28
8.11 Operating Environment
Temperature range:
21oC +3oC (70oF+5oF)
Temperature rate of change:
Maximum of 3oC/hour (5.4oF/hour)
Temperature adjustment for altitude:
Reduce the operating temperature by
1.8oC/1000 meters (1oF/1000
feet)
Relative humidity range:
50% RH+10% (no condensation)
Relative humidity rate of change:
Maximum of 6%/hour
8.12 Shipping And Storage In Shipment Containers For Less Than 60 Days
Temperature range:
-40o to 66oC (-40o to 151oF)
Temperature rate of change:
Maximum of 20oC/hour (36oF/hour)
Relative humidity range:
0 to 95% RH (no condensation)
8.13 Storage In Shipment Containers For More Than 60 Days
Temperature range:
5o to 50oC (40o to 122oF)
Temperature rate of change:
Maximum of 11oC/hour (20oF/hour)
Relative humidity range:
10 to 95% RH (no condensation)
Wet bulb temperature:
Maximum of 32oC (90oF)
8.14 Altitude
Most equipment has been normally tested on a short-term basis for performance, up to an altitude of 2.4 kilometers
(8000 feet). Above this altitude, the operation of equipment may be impaired.
8.15 Airflow Rate Range
266-314 m3/h-kilowatts or 550-650 cfm/ton at the air-conditioner output
8.16 Vibration
Most equipment has been normally tested on a short-term basis for performance up to the vibration limits specified
below. Above these limits or with a continuous vibration level, the operation of equipment may be impaired
Frequency (Hertz)
Amplitude
5 - 22
0.254 millimeters (0.010 inches) double amplitude
22-500
0.25 g peak