CommScope 360G2-iP-1U-32-MPO-DP-SD Скачать руководство пользователя страница 3

www.commscope.com 

 

860538982 

Instruction Sheet 

 

Page 3 of 9 

Separately Orderable Components 

Material ID 

Part No. 

Description 

760039883

 

600-23BRKT

 

Mounting bracket accessory kit for 23-inch (584mm) frame

 

Important:  Limits for iPatch shelf and panel connections: 

 

iPatch

 MPO fiber shelves are limited to a maximum number of rack units (RUs) and will not support a fully 

populated rack or cabinet. 

iPatch

 MPO fiber shelves support 26 rows per rack/cabinet, such as configured 

for  (26)  1U  shelves,  (13)  2U  shelves,  (10)  2U  UHD  shelves,  (6)  4U  shelves,  (5)  4U  UHD  shelves,  or  any 
combination thereof. 

 

 

iPatch

  MPO  fiber  shelves  are  limited  to  a  maximum  number  of  five  (5)  panels  per  panel  bus  male 

connector. 
Start a new panel bus chain with every sixth panel in the rack system.

 

  

Important Safety Cautions

 

 

To reduce the risk of fire, electric shock, and injury to persons, read, understand, and adhere to the following 
instructions as well as any warnings marked on the product. 

 

Remote  risk  of  electric  shock.  Never  install  the  product  in  wet  locations  or  during  lightning  storms.  Never 
touch uninsulated communication wires or terminals. 

 

Disconnected  optical  components  may  emit  invisible  optical  radiation  that  can  damage  your  eyes.  Never 
look directly  into an  optical component that may have a  laser coupled to  it.  Serious and permanent retinal 
damage  is  possible.  If  accidental  exposure  to  laser  radiation  is  suspected,  consult  a  physician  for  an  eye 
examination. 

 

Wear  safety  glasses  to  install  the  shelf.  Although  standard  safety  glasses  provide  no  protection  from 
potential optical radiation, they offer protection from accidental airborne hardware and cleaning solvents. 

Precautions 

 

iPatch 

high density fiber modules require virtually no maintenance to maintain their performance. They 

contain no user-serviceable components, and any damage to the anti-tamper label or removal of top cover 
or front adapter mounting panel will void the warranty. 

 

Fiber optic trunk cable and jumper performance is sensitive to bending, pulling, and crushing. Minimum 
bend radius must be maintained during installation per the manufacturer’s specification. Appropriate pulling 
socks must be used during installation, and pulling forces shall not exceed 

manufacturer’s 

recommendations. MPO terminated trunk cables may use ribbonized fiber optic cable, which has a 
preferential bend axis. Use caution to avoid kinking trunk cables. 

 

All wiring that connects to this equipment must meet applicable local and national building codes and 
network wiring standards for communication cable. 

 

Care should be taken not to compromise the stability of the rack by installation of this equipment. 

 

iPatch

 fiber shelves are for use in restricted access areas only. 

 

SYSTIMAX 360

 

iPatch

 shelves use infrared sensing technology and should be installed where they are not 

exposed to direct sunlight or other infrared sources. 

 

iPatch

 high density fiber MPO adapters are equipped with protective dust caps installed in the front of all 

adapters. 

 

Prior to installation, clean the trunk cable and jumper connectors per the manufacturer’s recommendations. 

 

 

Содержание 360G2-iP-1U-32-MPO-DP-SD

Страница 1: ...ting iPatch System the iPatch Rack and Panel Managers must be running firmware version 8 1 or later and the imVision Controller must be running firmware version 10 1 or later The System Manager firmware used to manage the system must be version 7 1 or later We recommend that you upgrade the System Manager software to version 7 1 or a later version before you install the shelf Ordering information ...

Страница 2: ...d Flat blade screwdriver Phillips head screwdriver Specifications Fiber Optic Interface Industry standard MPO Compatible Fiber Size Multimode with 50 µm core diameter such as LazrSPEED Singlemode with 8 3 µm core diameter such as TeraSPEED Environmental Data Temperature Range 40º F to 158º F 40º C to 70º C storage 23º F to 122º F 5º C to 50º C operational Humidity 95 noncondensing Parts List Verif...

Страница 3: ...safety glasses to install the shelf Although standard safety glasses provide no protection from potential optical radiation they offer protection from accidental airborne hardware and cleaning solvents Precautions iPatch high density fiber modules require virtually no maintenance to maintain their performance They contain no user serviceable components and any damage to the anti tamper label or re...

Страница 4: ...l to the outside of the rail 4 Snap the corrugated tubing protecting panel bus jumper into the cable retainer clip on the outside of rail as shown 5 Position the corrugated tubing so that about 3 5 inches 89mm of tubing extends past the end of cable retainer clip 6 Position the exposed ribbon cable of the panel bus jumper in the flat retainer clips on the outside of the sliding rail as shown above...

Страница 5: ...h screws included in the kit Mount shelf to rack using four 12 24 x 1 2 inch screws provided For an ETSI rack use the 600 23BRKT accessory kit ordered separately and install one conversion bracket on one side of the shelf using two of the four 10 32 x 3 8 inch screws included in the kit Mount shelf to rack using four M6 x 12 screws not provided The shelf will not be centered in the rack 2 Connect ...

Страница 6: ...ough on shelf so that indentions behind captive screws rest on the standoffs 2 Using a Phillips head screwdriver tighten the captive screw on each end of trough to secure it to shelf Note If installing the trough on a sliding shelf pull the shelf out enough to support the faceplate from behind before tightening the captive screws ...

Страница 7: ...de of rear apron Carefully loop cable to rear of shelf on either side and continue to feed cable over top of rear apron Loosely secure cable to rear of shelf using a cable tie or hook and loop strap 4 Temporarily store slack sub units in shelf 5 Remove plug from appropriate size opening in shelf to accommodate cable gland on fiber cable Select an opening on rear apron that will be most advantageou...

Страница 8: ...he panel bus jumper may slide in the corrugated tubing Method B Note This method reduces the slack loop length at rear of shelf but it requires an open space of at least 1U above the shelf to work 1 Working back from where the fiber cable enters shelf at a cable gland carefully loop cable over rear fiber management bar and then across shelf slide on opposite side of chassis from cable entry point ...

Страница 9: ...th other hand to seat pins into hinge sockets 5 Repeat on other end to secure door to trough 6 Pivot door into the vertical position until strikes engage latches and door snaps into the closed position with an audible click 7 Door may be reopened by pulling on both upper corners of door opposite strikes until the latches release verified by an audible click Note Trough door may be removed when ope...

Отзывы: