![Compressed Air Alliance POM200 Скачать руководство пользователя страница 46](http://html1.mh-extra.com/html/compressed-air-alliance/pom200/pom200_user-manual_2647447046.webp)
Power Meter
–
POM200
User Manual v1
www.compressedairalliance.com
46
For example: Read Voltage A, B, C value (Address starts 2147)
No.
Alias
Type
Range
(decimal)
Range
(hexadecimal)
Description
1
Salve ID
UInt8
1
0x01
2
Function code
UInt8
3
0x03
3
Registers Start
address
UInt16
2147
0x0863
4
Registers Numbers
UInt16
6
0x0006
5
CRC-16 Check
UInt16
46647
0xB637
Request data send as follows: 01 03 08 63 00 06 37 B6
Response data as follows: 01 03 0C 43 5C 00 00 43 5D 00 00 43 5E 00 00 14 AC
No.
Alias
Type
Range
(decimal)
Range
(hexadecimal)
Description
1
Salve ID
UInt8
01
1
2
Function code
UInt8
03
3
3
Bytes of Registers
Values
UInt8
0C
12
4
Voltage A
float32
435C0000
220V
5
Voltage B
float32 435D0000
221V
6
Voltage C
float32
435E0000
222V
7
CRC-16 Check
UInt16
14AC
Содержание POM200
Страница 1: ...www compressedairalliance com 1 User Manual Power Meter Din Rail with Display Model POM200...
Страница 10: ...Power Meter POM200 User Manual v1 www compressedairalliance com 10 Power Meter Dimensions 71 mm 2 8 95 mm 3 7...
Страница 19: ...Power Meter POM200 User Manual v1 www compressedairalliance com 19 3PH4W no VT...
Страница 20: ...Power Meter POM200 User Manual v1 www compressedairalliance com 20 3PH4W with VT...
Страница 21: ...Power Meter POM200 User Manual v1 www compressedairalliance com 21 3PH3W no VT 3PH3W with VT...
Страница 22: ...Power Meter POM200 User Manual v1 www compressedairalliance com 22 1PH3W 1PH2W...
Страница 23: ...Power Meter POM200 User Manual v1 www compressedairalliance com 23 Input Output Wiring diagram...