background image

www.fmiproducts.com

111161-01L

7

AIR FOR cOMBUSTION AND VENTILATION

Continued

between wall panels, at penetrations 

for plumbing, electrical and gas lines 

and at other openings.

If  your  home  meets  all  of  the  three  criteria 

above, you must provide additional fresh air. 

See 

Ventilation Air From Outdoors

, page 8.

If your home does not meet all of the three 

criteria above, proceed to 

Determining Fresh-

Air Flow For Heater Location

.

Confined Space and Unconfined Space

The National Fuel Gas Code, ANSI Z223.1/

NFPA 54 

defines a confined space as a space 

whose volume is less than 50 cubic feet per 

1,000 Btu/hr (4.8 m

3

 per kw) of the aggregate 

input rating of all appliances installed in that 

space and an unconfined space as a space 

whose volume is not less than 50 cubic feet 

per 1,000 Btu/hr (4.8 m

3

 per kw) of the ag-

gregate input rating of all appliances installed 

in that space. Rooms communicating directly 

with the space in which the appliances are 

installed*,  through  openings  not  furnished 

with doors, are considered a part of the un-

confined space.
* Adjoining rooms are communicating only if 

there are doorless passageways or ventilation 

grills between them.

DETERMINING FRESH-AIR FLOW 

FOR HEATER LOCATION

Determining if you Have a Confined or 

Unconfined Space

Use this work sheet to determine if you have 

a confined or unconfined space.

Space:

 Includes the room in which you will 

install heater plus any adjoining rooms with 

doorless  passageways  or  ventilation  grills 

between the rooms.

1.  Determine the volume of the space (length 

x width x height).

 

Length x Width x Height =__________cu. ft. 

(volume of space)

 

Example:

 Space size 20 ft. (length) x 16 ft. 

(width) x 8 ft. (ceiling height) = 2560 cu. ft. 

(volume of space)

 

If  additional  ventilation  to  adjoining  room 

is supplied with grills or openings, add the 

volume of these rooms to the total volume 

of the space. 

2.  Multiply the space volume by 20 to determine 

the maximum Btu/Hr the space can support.

 

  ________ (volume of space) x 20 = (Maxi-

mum Btu/Hr the space can support)

 

Example:

 2560 cu. ft. (volume of space) x 20 

= 51,200 (maximum Btu/Hr the space can 

support)

3.  Add the Btu/Hr of all fuel burning appliances 

in the space.

 

Vent-free fireplace 

 __________ Btu/Hr

 

Gas water heater* 

 __________ Btu/Hr

 

Gas furnace 

 __________ Btu/Hr

 

Vented gas heater 

 __________ Btu/Hr

 

Gas fireplace logs 

 __________ Btu/Hr

 

Other gas appliances* + _________ Btu/Hr

 

Total 

= _________ Btu/Hr

 

* Do not include direct-vent gas appliances. 

Direct-vent draws combustion air from the 

outdoors and vents to the outdoors.

 

Example:

 

 

Gas water heater 

 __________ Btu/Hr

 

Vent-free fireplace 

+ _________ Btu/Hr

 

Total 

= _________ Btu/Hr

4.  Compare  the  maximum  Btu/Hr  the  space 

can support with the actual amount of Btu/

Hr used.

 

  _______ Btu/Hr (maximum the space can 

support) 

 

  _______ Btu/Hr (actual amount of Btu/Hr 

used)

 

Example:

  51,200  Btu/Hr  (maximum  the 

space can support) 

 

 

79,000 Btu/Hr (actual amount of 

Btu/Hr used)

The space in the above example is a confined 

space because the actual Btu/Hr used is more 

than the maximum Btu/Hr the space can sup-

port. You must provide additional fresh air. Your 

options are as follows:
A.  Rework worksheet, adding the space of an 

adjoining room. If the extra space provides 

an unconfined space, remove door to adjoin-

ing  room  or  add  ventilation  grills  between 

rooms.  See 

Ventilation  Air  From  Inside 

Building

, page 8

.

B.  Vent  room  directly  to  the  outdoors.  See 

Ventilation Air From Outdoors

, page 8.

C.  Install a lower Btu/Hr fireplace, if lower Btu/

Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maxi-

mum Btu/Hr the space can support,

 

the space is 

an unconfined space. You will need no additional 

fresh air ventilation.

  40,000
  39,000
  79,000

Содержание CCL3924NRA

Страница 1: ...ycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fi...

Страница 2: ...fired heat er It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ven tilation section on...

Страница 3: ...ough no odor exists Make certain you read and understand all warnings Keep this manual for reference It is your guide to safe and proper operation of this heater WARNING Any change to this heater or i...

Страница 4: ...er is designed to be smoke less If logs ever appear to smoke turn off heater and call a qualified service person Note During initial operation slight smok ing may occur due to log curing and heater bu...

Страница 5: ...licensed plumber or gas fitter in the Commonwealth of Massachusetts Sellers of unvented propane or natural gas fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upo...

Страница 6: ...anever Newmaterials increasedinsulationand new construction methods help reduce heat loss in homes Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm ai...

Страница 7: ...g room is supplied with grills or openings add the volume of these rooms to the total volume of the space 2 Multiply the space volume by 20 to determine the maximum Btu Hr the space can support ______...

Страница 8: ...and Ventilation for required size of ventilation grills or ducts Ventilation Air From Outdoors Provide extra fresh air by using ventilation grills or ducts You must provide two perma nent openings on...

Страница 9: ...s without enough ventilation air may cause mildew to form from too much moisture See Air for Combustion and Ventila tion page 6 Installation NOTICE Thisheater isintended for use as supplemental heat U...

Страница 10: ...ble material must be 4 from the side of the fireplace opening see Figure 4 Note When installing your gas logs into a manufactured firebox follow firebox manufacturer s instructions for minimum clearan...

Страница 11: ...A6053 see Accessories page 31 Less than 8 Noncombustible material must be extended to at least 8 See Between 8 and 12 above If you can not extend material you must operate heater with flue damper open...

Страница 12: ...lace Clearances Above Combustible Flooring Figure 8 Minimum Fireplace Clearances If Installed at Floor Level INSTALLING DAMPER CLAMP AC CESSORY FOR VENTED OPERATION Note When used as a vented heater a...

Страница 13: ...e provided with heater approved flexible gas hose not provided if allowed by local codes sealant resistant to propane LP gas not provided electric drill with 3 16 masonry drill bit Note Install option...

Страница 14: ...y to male NPT threads This will prevent excess sealant from going into pipe Excess sealant in pipe could result in clogged heater valves Installation Continued Figure 13 External Regulator With Vent P...

Страница 15: ...or fittings CHECKING GAS CONNECTIONS WARNING Testallgaspiping and connections internal and external to unit for leaks after installing or servicing Correct all leaks at once WARNING Never use an open...

Страница 16: ...Closed Equipment Shutoff Valve Figure 16 Checking Gas Joints Propane LP Tank Equipment Shutoff Valve Control Valve Location Figure 17 Checking Gas Joints Gas Meter Equipment Shutoff Valve Control Valv...

Страница 17: ...ng It is very important to install these logs exactly as instructed Do not modify logs Only use logs supplied with heater 1 Place front log 1 on grate fingers Make sure front log rests firmly between...

Страница 18: ...ON Figure 21 Installing Crossover Log 4 CCL3930PR NRA Shown Log 2 Log 3 Pegs Figure 22 Installing Crossover Log 5 CCL3930PR NRA Shown AUTO OFF ON 7 Figure 24 Installing Crossover Log 7 to Models CCL39...

Страница 19: ...WARNING Burners will come on automatically within one minute when the selector switchisintheONpositionafter the pilot is lit FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not fol low these in...

Страница 20: ...light pilot The pilot is attached to the front burner If needed keep pressing ignitor button until pilot lights Note If pilot does not stay lit contact a qualified service person or gas supplier for...

Страница 21: ...here be tween HI and LO Slide the selector switch to the REMOTE position see Figure 27 Note The burner may light if hand held re mote was on when selector switch was last turned off You can now turn t...

Страница 22: ...Yourlocal computer store hardware store or home center may carry compressed air in a can If using com pressed air in a can please follow the directions on the can If you don t follow directions on th...

Страница 23: ...hen in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tub...

Страница 24: ...After ODS pilot lights keep control knob pressed in 30 seconds 3 Fully open equipment shut off valve 4 A Contact local natural or propane LP gas company B Clean ODS pilot see Cleaning and Maintenance...

Страница 25: ...on and Ventilation require ments page 6 1 Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local natural or propan...

Страница 26: ...ocate and correct all leaks see Checking Gas Con nections page 15 2 Replace control valve 1 Take apart gas tubing and remove foreign matter 2 Locate and correct all leaks see Checking Gas Con nections...

Страница 27: ...0NRA Rating Variable 20 000 39 000 Btu Hr Type Gas Natural Ignition Piezo Manifold Pressure 3 5 W C Inlet Gas Pressure in of water Max 10 5 W C Min 5 W C CCL3924PRA and CCL3930PRA Rating Variable 20 0...

Страница 28: ...27 18 23 12 11 14 4 5 1 2 17 10 21 20 22 6 7 3 9 20 16 8 15 29 28 28 25 26 O F F P I L O T O N H I L O O F F P I L O T O N H I L O 24 31 13 Parts MODELS CCL3924PRA CCL3924NRA CCL3930PRA and CCL3930NRA...

Страница 29: ...Pilot Tube 1 16 103781 02 103781 02 Gas Control Valve LP 1 103781 01 103781 01 Gas Control Valve NG 1 17 103345 01 103345 01 103345 01 103345 01 Lower Bracket 1 18 M11084 38 M11084 38 M11084 38 M1108...

Страница 30: ...elayed ignition heater will not produce specified heat propane LP gas supply may be low You may feel your gas pressure is too low If so contact your local propane LP gas supplier If this product is mi...

Страница 31: ...FMI PRODUCTS LLC at 1 866 328 4538 for information You can also write to the address listed on the back page of this manual RECEIVER AND HAND HELD THERMOSTAT REMOTE CONTROL KIT MLCR M For all Remote...

Страница 32: ...product and or FMI PRODUCTS LLC who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic mat...

Отзывы: