Step 1
• Select your preferred torque mode (ships in standard torque) Press the device push pad to the
desired setting. (Recommend to fully depress and release 5%, giving the device room for changing
door conditions.)
Step 2
• While depressing the push pad, apply power. (i.e. presenting the credential to the reader).
Step 3
• Continue to keep pad depressed, the device will beep 6 times. After the beeps have stopped, release the
pad and now the adjustment is complete. If not to your liking repeat the 3 steps.
Setting PTS
2 Beeps
3 Beeps
5 Beeps
6 Beeps
Beeps
Explanation
Solution
Over Voltage
Under Voltage
Retraction or dogging failure
PUSH TO SET
> 30V unit will shut down. Check voltage & adjust to 24 V.
< 20V unit will shut down. Check voltage & adjust to 24 V.
After 1st fail: 5 beeps then immediately attempts to retract again.
After 2nd fail: 5 beeps with pause in-between for 30 seconds then
device attempts to retract again.
After 3rd fail: 5 beeps every 7 minutes, device will not attempt to
retract.
To Reset: Depress bar for 5 seconds at any time.
Device is recording it’s new position and power mode after the
6th beep.
Troubleshooting & Diagnostics
4 Beeps Failed Sensor
Verify all 3 sensor wires are installed correctly. Replace sensor if
problem persists by contacting office.
**Important Info**
Make sure to set PTS before finishing installation
Technical Information
MM4S V
ideo
U S c u s t o m e r s u p p o r t 1 - 8 8 8 - 6 2 2 - 2 3 7 7 | w w w. c o m m a n d a c c e s s . c o m | C A c u s t o m e r s u p p o r t 1 - 8 5 5 - 8 2 3 - 3 0 0 2
mm4s switches
2
on
on
off
STANDARD TORQUE
HIGH TORQUE
PTS PROGRAMMING LOCKED
PTS PROGRAMMING on
off
Average Latch Retraction Current: 2 Amp
Average Holding Current: 250 mA
High Torque Mode
Average Latch Retraction Current: 1 Amp
Average Holding Current: 215 mA
Standard Torque Mode
SPECIFICATIONS
• Input Voltage: 24VDC +/- 10%
• Wire gauge: Minimum 18 gauge
• Direct wire run - no relays or access control
units in-between power supply & module
1