background image

ODPMT200 Series DryLine® Dehydrator User Manual

11

every 6000 hours of compressor operation.  The 

kit listed below, contains all of the necessary 

parts to perform this overhaul.

Maintenance Parts

1.  Dehydrator Overhaul Kit 1 ea. 

AE01K-C0398-015

2.  Compressor Air Intake Filter bag of 6, 

EFLTR-91101

Tools

The following tools are used in the maintenance 

and overhaul procedures. 

A ballpoint pen, an adjustable open-end wrench, 

a socket wrench with a 7/16-inch (or 11mm) 

socket, a No. 2 Phillips screwdriver and a small 

flat-blade screwdriver.

Overhaul Procedure

When the ODPMT200 compressor run time 

reaches 6000 hours (or a multiple of 6000 

hours) it is time to replace certain items in the 

compressor and the air path of the dehydrator.  

These include the piston cups, piston seals 

and head gaskets of the compressor, the filter 

elements in the water and coalescing filters and 

the tube section connecting the compressor 

output to the water filter input.

Unit Shutdown and Removal

In order to perform an overhaul on the 

ODPMT200, the unit must be turned off and 

removed from service.  As this is being done 

the low pressure alarm may activate through a 

reporting alarm system.  Personnel monitoring 

such an alarm should be notified in advance 

so that they are aware of the fact that service 

is being performed.  It is also necessary to 

disconnect the dehydrator dry air output from the 

waveguide system during the overhaul.

3.7 

Dehydrator Filter Element  Replacement

Clean/replace the air intake filter

The air intake filter protects the compressor 

from contamination and dust.  Periodic cleaning/

replacement extends the life of the compressor. 

The filter is made of open-cell foam material.  It 

should be cleaned or replaced once a year (or 

more frequently, if the operating environment is 

very dusty.)

Pull off the filter cover and remove the foam 

element.  (The cover is held in place by two 

tabs.  Use a small screwdriver or a ballpoint pen 

to release them.)

Wash the filter in running water, squeezing it 

between the fingers.

Содержание DryLine ODPMT200 Series

Страница 1: ...ODPMT200 SERIES DryLine DEHYDRATOR USER MANUAL Bulletin AE01B A0467 001 Rev E 2007 2013 CommScope Inc All rights reserved 01 13 ...

Страница 2: ...Dehydrator to the Transmission Line 8 2 8 Purging the Transmission Line 8 Section 3 Maintenance 9 3 1 Maintenance 9 3 2 Regular Maintenance 9 3 3 Preventive Maintenance 9 3 4 6000 Hour Overhaul 9 3 5 Annual Maintenance 10 3 6 Parts Replacement and Dehydrator Overhaul 10 3 7 Dehydrator Filter Element Replacement 11 3 8 Service Restoration 12 Section 4 Troubleshooting 13 Figure 3 Schematic With All ...

Страница 3: ...DPMT200 Theory of operation The ODPMT200 series of DryLine dehydrators while similar in moisture removal technology operates differently than the rest of the DryLine series of dehydrators In order to provide a constant supply of dry air to small air volume systems and to maintain an acceptable moisture level in the product air stream a high pressure reservoir tank is needed This reservoir tank is ...

Страница 4: ...ary to make the connections The connection to the alarm strip is as follows and refer to Figure 1 for correct locations and colors of the wires on the terminal strip Term Function Wire Color 1 Power Fail Com Black 2 Power Fail Alarm Red 3 Humidity Com Green 4 Humidity Alarm Brown 5 Excess Run Com Blue 6 Excess Run Alarm White 7 Low Press Com Grey 8 Low Press Alarm Orange Alarm Definitions Low Pres...

Страница 5: ...Input 115 Vac 50 60 Hz Output Connector 3 8 polytube compression Dimensions 18 5 W x 32 0 H x 10 0 D Optional Alarms High Humidity Alarm Set Point 7 5 RH factory set Excess Run Alarm Set Point 10 minutes factory set Power Fail Alarm loss of input power Alarm Factory setting Where To Reset Low Normally Alarm switch Pressure Closed N C center term N O bottom term N C Mains Normally Power Fail Power ...

Страница 6: ...ove the top piece of corrugated packing Carefully remove the installation accessories and manual and dehydrator Check the dehydrator for shipping damage such as dents or loose parts Pressure Gauge indicates dehydrator output pressure in psig and kPa ON OFF Switch controls compressor and sensors Light indicates power switch is ON Circuit Breaker white tab indicates a circuit overload Push to reset ...

Страница 7: ...sure the power circuit is properly grounded Verify the power switch is OFF Feed the power cable not supplied through the liquid tite fitting on bottom of unit Connect power cable to input terminal strip on unit Use a small flat blade screwdriver to tighten connections on the terminal strip After power connections are Proper electrical connection is required It is suggested a licensed electrician b...

Страница 8: ...ely with a 9 16 wrench Be careful not to over tighten Connect the other end of the polytube to the transmission line Two air outputs are provided with individual shut off valves on the front of the unit Make sure that the valve is open position for each transmission line connection If one of the outputs connection is not used close the valve and leave the port capped Note If the transmission lines...

Страница 9: ... an ODPMT200 consists of a preventative maintenance inspection of the dehydrator and cleaning or replacement of the foam air intake filter These tasks can easily be performed in the field with the unit connected to the transmission line system and with only the front access door opened for maintenance 3 4 6000 Hour Overhaul A run time meter is provided on the front of the ODPMT200 to indicate the ...

Страница 10: ...t Check the run time meter Check the run time meter on the front panel to determine the duty cycle of the dehydrator If the dehydrator has been running for more than 10 15 of its installed time check the system for leaks Also check the time on the meter to determine if it is time to perform the 6000 hour overhaul 3 6 Parts Replacement and Dehydrator Overhaul CommScope ODPMT200 Dehydrators are desi...

Страница 11: ...ompressor output to the water filter input Unit Shutdown and Removal In order to perform an overhaul on the ODPMT200 the unit must be turned off and removed from service As this is being done the low pressure alarm may activate through a reporting alarm system Personnel monitoring such an alarm should be notified in advance so that they are aware of the fact that service is being performed It is a...

Страница 12: ...ION If the dehydrator overhaul process has taken more than a few hours it is recommended that the unit be run for one hour into the room to purge the membrane dryer and tank of any acquired moisture before reconnecting to the transmission line system Reverse the steps followed initially to remount the dehydrator To reconnect the dry air lines to reconnect the power and alarm cabling to turn the un...

Страница 13: ...nd observe pressure gauge The pressure gauge should read approximately 5 0 psig and the alarm should clear If alarm does not clear remove cover and verify wiring to low pressure alarm switch If the pressure does not stay constant after shutting off the valve apply leak detector to isolate the leak in the dehydrator exercise care when applying solution not to wet wiring or electronics See Figure 6 ...

Страница 14: ...ODPMT200 Series DryLine Dehydrator User Manual 14 Figure 3 Schematic With All Options ...

Страница 15: ...ODPMT200 Series DryLine Dehydrator User Manual 15 Figure 4 Alarm s ...

Страница 16: ...istance Record the Model Number e g ODPMT200 and Serial Number from the product label as you will be asked for these when you call Two main locations are currently available to help From North America Telephone 1 800 255 1479 Fax U S A 1 800 349 5444 International Telephone 1 779 435 6500 Fax Number 1 779 435 8579 Web Access Internet www commscope com email prc commscope com Section 5 Replacement ...

Страница 17: ...t to repair the unit we will invoice you for the inspection and freight charge if unit is to be returned LOANER UNITS Loaner units are available from the repair center to maintain your system while repairs are being performed If you feel you need a loaner please contact us at at one of the numbers listed under contact numbers A P O for the full value of the unit must be issued prior to shipment Al...

Страница 18: ...ODPMT200 Series DryLine Dehydrator User Manual 18 This page was left blank ...

Страница 19: ...ODPMT200 Series DryLine Dehydrator User Manual 19 Figure 5 Hole pattern for locateing J bolts in cement slab Bottom of Mounting Bracket 2 25 1 50 8 00 18 50 5 00 14 00 4X 0 43 ...

Страница 20: ...ODPMT200 Series DryLine Dehydrator User Manual 20 This page was left blank ...

Отзывы: