CAUTION 

Bend the tubing in proper way. Do not harm to them. 

Connect the indoor unit at first, then the outdoor 

unit. 

Too large torque will harm the bellmouthing and too small 
will cause leakage. Please determine the torque 
according to Table 8-2. 

 
After the connecting work is finished, be sure to check 
that there is no gas leak. 

The bending angle should not exceed 90. 

Bending position is preferably in the middle of the 
bendable pipe. The larger the bending radius the better it 
is. 

Do not bend the pipe more than three times. 

When connecting the flare nut, coat the flare both inside 
and outside with either oil or ester oil and initially tighten 
by hand 3 or 4 turns before tighting firmly. 

 

 

 

 

 
Be sure to use both a spanner and torque wrench 
together when connecting or disconnecting pipes to /from 
the unit. 

(Fig.8-4) 

Bend the pipe with thumb 

min-radius 3.9in

Fig.8-2

Fig.8-3

Fig.8-4

How to expel the air with a vacuum pump 

Stop valve operation intruduction 

1.          Opening stop valve 

2.          Closing stop valve 

1) 

2) 

1) 

2) 

3) 

Remove the cap and turn the valve 
counterclock-wise with the hexagon wrench. 

Turn it until the shaft stops.Do not apply excessive force 
to the stop valve. Doing so may breakthe valve body, as 
the valve is not a backseat type. Always use the special 
tool. 

Make sure to tighten the cap securely. 

Remove the cap and turn the valve clockwise with the 
hexagon wrench. 

Securely tighten the valve until the shaft contacts the 
main bodyseal. 

CAUTION 

Tightening torque N.M (Turn clockwise to close) 

Stop

 

Valve

 

size

Shaft

 

(valve body)

Cap

 

(Valve lid) 

Ø6.4 

5.4

6.6 

Hexagonal

 

13.5

16.5 

11.5

13.9 

Ø9.5 

Ø12.7 8.1

9.9 18

22 

Ø15.9 

13.5

16.5 

Hexagonal

 

23

27 

Ø22.2 

27

33 

Hexagonal

 

wrench

 

36

44 

Ø25.4 

Loosen and remove the maintenance nuts of stop valves A 
and B, and connect the charge hose of the manifold valve to 
the service port of stop valve A. (Be sure that stop valves A 
and B are both closed) 
 
Connect the joint of the charge hose with the vacuum pump. 
 
Open the Lo-lever of the manifold value completely. 
 
Turn on the vacuum pump. At the beginning of pumping, 
loosen the maintenance nut of stop valve B a little to check 
whether the air comes in (the sound of the pump changes, 
and the indicator of compound meter turns below zero). Then 
fasten the maintenace nut. 
 
 

Using the vacuum pump 

When the pumping has finished, close the Lo-lever of the 
manifold valve completely and turn off the vacuum 
pump.Make pumping for 15 minutes or more and check that 

 
Loosen and remove the cap of stop valves A and B to open 
stop valve A and B completely, then fasten the cap. 
 
Disassemble the charge hose from the service port of stop 
valve A, and fasten the nut. 

Fig.8-6

Fig.8-5

Always use a charge hose for service port connection.

After tightening the cap, check that no refrigerant leaks 
arepresent.

service port 

cap 

maintenance nut 

hexagon hole 

shaft 

seal 

Make sure to tighten the cap securely. 
For the tightening torque, refer to the table below. 

Outdoor 

unit 

Indoor 

unit 

Stop valv e 

Ga s s ide 

Liq uid  si de 

Table 8-3 

 

Maintenance nut 

 

12

installation manual 

wrench 0.16in 

wrench 0.24in 

0.39in

the compound meter indicates -76

cm

Hg(-1X10 Pa) 

Содержание CPP012CD(O)

Страница 1: ...PA 12 TPA 18 TPA 24 TPA 36DU TPA 48DU Outdoor Unit CPP009CD O CPP012CD O CPP018CD O CPP024CD O CPP036CD O DU CPP048CD O DU If used as MULTI unit please refer to the Installation operation manuals pack...

Страница 2: ...strong and firm location which is able to withstand the set s weight If the strength is not enough or installation is not properly done the set will drop to cause injury The appliance must be installe...

Страница 3: ...not be sufficient enough to eliminate the noise The appliance is not intended for use by young children or infirm persons without supervision Don t install the air conditioner in the following locatio...

Страница 4: ...vement without further notices Cautions on remote controller installation Remote controller Remote controller holder Mounting screw B ST2 9x10 C H CANCEL LOCK SET TEMPERATURE C AUTO COOL DRY HEAT FAN...

Страница 5: ...INSPECTING AND HANDLING THE UNIT At delivery the package should be checked and any damage should be reported immediately to the service agent When handling the unit take into account the following 5...

Страница 6: ...y by wrenching the nuts after having adjusted the body s position well Refer to Fig 5 5 Select the position of installation hooks according to the hook holes on the installation board positions on the...

Страница 7: ...our corners if the lift of the indoor unit and the drainpipe is not influenced Refer to Fig 5 13 right Hang the air in grill to the panel then connect the lead terminator of the swing motor and that o...

Страница 8: ...ge test Check whether the drainpipe is unhindered New built house should have this test done before paving the ceiling The unit with pump Remove the test cover and stow about 2000ml water to the water...

Страница 9: ...g 5 19 Fig 5 18 One way Two way In case of one duct connection In case of two duct connection NOTE Fig 5 17 5 4 Install the distribution duct Conditioned air can be distributes by means of a distribut...

Страница 10: ...direct sunlight If necessary install a blind that does not interfere with the air flow During the heating mode the water drained off the outdoor unit The condensate should be well drained away by the...

Страница 11: ...lve of vacuum meter 2 Cut off the connection between pressure meter and vacuum pump 3 Close the vacuum pump Fig 6 7 NOTE All the pictures in this manual are for explanation purpose only They may be sl...

Страница 12: ...ell with the tapes to prevent leakage Execute heat insulation work completely on both sides of the gas piping and the liquid piping Otherwise this can sometimes result in water leakage 1 2 3 5 6 7 4 B...

Страница 13: ...orque N M Turn clockwise to close Stop Valve size Shaft valve body Cap Valve lid 6 4 5 4 6 6 Hexagonal 13 5 16 5 11 5 13 9 9 5 12 7 8 1 9 9 18 22 15 9 13 5 16 5 Hexagonal 23 27 22 2 27 33 Hexagonal wr...

Страница 14: ...ion 3 The drain plug is used to empty the water receiver for maintenance of the air conditioner Please stuff it imposition at all times during operation to avoid leakage The body s pump pipe and the d...

Страница 15: ...ment has to be connected with this power line For detailed installation acceptance please refer to your power supplier if restrictions do apply for products like washing machines air conditioners or e...

Страница 16: ...impeded The heating insulation works well The ground wiring is connected correctly The length of the tubing and the added stow capacity of the refrigerant have been recorded The power voltage fits the...

Страница 17: ...ding to the wiring scheme or it damages the unit Before obtaining access to terminals all supply circuits must be disconnected CAUTION Indoor Outdoor connection The power supply must comply with the r...

Страница 18: ...ls TECHNICAL BULLETIN Heat Sink Compound Thermal Paste Make sure to use Heat Sink Compound not provided when replacing Mini Split electronic boards Clean up thoroughly old paste on chips located under...

Отзывы: