background image

Comfortflame.US.com

900564-00NC

7

You must provide additional fresh air. Your options are as follows:
A.  Rework work sheet, adding the space of an adjoining room. If the 

extra space provides an unconfined space, remove door to adjoin-

ing room or add ventilation grills between rooms. See Ventilation 

Air from Inside Building.

B.  Vent room directly to the outdoors. See Ventilation Air from 

Outdoors, .

C.  Install a lower Btu/Hr gas log appliance, if lower Btu/Hr size makes 

room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space 

can support, the space is an unconfined space. You will need no ad-

ditional fresh air ventilation.

 WARNING: If the area in which the appliance may 

be operated does not meet the required volume for 

indoor combustion air, combustion and ventilation air 

shall be provided by one of the methods described in 

the National Fuel Gas Code, ANSI Z223.1/NFPA 54, the 

International Fuel Gas Code, or applicable local codes.

VENTILATION AIR
Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When 

ventilating to an adjoining unconfined space, you must provide two 

permanent openings: one within 12" of the ceiling and one within 

12" of the floor on the wall connecting the two spaces (see option 1, 

Figure 3). You can also remove door into adjoining room (see option 

2, Figure 3). Follow the National Fuel Gas Code ANS Z223.1/NFPA 

54 Air for Combustion and Ventilation for required size of ventilation 

grills or ducts. 

AIR FOR COMBUSTION AND VENTILATION  

Continued

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must 

provide two permanent openings: one within 12" of the ceiling and one 

within 12" of the floor. Connect these items directly to the outdoors 

or spaces open to the outdoors. These spaces include attics and 

crawl spaces. Follow the National Fuel Gas Code ANS Z223.1/NFPA 

54 Air for Combustion and Ventilation for required size of ventilation 

grills or ducts.

IMPORTANT:

 Do not provide openings for inlet or outlet air into attic 

if attic has a thermostat-controlled power vent. Heated air entering 

the attic will activate the power vent.

Figure 3 - Ventilation Air from Inside Building

Or

Remove

Door into
Adjoining

Room,
Option

2

Ventilation

Grills Into

Adjoining 

Room,

Option 1

Figure 4 - Ventilation Air from Outdoors

Outlet

Air

Ventilated

Attic 

Outlet

Air

Inlet

Air

Inlet Air

Ventilated 

Crawl Space

To 

Crawl

Space

To Attic

Содержание Barkley Series

Страница 1: ...stment alteration service or maintenance can cause injury or property damage Refer to this manual for correct installation and operational procedures For assistance or additional information consult a...

Страница 2: ...her flammable material on or near the appliance Never place any objects in the firebox or on logs Firebox front and screen becomes very hot when run ning firebox Keep children and adults away from hot...

Страница 3: ...been under water due to the shock hazard that could result with the blower accessary if installed in place 13 Provide adequate clearances around air openings LOCAL CODES Install and use firebox with...

Страница 4: ...cora tive type unvented room appliances Physical size limitations apply Refer to minimum firebox requirements supplied with log appliance It requires no outside venting or chimney making installation...

Страница 5: ...es page 8 2 Everything needed to complete installation 3 This model CANNOT be installed in a bedroom or bathroom 4 Proper air for combustion and ventilation 5 Consider a location where heat output wou...

Страница 6: ...e criteria above proceed to Determining Fresh Air Flow for Firebox Location Confined and Unconfined Space The National Fuel Gas Code ANS Z223 1 NFPA 54 defines a confined space as a space whose volume...

Страница 7: ...provide two permanent openings one within 12 of the ceiling and one within 12 of the floor on the wall connecting the two spaces see option 1 Figure 3 You can also remove door into adjoining room see...

Страница 8: ...l lations Wall or framing material can be placed against any exterior surface on the rear sides or top of your firebox except where standoff spacers are integrally attached If standoff spacers are att...

Страница 9: ...extending the full width and depth of the vent free firebox Figure 7 Minimum Mantel Clearances for Built In Installation Supplied Firebox Hoods Must Be Used at All Times Wire mesh Screen Firebox Top M...

Страница 10: ...codes IMPORTANT See Connecting to Gas Supply in your log set owner s manual for details on gas hookup You may run the gas line from either side of the firebox see Figure 11 page 11 When you have deter...

Страница 11: ...g the incoming gas line to the appliance regulator Secure all joints tightly with wrench but do not overtighten If a flexible gas line is used take care not to kink the connector WARNING All gas pipin...

Страница 12: ...he receptacle with wires that are routed through the bushing provided see Figure 15 The recep tacle may be relocated to either side when necessary However the cover plate must be replaced over the unu...

Страница 13: ...17 Optional Blower Wiring Diagram INCOMING 120V AC FUSE BOX OR BREAKER BLK BLK GRN GRN WHT WHT FIELD WIRE GND CONNECTORS NOT SUPPLIED VARIABLE SPEED CONTROL BLOWER RECEPTACLE ELECTRICAL RATING 120v 6...

Страница 14: ...s to cool before handling IMPORTANT Turn off the gas supply at the external shutoff valve before servicing appliance Any safety screen or guard removed for servicing must be replaced prior to operatin...

Страница 15: ...umbers of your fireplace ready You can also visit our web site at Comfortflame US com REPLACEMENT PARTS See Pages 16 to 17 for a complete replacement parts list Use only parts supplied from the manufa...

Страница 16: ...ALOG NO MODEL F2564 BarkleySTXWS F2565 BarkleySTYWS These items are used on both sides of fireplace 8 14 16 16 16 7 1 7 2 2 16 11 12 6 6 6 15 15 15 15 13 18 5 15 15 15 15 6 6 15 15 4 15 15 15 15 15 15...

Страница 17: ...tom Refractory Brick Liner 2 8 J7021 Side Refractory Retainer 4 9 J5691 Screen 4 10 J7104 Top Louver 2 11 J7105 Bottom Louver 2 12 J6835 Receptacle 15A DVP 1 J8145 Handy Box 1 7 8 Deep 1 J8146 Cover D...

Страница 18: ..._______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ___...

Страница 19: ...will cause damage to the Product will produce excessive temperatures and could result in a fire hazard c damages caused by failing to provide proper maintenance and service in accordance with the inst...

Страница 20: ...s pricesandalsotodiscontinuecolors stylesandproducts Consult your local distributor for fireplace code information Printed in U S A 2015 IHP LLC P N 900564 00 Rev N C 09 2015 1508 Elm Hill Pike Suite...

Отзывы: