OWNER’S MANUAL

AIR FOR
COMBUSTION AND
VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this worksheet to determine if you have a confined or unconfined space.

Space:

 Includes the room in which you will install heater plus any adjoining rooms with doorless passageways or ventilation grills between

the rooms.

1.

Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example:

 Space size 20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of
the space.

2.

Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) 

÷

 50 cu. ft. = (Maximum Btu/Hr  the space can support)

Example:

 2560 cu. ft. (volume of space) 

÷

 50 cu. ft. = 51.2 or 51,200 (maximum Btu/Hr the space can support)

3.

Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

___________________ Btu/Hr

Gas water heater*

___________________ Btu/Hr

Gas furnace

___________________ Btu/Hr

Vented gas heater

___________________ Btu/Hr

Gas fireplace logs

___________________ Btu/Hr

Other gas appliances* + __________________ Btu/Hr

Total

= __________________ Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.

Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200 Btu/Hr (maximum the space can support)

60,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support.
You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin-

ing room or add ventilation grills between rooms. See Ventilation Air From Inside Building, page 6.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 6.

C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no
additional fresh air ventilation.

Example:

Gas water heater

40,000

Btu/Hr

Vent-free heater

+

20,000

Btu/Hr

Total

=

60,000

Btu/Hr

Continued

 WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space

or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of
the methods described in the 

National Fuel Gas Code, ANS Z223.1, Section 5.3 or applicable local codes.

Содержание CGP20TB

Страница 1: ...ence CGP20TB CGP20TLB CGP30TB CGP30TLB 20 000 Btu Hr Thermostat and 30 000 Btu Hr Thermostat Model Heaters WARNING Improper installa tion adjustment alteration ser vice or maintenance can cause injury...

Страница 2: ...can be dangerous 4 This heater shall not be installed in a bedroom or bathroom 5 This heater needs fresh outside air ven tilation to run properly This heater has an Oxygen Depletion Sensing ODS safety...

Страница 3: ...shipment 3 Check heater for any shipping damage If heater is damaged promptly inform dealer where you bought heater PRODUCT FEATURES SAFETY DEVICE This heater has a pilot with an Oxygen Depletion Sen...

Страница 4: ...ing only iftherearedoorlesspassagewaysorventila tion grills between them PROVIDING ADEQUATE VENTILATION The following are excerpts from National Fuel Gas Code NFPA 54 ANS Z223 1 Sec tion5 3 AirforComb...

Страница 5: ...include direct vent gas appliances Direct vent draws combustion air from the outdoors and vents to the outdoors 4 Compare the maximum Btu Hr the space can support with the actual amount of Btu Hr used...

Страница 6: ...igure 2 Ventilation Air from Inside Building WARNING Rework work sheet adding the space of the adjoining unconfined space The combined spaces must have enough fresh air to supply all appliances in bot...

Страница 7: ...N This heater cre ates warm air currents These currents move heat to wall sur faces next to heater Installing heater next to vinyl or cloth wall coverings or operating heater where impurities such as...

Страница 8: ...ng bracket to wall in one of two ways 1 Attaching to wall stud 2 Attaching to wall anchor Removing Front Panel Of Heater 1 Remove two screws near bottom cor ners of front panel 2 Liftstraightupongrill...

Страница 9: ...l mounting bracket is firmly fastened to wall Figure 9 Folding Anchor INSTALLATION Continued Figure 10 Popping Open Anchor Wings For Thin Walls Stand Out Tab Figure 11 Mounting Heater Onto Mounting Br...

Страница 10: ...un properly IMPORTANT Holdpressureregulatorwith wrench when connecting it to gas piping and or fittings CAUTION Never connect heater directly to the propane LP supply This heater requires an external...

Страница 11: ...ppliance area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHATTODOIFYOUSMELLGAS Do not try to light any appliance Do not touch any elec...

Страница 12: ...ol knob Note If pilot goes out repeat steps 3 through 7 This heater has a safety interlock system Wait one 1 minute before lighting pilot again 8 Turn control knob counterclockwise C clockwise to desi...

Страница 13: ...an WARNING Turn off heater and let cool before cleaning CAUTION You must keep control areas burner and circu lating air passageways of heater clean Inspect these areas of heater before each use Have h...

Страница 14: ...d REMEDY 1 Replace ignitor 2 Replace ignitor 3 Reconnect ignitor cable 4 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 5 Tighten nut holding piezo ignitor to heater cabin...

Страница 15: ...ound clean burner see Cleaning and Maintenance page 13 2 Replace gas regulator 1 Problem will stop after a few hours of operation 1 Turn control knob to LO position and let warm up for a minute 2 Oper...

Страница 16: ...se just after burner is lit or shut off Heater produces unwanted odors Heater shuts off in use ODS operates Gas odor even when control knob is in OFF position Gas odor during combustion Moisture conde...

Страница 17: ...may be low When Gas Quality Is Bad pilot will not stay lit burner will produce flames and soot heater will backfire when lit Youmayfeelyourgaspressureistoolowor gas quality is bad If so contact your l...

Страница 18: ...ted on the back page of this manual FLOOR MOUNTING STAND 20 000 Btu Hr Models CGP20TLB GA4500L Ivory CGP20TB GA4500 Champagne 30 000 Btu Hr Models CGP30TLB GA4510L Ivory CGP30TB GA4510 Champagne For l...

Страница 19: ...ww nbmc com Washer Equipment Co 1715 Main Street Kansas City MO 64108 2195 KS MO AR 816 842 3911 www washerparts com East Coast Energy Products 707 Broadway W Long Branch NJ 07764 1542 732 870 8809 1...

Страница 20: ...20 104332 BLUE FLAME PROPANE LP HEATER 11 1 11 2 CGP20TB CGP20TLB CGP30TB CGP30TLB ILLUSTRATED PARTS BREAKDOWN 1 2 3 4 5 6 7 8 9 10 10 11 12 13 14 16 18 19 20 21 22 15 23 24 17 7...

Страница 21: ...Cable 1 10 098249 01 098249 01 Nut M5 2 11 103594 04 103594 04 Pilot ODS 1 11 1 098514 01 098514 01 Thermocouple 1 11 2 106842 01 106842 01 Ignitor Electrode 1 12 103446 01 103447 01 Burner 1 13 0993...

Страница 22: ...the unit This warranty does not apply to parts that are not in original condition because of normal wear and tear or parts that fail or become damaged as a result of misuse accidents lack of proper m...

Отзывы: