 y times harmonics current distortion I3THDy 2039 R 2 Float32 Phase 3 y times harmonics current di...

Страница 57: ...HD I1THx 2059 R 2 Float32 V Phase 1 x times harmonics current I2THx 2061 R 2 Float32 V Phase 2 x times harmonics current I3THx 2063 R 2 Float32 V Phase 3 x times harmonics current ITHx Avg 2065 R 2 Fl...

Страница 58: ...tion U2THDx 2085 R 2 Float32 Phase 2 X times harmonics voltage distortion U3THDx 2087 R 2 Float32 Phase 3 X times harmonics voltage distortion UTHDx Avg 2089 R 2 Float32 Average of U1THDx U2THDx U3THD...

Страница 59: ...al harmonics voltage distortion U2THD 2109 R 2 Float32 Phase 2 total harmonics voltage distortion U3THD 2111 R 2 Float32 Phase 3 total harmonics voltage distortion UTHD Avg 2113 R 2 Float32 Average of...

Страница 60: ...2 Float32 V Phase 3 z times harmonics voltage UTHz Avg 2137 R 2 Float32 V Average of U1THz U2THz U3THz Current I1 2139 R 2 Float32 A Phase 1 Current I2 2141 R 2 Float32 A Phase 2 Current I3 2143 R 2 F...

Страница 61: ...Fundamental Reactive Power Phase 1 FQ2 2165 R 2 Float32 kVAR Fundamental Reactive Power Phase 2 FQ3 2167 R 2 Float32 kVAR Fundamental Reactive Power Phase 3 FQTotal 2169 R 2 Float32 kVAR Total Fundam...

Страница 62: ...4 R 2 UInt32 kWh Active Energy Import Phase 3 EPsumImp 4006 R 2 UInt32 kWh Total Active Energy Import Phase All EP1Exp 4008 R 2 UInt32 kWh Active Energy Export Phase 1 EP2Exp 4010 R 2 UInt32 kWh Activ...

Страница 63: ...l Apparent Energy ES1Imp 4048 R 2 UInt32 kVAh Apparent Energy Import Phase 1 ES2Imp 4050 R 2 UInt32 kVAh Apparent Energy Import Phase 2 ES3Imp 4052 R 2 UInt32 kVAh Apparent Energy Import Phase 3 ESsum...

Страница 64: ...Float32 kW Active Power Peak Demand PPeakDemandDate 5004 R 4 Date time Active Power Peak Demand Date Time QDemand 5008 R 2 Float32 kW Reactive Power Present Demand QPeakDemand 5010 R 2 Float32 kW Rea...

Страница 65: ...R 2 Float32 kW Current I2 Peak Demand I2PeakDemandDate 5036 R 4 Date time Current I2 Peak Demand Date Time I3Demand 5040 R 2 Float32 kW Current I3 Present Demand I3PeakDemand 5042 R 2 Float32 kW Curr...

Страница 66: ...quality analysis values use the following abbreviations Fundamental phase current rms I1 Fundamental phase voltage rms V1 Total harmonic distortion of the phase current Total harmonic distortion of t...

Страница 67: ...d exported means negative real power flow P Power factor PF Power factor PF is the ratio of real power P to apparent power S and is a number between 0 and 1 An ideal purely resistive load has no react...

Страница 68: ...wer Meter POM200 User Manual v1 www compressedairalliance com 68 Compressed Air Alliance Pty Ltd Phone Australia 1300 558 526 E mail sales compressedairalliance com Website www compressedairalliance c...

Отзывы: