background image

Comfortflame.US.com

900564-00NC

9

INSTALLATION  

Continued

Mantel Clearances for Built-In Installation

If placing custom mantel above built-in firebox, you must meet 

the minimum allowable clearance between mantel shelf and top of 

firebox opening shown in Figure 7. These are the minimum allow-

able mantel clearances for a safe installation. Use larger clearances 

wherever possible to minimize the heating of objects and materials 

placed on the mantel.

 CAUTION: Do not allow the vent-free gas log ap-

pliance to touch or extend beyond the firebox screen.

If your installation does not meet the above minimum clearances in 

Figure 7, you must:

•  raise the mantel to an acceptable height,

OR

•  remove the mantel.

BUILT-IN FIREBOX INSTALLATION

Built-in installation of this firebox involves installing firebox into a 

framed-in enclosure. This makes the front of firebox flush with wall. 

Follow the instructions below to install the firebox in this manner.
1.  Frame in rough opening. The firebox framing should be construct-

ed of 2 x 4 lumber or heavier. Construct framing using dimensions 

shown in Figure 8 and 9, page 10. It is recommended that the 

framing be constructed first and the unit be placed in position by 

removing the nailing flanges from one side. After sliding the unit 

into place, the outer most flanges may be replaced and nailed 

to the framing on all sides before applying the wallboard to the 

exterior framing.

2.  If the vent-free firebox is to be installed directly on carpeting, tile 

(other than ceramic) or any combustible material other than wood 

flooring; the vent-free firebox must be installed upon a metal or 

wood panel extending the full width and depth of the vent-free 

firebox.

Figure 7 - Minimum Mantel Clearances for Built-In Installation

Supplied 

Firebox

Hoods Must

Be Used

at All Times

Wire-mesh

Screen

Firebox Top

Mantel Shelf

3" 

6" 

1

/

4

Combustible 

Material

1

/

2

" Max

Thickness

Note: All vertical

measurements are from

top of fireplace hood to

bottom of mantel shelf.

These minimum

clearances replace any

other recommended

clearances supplied

with your ANS Z21.11.2

approved gas logs.

Wall board or facing material (above firebox)

may be of combustible material, including 

decorative mantel ornaments or other similar

projections off of the facing material.

Top Frame

(Combustible

Material)

 

 

12" 15" 18"

 

Note: Do not

cover louver 

openings.

6" Min. 

 

44 

1

/

4

" Min.

40 

1

/

4

" Min.

36" Min. to 
Facing Wall

22 

3

/

4

"

Min.

Facing

Wall

Wallboard

Wallboard

Gas Line

Facing Wall

 (Base  line)

Note: Gas line 
may also be on 
opposite side.

Figure 8 - Framing for Built-In Firebox Installation

3.  If a raised platform is to be constructed, ceiling clearances must 

be maintained.

4.  Install gas piping to firebox location. See Installing Gas Line and 

Connecting to Gas Supply in log set owner’s manual.

IMPORTANT:

 If installing blower accessory. See Hard-Wiring Firebox, 

page 12.
5.  Carefully set firebox in front of rough opening. 

IMPORTANT:

 If 

installing brass trim kit, see instructions included with brass trim 

accessory. You must install shoulder screws from brass trim kit 

now.

6.  Carefully insert firebox into rough opening. 

7.  Attach firebox to wall studs using nails or wood screws through 

holes in nailing flange (see Figure 10, page 10).

IMPORTANT:

 When finishing your firebox, combustible materials such 

as wall board, gypsum board, sheet rock, drywall, plywood, etc. may 

be butted up next to the sides and top of the firebox. Combustible 

materials should never overlap the firebox front facing.

Содержание Barkley Series

Страница 1: ...stment alteration service or maintenance can cause injury or property damage Refer to this manual for correct installation and operational procedures For assistance or additional information consult a...

Страница 2: ...her flammable material on or near the appliance Never place any objects in the firebox or on logs Firebox front and screen becomes very hot when run ning firebox Keep children and adults away from hot...

Страница 3: ...been under water due to the shock hazard that could result with the blower accessary if installed in place 13 Provide adequate clearances around air openings LOCAL CODES Install and use firebox with...

Страница 4: ...cora tive type unvented room appliances Physical size limitations apply Refer to minimum firebox requirements supplied with log appliance It requires no outside venting or chimney making installation...

Страница 5: ...es page 8 2 Everything needed to complete installation 3 This model CANNOT be installed in a bedroom or bathroom 4 Proper air for combustion and ventilation 5 Consider a location where heat output wou...

Страница 6: ...e criteria above proceed to Determining Fresh Air Flow for Firebox Location Confined and Unconfined Space The National Fuel Gas Code ANS Z223 1 NFPA 54 defines a confined space as a space whose volume...

Страница 7: ...provide two permanent openings one within 12 of the ceiling and one within 12 of the floor on the wall connecting the two spaces see option 1 Figure 3 You can also remove door into adjoining room see...

Страница 8: ...l lations Wall or framing material can be placed against any exterior surface on the rear sides or top of your firebox except where standoff spacers are integrally attached If standoff spacers are att...

Страница 9: ...extending the full width and depth of the vent free firebox Figure 7 Minimum Mantel Clearances for Built In Installation Supplied Firebox Hoods Must Be Used at All Times Wire mesh Screen Firebox Top M...

Страница 10: ...codes IMPORTANT See Connecting to Gas Supply in your log set owner s manual for details on gas hookup You may run the gas line from either side of the firebox see Figure 11 page 11 When you have deter...

Страница 11: ...g the incoming gas line to the appliance regulator Secure all joints tightly with wrench but do not overtighten If a flexible gas line is used take care not to kink the connector WARNING All gas pipin...

Страница 12: ...he receptacle with wires that are routed through the bushing provided see Figure 15 The recep tacle may be relocated to either side when necessary However the cover plate must be replaced over the unu...

Страница 13: ...17 Optional Blower Wiring Diagram INCOMING 120V AC FUSE BOX OR BREAKER BLK BLK GRN GRN WHT WHT FIELD WIRE GND CONNECTORS NOT SUPPLIED VARIABLE SPEED CONTROL BLOWER RECEPTACLE ELECTRICAL RATING 120v 6...

Страница 14: ...s to cool before handling IMPORTANT Turn off the gas supply at the external shutoff valve before servicing appliance Any safety screen or guard removed for servicing must be replaced prior to operatin...

Страница 15: ...umbers of your fireplace ready You can also visit our web site at Comfortflame US com REPLACEMENT PARTS See Pages 16 to 17 for a complete replacement parts list Use only parts supplied from the manufa...

Страница 16: ...ALOG NO MODEL F2564 BarkleySTXWS F2565 BarkleySTYWS These items are used on both sides of fireplace 8 14 16 16 16 7 1 7 2 2 16 11 12 6 6 6 15 15 15 15 13 18 5 15 15 15 15 6 6 15 15 4 15 15 15 15 15 15...

Страница 17: ...tom Refractory Brick Liner 2 8 J7021 Side Refractory Retainer 4 9 J5691 Screen 4 10 J7104 Top Louver 2 11 J7105 Bottom Louver 2 12 J6835 Receptacle 15A DVP 1 J8145 Handy Box 1 7 8 Deep 1 J8146 Cover D...

Страница 18: ..._______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ___...

Страница 19: ...will cause damage to the Product will produce excessive temperatures and could result in a fire hazard c damages caused by failing to provide proper maintenance and service in accordance with the inst...

Страница 20: ...s pricesandalsotodiscontinuecolors stylesandproducts Consult your local distributor for fireplace code information Printed in U S A 2015 IHP LLC P N 900564 00 Rev N C 09 2015 1508 Elm Hill Pike Suite...

Отзывы: