ADCP-90-326 • Rev B • November 2020
Page 24
© 2020, CommScope Inc.
7.2
Accessing Sliding Adapter Packs
To access a sliding adapter pack (
1. Route the patch cord into the tray as shown in the appropriate diagram in
.
2. Lift up the release tab and slide up the adapter pack.
Figure 21. Removing Dust Cap From Sliding Adapter
3. Pull the dust cap straight out.
4. Connect the patch cord connector to the adapter.
5. Slide down the adapter back to its home position.
6. Close the tray.
Danger:
Infrared radiation is invisible and can seriously damage the retina of the eye. Do not
look into the ends of any optical fiber. Do not look directly into the optical adapters of the
adapter packs. Exposure to invisible laser radiation may result. An optical power meter should
be used to verify active fibers. A protective cap or hood MUST be immediately placed over any
radiating adapter or optical fiber connector to avoid the potential of radiation exposure. This
practice also prevents dirt particles from entering the adapter or connector
.
Note:
Always inspect connectors and adapters when connecting connectors to adapters.
For cleaning procedures, refer to ADCP-90-139.
18541-A