Issue 6, June 2014 
www.commscope.com

 

 

 

SYSTIMAX 360

 iPatch

®

 G2 Fiber Sliding Shelf, 

MPO Distribution Panel Instructions 

 

 

 

 

© 2014 CommScope, Inc.  All rights reserved 

 

Page 1 of 9 

 

General 

The 

SYSTIMAX  360

  360G2  shelf  comes  equipped  with 

iPatch

® 

MPO  kits,  jumper-storage  trough,  and 

polycarbonate top cover. This sliding distribution shelf includes 

iPatch

 MPO kits designed for use in an 

iPatch

 

System  and  MPO  adapters  that  allow  connection  of  multi-fiber  trunk  cables  terminated  with  push-on  MPO 
connectors.  

These  shelves  mount  in  a  standard  19-inch  (483mm)  rack  with  universal  hole  spacing.  These  shelves  are 
intended for indoor use, but may be used outdoors in a suitable enclosure. 

Note:

    To  use  the 

SYSTIMAX  360

 

iPatch

  shelf  in  an  existing 

iPatch

  System,  the 

iPatch

  Rack  and  Panel 

Managers must be running firmware version 8.1 or later and the 

imVision

®

 Controller must be running firmware 

version 10.1 or later. The System Manager firmware, used to manage the system, must be version 7.1 or later. 
We  recommend  that  you  upgrade  the  System  Manager  software  to  version  7.1  or  a  later  version  before  you 
install the shelf. 

Ordering information is listed below:  

Material ID 

Part No. 

Description 

760169144 

360G2-iP-1U-32-MPO-DP

-

SD 

360G2 

iPatch

 1U 32-MPO distribution panel, sliding shelf 

760169185 

360G2-iP-2U-64-MPO-DP

-

SD 

360G2 

iPatch

 2U 64-MPO distribution panel, sliding shelf 

 

 

1U MPO Distribution Panel  

2U MPO Distribution Panel 

 

 

SYSTIMAX 360

 iPatch

®

 G2 MPO Fiber Sliding Shelves 

 

 

 

 

This product is covered by one or more of the following U.S. patents or their foreign equivalents: 
5,923,807,  6,245,998.  The 

iPatch

 System is covered by U.S. patents 6,285,293, 6,522,737 and 8,344,900

 

          

 

Содержание 360G2-iP-1U-32-MPO-DP-SD

Страница 1: ...ting iPatch System the iPatch Rack and Panel Managers must be running firmware version 8 1 or later and the imVision Controller must be running firmware version 10 1 or later The System Manager firmware used to manage the system must be version 7 1 or later We recommend that you upgrade the System Manager software to version 7 1 or a later version before you install the shelf Ordering information ...

Страница 2: ...d Flat blade screwdriver Phillips head screwdriver Specifications Fiber Optic Interface Industry standard MPO Compatible Fiber Size Multimode with 50 µm core diameter such as LazrSPEED Singlemode with 8 3 µm core diameter such as TeraSPEED Environmental Data Temperature Range 40º F to 158º F 40º C to 70º C storage 23º F to 122º F 5º C to 50º C operational Humidity 95 noncondensing Parts List Verif...

Страница 3: ...safety glasses to install the shelf Although standard safety glasses provide no protection from potential optical radiation they offer protection from accidental airborne hardware and cleaning solvents Precautions iPatch high density fiber modules require virtually no maintenance to maintain their performance They contain no user serviceable components and any damage to the anti tamper label or re...

Страница 4: ...l to the outside of the rail 4 Snap the corrugated tubing protecting panel bus jumper into the cable retainer clip on the outside of rail as shown 5 Position the corrugated tubing so that about 3 5 inches 89mm of tubing extends past the end of cable retainer clip 6 Position the exposed ribbon cable of the panel bus jumper in the flat retainer clips on the outside of the sliding rail as shown above...

Страница 5: ...h screws included in the kit Mount shelf to rack using four 12 24 x 1 2 inch screws provided For an ETSI rack use the 600 23BRKT accessory kit ordered separately and install one conversion bracket on one side of the shelf using two of the four 10 32 x 3 8 inch screws included in the kit Mount shelf to rack using four M6 x 12 screws not provided The shelf will not be centered in the rack 2 Connect ...

Страница 6: ...ough on shelf so that indentions behind captive screws rest on the standoffs 2 Using a Phillips head screwdriver tighten the captive screw on each end of trough to secure it to shelf Note If installing the trough on a sliding shelf pull the shelf out enough to support the faceplate from behind before tightening the captive screws ...

Страница 7: ...de of rear apron Carefully loop cable to rear of shelf on either side and continue to feed cable over top of rear apron Loosely secure cable to rear of shelf using a cable tie or hook and loop strap 4 Temporarily store slack sub units in shelf 5 Remove plug from appropriate size opening in shelf to accommodate cable gland on fiber cable Select an opening on rear apron that will be most advantageou...

Страница 8: ...he panel bus jumper may slide in the corrugated tubing Method B Note This method reduces the slack loop length at rear of shelf but it requires an open space of at least 1U above the shelf to work 1 Working back from where the fiber cable enters shelf at a cable gland carefully loop cable over rear fiber management bar and then across shelf slide on opposite side of chassis from cable entry point ...

Страница 9: ...th other hand to seat pins into hinge sockets 5 Repeat on other end to secure door to trough 6 Pivot door into the vertical position until strikes engage latches and door snaps into the closed position with an audible click 7 Door may be reopened by pulling on both upper corners of door opposite strikes until the latches release verified by an audible click Note Trough door may be removed when ope...

Отзывы: