INSTALLATION

Continued

*  Purchase  the  optional  equipment  shutoff 

valve from your dealer.
** Minimum inlet pressure for purpose of input 

adjustment. 

Figure 14 - Gas Connection

Gas Control 

3" Minimum

Equipment Shutoff 

Valve With 1/8" 

NPT Tap*

Approved 

Flexible 

Gas Hose (if 

allowed by 

local codes)

PROPANE/LP

From External 

Regulator (11" 

W.C.** to 14" W.C. 

Pressure)

NATURAL

From Gas Meter

(5" W.C.** to

           10.5" W.C.

            Pressure)

 Cap  Pipe  Tee

   

Nipple Joint

Sediment Trap

  WARNING:  Use  pipe  joint 

sealant that is resistant to liquid 

petroleum (LP) gas.

We recommend that you install a sediment 

trap  in  supply  line  as  shown  in  Figure  14. 

Locate sediment trap where it is within reach 

for cleaning. Install in piping system between 

fuel  supply  and  heater.  Locate  sediment 

trap  where  trapped  matter  is  not  likely  to 

freeze. A sediment trap traps moisture and 

contaminants. This  keeps  them  from  going 

into  heater  controls.  If  sediment  trap  is  not 

installed  or  is  installed  wrong,  heater  may 

not run properly.

 CAUTION: Avoid damage to 

regulator.  Hold  gas  regulator 

with wrench when connecting it 

to gas piping and/or fittings.

CHECKING GAS CONNECTIONS

 WARNING: Test all gas piping 

and  connections,  internal  and 

external to unit, for leaks after 

installing or servicing. Correct 

all leaks at once.

  WARNING:  Never  use  an 

open flame to check for a leak. 

Apply a noncorrosive leak detec

-

tion fluid to all joints. Bubbles 

forming show a leak. Correct all 

leaks at once

 CAUTION: Make sure exter-

nal regulator has been installed 

between  propane/LP  supply 

and heater. See guidelines un

-

der 

Connecting to Gas Supply

page 14.

PRESSURE TESTING GAS SUPPLy 

PIPING SySTEM

Test Pressures In Excess Of 1/2 PSIG 

(3.5 kPa)

1.  Disconnect appliance with its appliance 

main gas valve (control valve) and equip-

ment shutoff valve from gas supply piping 

system. Pressures in excess of 1/2 psig 

will damage heater regulator.

2.  Cap off open end of gas pipe where equip-

ment shutoff valve was connected.

3.  Pressurize supply piping system by either 

opening  propane/LP  supply  tank  valve 

for propane/LP gas or opening main gas 

valve  located  on  or  near  gas  meter  for 

natural gas or using compressed air.

4.  Check all joints of gas supply piping sys-

tem. Apply  noncorrosive  leak  detection 

fluid to gas joints. Bubbles forming show 

a leak. 

5.  Correct all leaks at once.
6.  Reconnect heater and equipment shutoff 

valve to gas supply. Check reconnected 

fittings for leaks.

Содержание CCL3924NRA

Страница 1: ...ycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fi...

Страница 2: ...fired heat er It uses air oxygen from the room in which it is installed Provisions for adequate combustion and ventilation air must be provided Refer to Air for Combustion and Ven tilation section on...

Страница 3: ...ough no odor exists Make certain you read and understand all warnings Keep this manual for reference It is your guide to safe and proper operation of this heater WARNING Any change to this heater or i...

Страница 4: ...er is designed to be smoke less If logs ever appear to smoke turn off heater and call a qualified service person Note During initial operation slight smok ing may occur due to log curing and heater bu...

Страница 5: ...licensed plumber or gas fitter in the Commonwealth of Massachusetts Sellers of unvented propane or natural gas fired supplemental room heaters shall provide to each purchaser a copy of 527 CMR 30 upo...

Страница 6: ...anever Newmaterials increasedinsulationand new construction methods help reduce heat loss in homes Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm ai...

Страница 7: ...g room is supplied with grills or openings add the volume of these rooms to the total volume of the space 2 Multiply the space volume by 20 to determine the maximum Btu Hr the space can support ______...

Страница 8: ...and Ventilation for required size of ventilation grills or ducts Ventilation Air From Outdoors Provide extra fresh air by using ventilation grills or ducts You must provide two perma nent openings on...

Страница 9: ...s without enough ventilation air may cause mildew to form from too much moisture See Air for Combustion and Ventila tion page 6 Installation NOTICE Thisheater isintended for use as supplemental heat U...

Страница 10: ...ble material must be 4 from the side of the fireplace opening see Figure 4 Note When installing your gas logs into a manufactured firebox follow firebox manufacturer s instructions for minimum clearan...

Страница 11: ...A6053 see Accessories page 31 Less than 8 Noncombustible material must be extended to at least 8 See Between 8 and 12 above If you can not extend material you must operate heater with flue damper open...

Страница 12: ...lace Clearances Above Combustible Flooring Figure 8 Minimum Fireplace Clearances If Installed at Floor Level INSTALLING DAMPER CLAMP AC CESSORY FOR VENTED OPERATION Note When used as a vented heater a...

Страница 13: ...e provided with heater approved flexible gas hose not provided if allowed by local codes sealant resistant to propane LP gas not provided electric drill with 3 16 masonry drill bit Note Install option...

Страница 14: ...y to male NPT threads This will prevent excess sealant from going into pipe Excess sealant in pipe could result in clogged heater valves Installation Continued Figure 13 External Regulator With Vent P...

Страница 15: ...or fittings CHECKING GAS CONNECTIONS WARNING Testallgaspiping and connections internal and external to unit for leaks after installing or servicing Correct all leaks at once WARNING Never use an open...

Страница 16: ...Closed Equipment Shutoff Valve Figure 16 Checking Gas Joints Propane LP Tank Equipment Shutoff Valve Control Valve Location Figure 17 Checking Gas Joints Gas Meter Equipment Shutoff Valve Control Valv...

Страница 17: ...ng It is very important to install these logs exactly as instructed Do not modify logs Only use logs supplied with heater 1 Place front log 1 on grate fingers Make sure front log rests firmly between...

Страница 18: ...ON Figure 21 Installing Crossover Log 4 CCL3930PR NRA Shown Log 2 Log 3 Pegs Figure 22 Installing Crossover Log 5 CCL3930PR NRA Shown AUTO OFF ON 7 Figure 24 Installing Crossover Log 7 to Models CCL39...

Страница 19: ...WARNING Burners will come on automatically within one minute when the selector switchisintheONpositionafter the pilot is lit FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not fol low these in...

Страница 20: ...light pilot The pilot is attached to the front burner If needed keep pressing ignitor button until pilot lights Note If pilot does not stay lit contact a qualified service person or gas supplier for...

Страница 21: ...here be tween HI and LO Slide the selector switch to the REMOTE position see Figure 27 Note The burner may light if hand held re mote was on when selector switch was last turned off You can now turn t...

Страница 22: ...Yourlocal computer store hardware store or home center may carry compressed air in a can If using com pressed air in a can please follow the directions on the can If you don t follow directions on th...

Страница 23: ...hen in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tub...

Страница 24: ...After ODS pilot lights keep control knob pressed in 30 seconds 3 Fully open equipment shut off valve 4 A Contact local natural or propane LP gas company B Clean ODS pilot see Cleaning and Maintenance...

Страница 25: ...on and Ventilation require ments page 6 1 Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local natural or propan...

Страница 26: ...ocate and correct all leaks see Checking Gas Con nections page 15 2 Replace control valve 1 Take apart gas tubing and remove foreign matter 2 Locate and correct all leaks see Checking Gas Con nections...

Страница 27: ...0NRA Rating Variable 20 000 39 000 Btu Hr Type Gas Natural Ignition Piezo Manifold Pressure 3 5 W C Inlet Gas Pressure in of water Max 10 5 W C Min 5 W C CCL3924PRA and CCL3930PRA Rating Variable 20 0...

Страница 28: ...27 18 23 12 11 14 4 5 1 2 17 10 21 20 22 6 7 3 9 20 16 8 15 29 28 28 25 26 O F F P I L O T O N H I L O O F F P I L O T O N H I L O 24 31 13 Parts MODELS CCL3924PRA CCL3924NRA CCL3930PRA and CCL3930NRA...

Страница 29: ...Pilot Tube 1 16 103781 02 103781 02 Gas Control Valve LP 1 103781 01 103781 01 Gas Control Valve NG 1 17 103345 01 103345 01 103345 01 103345 01 Lower Bracket 1 18 M11084 38 M11084 38 M11084 38 M1108...

Страница 30: ...elayed ignition heater will not produce specified heat propane LP gas supply may be low You may feel your gas pressure is too low If so contact your local propane LP gas supplier If this product is mi...

Страница 31: ...FMI PRODUCTS LLC at 1 866 328 4538 for information You can also write to the address listed on the back page of this manual RECEIVER AND HAND HELD THERMOSTAT REMOTE CONTROL KIT MLCR M For all Remote...

Страница 32: ...product and or FMI PRODUCTS LLC who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic mat...

Отзывы: