Comfortaire HRG18 S1P Series Скачать руководство пользователя страница 20

Installation and Operation Manual  -  

HRG18xxS1P

Page 20 of 23

508133M01

Issue 2106

2.  Connect gauge to the service port.
3.  When testing is completed, replace service port cap. 

Tighten finger tight, then an additional 1/6 turn.

To Open Liquid or Suction Line Service Valve:

1.  Remove stem cap with an adjustable wrench.
2.  Use service wrench with a hex-head extension to back 

the stem out counterclockwise as far as it will go. Use a 

3/16” hex head extension for liquid line service valves 

and a 5/16” extension for suction line service valves.

3. 

Replace the stem cap. Tighten finger tight, then tighten 

an additional 1/6 turn.

To Close Liquid or Suction Line Service Valve:

1.  Remove the stem cap with an adjustable wrench.
2.  Use a service wrench with a hex-head extension to 

turn the stem clockwise to seat the valve. Tighten 

firmly.

3. 

Replace the stem cap. Tighten finger tight, then tighten 

an additional 1/6 turn.

Suction Line (Ball Type) Service Valve

Suction line (ball type) service valves function the same 

way as the other valves; the difference is in the construction 

(see Figure 13).

The ball valve is equipped with a service port with a factory-

installed Schrader valve. A service port cap protects the 

Schrader valve from contamination and serves as the 

primary seal.

Figure 13. 

Maintenance

Regular Maintenance Requirements

Your system should be regularly inspected by a qualified 

service technician. These regular visits may include 

(among other things) checks for:

•  Motor operation
•  Ductwork air leaks
•  Coil & drain pan cleanliness (indoor & outdoor)
•  Electrical component operation & wiring check
•  Proper refrigerant level & refrigerant leaks
• 

Proper airflow

•  Drainage of condensate
• 

Air filter(s) performance

•  Blower wheel alignment, balance & cleaning
•  Primary & secondary drain line cleanliness
•  Proper defrost operation (heat pumps)

Air Filter

Inspect air filters at least monthly and replace or clean as 

required. Disposable filters should be replaced. Washable 

filters  may  be  cleaned  by  soaking  in  mild  detergent  and 

rinsing with cold water. Allow filter to dry before reinstalling. 

Replace filters with the arrows pointing in the direction of 

airflow.  Dirty  filters  are  the  most  common  cause  of  poor 

heating / cooling performance and compressor failures.

Indoor Coil

If the system has been operated with a clean filter in place, 

it should require minimal cleaning. If cleaning is needed, 

call your dealer for service.

Condensate Drain

During cooling season check at least monthly for free flow 

of drainage and clean if necessary.

Outdoor Unit

Grass cuttings, leaves, dirt, dust, lint from clothes dryers, 

and foliage from trees can be drawn into coils by movement 

of the air. Clogged condenser coils will lower the efficiency 

of your unit and could cause damage to the condenser and 

compressor. 
Periodically, debris should be brushed from the condenser 

coils. Use a soft bristle brush with light pressure only. DO 

NOT  damage  or  bend  condenser  coil  fins.  Damaged  or 

bent fins may affect unit operation.

Содержание HRG18 S1P Series

Страница 1: ...d qualified service personnel should install or service this equipment Installation and service performed by unqualified persons can result in property damage personal injury or death WARNING Sharp me...

Страница 2: ...cautions Follow all safety codes Wear safety glasses and work gloves Use quenching cloth for brazing operations Have fire extinguisher available Read these instructions thoroughly and follow all warni...

Страница 3: ...lightly away from building not to exceed 1 4 per foot Figure 1 Slab Mounting Install on a Solid Level Mounting Pad The outdoor section is to be installed on a solid foundation This foundation should e...

Страница 4: ...he drier is shipped loose it must be installed by the installer in the field Unit warranty will be void if the drier is not installed Installation of Line Sets DO NOT fasten liquid or suction lines in...

Страница 5: ...that has not had compressor burnout If the system has experienced burnout it is recommended that the existing line set and indoor coil be replaced NOTE In lieu of R 410A an industry standard flushing...

Страница 6: ...uid line valve 3 Refrigerant gauge set center port to inlet on the recovery machine with an empty recovery tank connected to the gauge set 4 Connect recovery tank to recovery machine per machine instr...

Страница 7: ...system use a regulator that can control the pressure down to 1 or 2 psig 6 9 to 13 8 kPa WARNING Refrigerant must be reclaimed in accordance with national and local codes WARNING 1 Set the recovery ma...

Страница 8: ...Coil Shown Sensing bulb insulation is required if mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUT...

Страница 9: ...The pipe must remain round Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP S...

Страница 10: ...INE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around serv...

Страница 11: ...valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added...

Страница 12: ...itioned to deliver liquid refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut...

Страница 13: ...re required to control the outdoor unit R C W1 O and Y1 and Y1 is jumpered to Y2 in the outdoor unit Note that the published performance data is based upon the use of a two stage thermostat Refer to t...

Страница 14: ...trol Using Suction Pressure Figure 9 Table 4 HRG18 Thermostat Control Options Size Circuit and Install Service Disconnect Switch Refer to the unit nameplate for minimum circuit ampacity and maximum fu...

Страница 15: ...Less than 100 30m 18 Temperature Rating 35 C Minimum More than 100 30m 16 Table 5 Conventional 24VAC Non Communicating Thermostat Wiring Route High Voltage and Ground Wires Any excess high voltage fie...

Страница 16: ...S C I I R DF TST Y1 O C W1 R G TC TO ACC2 ACC1 Y1 O DH C W2 W1 R G DS W2 O D SENSOR OPTIONAL FOR SINGLE STAGE OPERATION INSTALL A JUMPER BETWEEN Y1 TO Y2 ON THE OUTDOOR UNIT TERMINAL STRIP Figure 9 Co...

Страница 17: ...des of operation If the intended capacity for the application is 3 or 5 Ton skip this section The units are field convertible to 2 Ton or 4 Ton to efficiently perform for the required application If t...

Страница 18: ...harge Mode To exit the charging mode remove the Charge Mode Jumper from the Charge Mode Pins The system will be in Charge Mode for a maximum time of 60 minutes and will automatically exit the charge m...

Страница 19: ...ystems below 60 F charge in heating mode using the subcooling method and table provided on the unit access panel Attach low pressure gauge hose to auxiliary service port to access suction side in heat...

Страница 20: ...echnician These regular visits may include among other things checks for Motor operation Ductwork air leaks Coil drain pan cleanliness indoor outdoor Electrical component operation wiring check Proper...

Страница 21: ...e auxiliary heat Indicating Light Most heat pump thermostats have an amber light which indicates when the heat pump is operating in the emergency heat mode Temperature Indicator The temperature indica...

Страница 22: ...A SERVICE CALL 1 Ensure thermostat is set below cooling or above heating room temperature and that the system lever is in the COOL HEAT or AUTO position 2 Inspect your return air filter If it is dirty...

Страница 23: ...Installation and Operation Manual HRG18xxS1P 508133M01 Page 23 of 23 Issue 2106 Figure 14 Wiring Diagram...

Страница 24: ...See the HRG18 tables on page 1 and 2 Install a wire nut on any unused wire to electrically insulate the unused wire Field Connection Wire Harness Wire Color Marking Stamped on the Wire Thermostat Wir...

Страница 25: ...Yellow Y1 Y1 Y1 first stage cooling with conventional non communicating thermostat only Install a wire nut on this wire if unused Blue Y2 Y2 Y2 second stage cooling with conventional non communicating...

Страница 26: ...18 9 8 5 3 TON MODE INDOOR MATCHUP SUBCOOL 4 TON MODE C M CG60P C D AP C M CG60T C D AP 15 5 6 5 C M CG60P C D BP C M CG60T C D BP 16 7 5 5 TON MODE C M CG60P C D AP C M CG60T C D AP 15 5 C M CG36P A...

Страница 27: ...HULI LQJ GLPHQVLRQDO GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQFH DQG FHUWLILFDWLRQ OO SU...

Отзывы: