TECH SUPPORT: 1.888.678.9427

INSTALLATION AND OPERATION MANUAL 

RLMCSFP SERIES

INS_RLMCSFP_REV–   

Rev. 18 Sep 2020   PAGE 4

Figure 4 –  DIP Switches

Table 2 – DIP Switch Settings

SW NAME

OFF (DOWN)

ON (UP)

1

Link Fault Enable Port 1 Link Fault Pass-Through Disabled

Link Fault Pass-Through Enabled

2

– 

N/A

N/A

3

FFE

Fiber Fault Relay Disabled

Fiber Fault Relay Enabled

4

PS Fault Enable

Power Supply Fault Relay Disabled

Power Supply Fault Relay Enabled

5

– 

N/A

N/A

6

1000/100 (SFP Speed)

100 Mbps Speed Set Speed must match speed of installed 

SFP. Reset power if switch or SFP is changed.

1000 Mbps Speed Set. Speed must match speed of 

installed SFP. Reset power if switch or SFP is changed.

1 -   SET DATA RATE DIP SWITCHES

Locate the 100/1000 data rate DIP switch on the bottom panel of the unit. 

Set the data rate according to bandwidth required.

NOTE: If two units are connected via the SFP Port, the data rate must be set the same on both units, and must match the 

data rate of the installed SFPs. Data rate settings are read on start-up, so restart the unit after making any changes.

2 -   SET FAULT DIP SWITCHES

 (UTP MODELS ONLY, FOR COAX MODELS SKIP TO STEP 3)

Locate the LFE, FFE, and PSE DIP switches on the bottom panel of the unit. 

LFE1:  If the Copper Port is Down or Not Connected, the Optical Port will turn on and off at a ~1 sec rate to indicate copper port 

fault and the alarm relay will be triggered.

FFE:  If the optical link is lost or there is a power failure then the alarm relay output will be triggered.

NOTE: You may select multiple fault event triggers.

NOTE: Power Supply Fault DIP Switch is only available on Redundant Power Models. When a redundant power supply is 

available, a failure of power on one power supply will trigger the alarm relay output. 

NOTE: Restart not required when making changes to this DIP switch setting.

3 -   CONNECT GROUND WIRING

Connect Ground Wiring to ground screw and tighten nut to secure.

4 -   CONNECT FAULT RELAY WIRING

Connect Fauly Relay device to 3-pin terminal block. The COM to N/C will be shorted in the fault condition.

5 -   CONNECT DATA WIRING

Connect RJ-45 Ports to field wiring using Cat5/5e/6 cable.

6 -   CONNECT NETWORK WIRING

Using fiber optic cabling appropriate to the installed SFP, connect the unit to a network device.

Installation Instructions

DIP Switches on RLMCSFP24DC,  

RLMCSFP48DC, and RLMCSFPPOEHO 

Models

DIP Switches on RLMCSFPHV Model

Содержание RLMCSFP Series

Страница 1: ...electable link fault pass through provides remote indication of a network fault and a summary fault alarm provides a local or remote indication via Form C dry contact closure in the event of loss of optical link or operating power The 10 100 1000BASE TX port supports both auto negotiation and automatic MDI MDI X crossover for full and half duplex operation manual MDI MDI X switching is not require...

Страница 2: ...lation Instructions Step 6 3 10 100 1000 TX RJ 45 Port 1 and Port 1 Link Activity L A and Speed LED Indicators See Installation Instructions Step 8 See Table 6 Indicating LEDs 4 SFP Port Link Status and SFP Port Link Speed LED Indicators See Table 5 Indicating LEDs 5 Power LED Indicator See Table 5 Indicating LEDs 6 User selectable DIP Switches See Installation Instructions Steps 1 2 See Table 3 D...

Страница 3: ...1 Link Activity L A and Speed LED Indicators See Installation Instructions Step 8 See Table 6 Indicating LEDs 4 SFP Port Link Status and SFP Port Link Speed LED Indicators See Table 5 Indicating LEDs 5 Power LED Indicator See Table 5 Indicating LEDs 6 Power over Ethernet PoE LED Indicator for Port 1 See Table 5 Indicating LEDs 7 User selectable DIP Switches See Installation Instructions Steps 1 2 ...

Страница 4: ...SWITCHES UTP MODELS ONLY FOR COAX MODELS SKIP TO STEP 3 Locate the LFE FFE and PSE DIP switches on the bottom panel of the unit LFE1 If the Copper Port is Down or Not Connected the Optical Port will turn on and off at a 1 sec rate to indicate copper port fault and the alarm relay will be triggered FFE If the optical link is lost or there is a power failure then the alarm relay output will be trigg...

Страница 5: ...ng transmitted 1000 Mbps No Fault NC COM Power Applied Flashing Fiber failure or copper failure Link Fault Enable must be switched set to ON Dim 30 W Mode Bright 60 W Mode RED Solid 100 Mbps Fault NO COM OFF Communication link has not been established Unit is not correctly powered up or DIP Switch incorrectly set Reset power after switch change Unit is not correctly powered up Unit is not correctl...

Страница 6: ...tion should be given to installing the equipment in an environment compatible with the maximum ambient temperature Tma specified by the manufacturer B Reduced Air Flow Installation of the equipment in a rack should be such that the amount of air flow required for safe operation of the equipment is not compromised Figure A Dimensions and mounting methods for a ComNet Reliance mini DIN Rail module T...

Отзывы: