background image

506843-01

Page 39  of  39

Issue 1132

REQUIREMENTS for COMMONWEALTH of MASSACHUSETTS

Modifications to NFPA-54, Chapter 10 -

Revise NFPA-54 section 10.8.3 to add the following

requirements:

For all side wall, horizontally vented, gas fueled equipment

installed in every dwelling, building or structure used in

whole or in part for residential purposes, including those

owned or operated by the Commonwealth and where the

side wall exhaust vent termination is less than seven (7)

feet above the finished grade in the area of the venting,

including but not limited to decks and porches, the following

requirements shall be satisfied:
1.

INSTALLATION OF CARBON MONOXIDE

DETECTORS.

 At the time of installation of the side

wall, horizontally vented, gas-fueled equipment, the

installing plumber or gas fitter shall observe that a

hard wired carbon monoxide detector with an alarm

and battery backup is installed on the floor level where

the gas equipment is to be installed.  In addition, the

installing plumber or gas fitter shall observe that a

battery operated or hard wired carbon monoxide

detector with an alarm is installed on each additional

level of the dwelling, building or structure served by

the side wall, horizontally vented, gas fueled

equipment.  It shall be the responsibility of the property

owner to secure the services of qualified licensed

professionals for the installation of hard wired carbon

monoxide detectors.

a. In the event that the side wall, horizontally vented,

gas fueled equipment is installed in a crawl space

or an attic, the hard wired carbon monoxide

detector

with alarm and

battery backup may be installed on

the next adjacent floor level.

b. In the event that the requirements of this

subdivision

cannot be met

at the time of completion of

installation, the owner shall have a period of thirty

(30) days to comply with the above requirements;

provided, however, that during said thirty (30) day

period, a battery operated carbon monoxide

detector with an alarm shall be installed.

2.

APPROVED CARBON MONOXIDE DETECTORS.

Each carbon monoxide detector as required in

accordance with the above provisions shall comply

with NFPA 720 and be ANSI/UL 2034 listed and IAS

certified.

3.

SIGNAGE

.   A metal or plastic identification plate shall

be permanently mounted to the exterior of the building

at a minimum height of eight (8) feet above grade

directly in line with the exhaust vent terminal for the

horizontally vented, gas fueled heating appliance or

equipment.  The sign shall read, in print size no less

than one half (1/2) inch in size, 

“GAS VENT DIRECTLY

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”

4. INSPECTION. The state or local gas inspector of the

side wall, horizontally vented, gas-fueled equipment

shall not approve the installation unless, upon

inspection, the inspector observes carbon monoxide

detectors and signage installed in accordance with

the provisions of 248 CMR 5.08(2)(a) 1 through 4.

EXEMPTIONS:  The following equipment is exempt

from 24 CMR 5.08(2)(a) 1 through 4:

1. The equipment listed in Chapter 10 entitled “Equipment

Not Required to Be Vented” in the most current edition

of NFPA 54 as adopted by the Board; and

2. Product Approved side wall, horizontally vented, gas

fueled equipment installed in a room or structure

separate from the dwelling, building or structure used

in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS -

GAS EQUIPMENT VENTING SYSTEM PROVIDED.

When the manufacturer of Product Approved side wall,

horizontally vented, gas fueled equipment provides a

venting system design or venting system components with

the equipment, the instructions provided by the

manufacturer for installation of the equipment and the

venting system shall include:

1. Detailed instructions for the installation of the venting

system design or the venting system components:

and

2. A complete parts list for the venting system design or

venting system.

MANUFACTURER REQUIREMENTS -

GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.

When the manufacturer of Product Approved sidewall,

horizontally vented, gas fueled equipment does not provide

the parts for venting the flue gases, but identifies “special

venting systems,” the following requirements shall be

satisfied by the manufacturer:

1. The referenced “special venting system” instructions

shall be included with the appliance or equipment

installation instructions; and

2. The “special venting systems” shall be Product

Approved by the Board, and the instructions for that

system shall include a parts list and detailed

installation instructions.

A copy of all installation instructions for all Product

Approved side wall, horizontally vented, gas fueled

equipment, all venting instructions, all parts lists for

venting instructions, and/or all venting design

instructions shall remain with the appliance or

equipment at the completion of the installation.

Содержание Century GDD80C

Страница 1: ...ING This manual must be left with the homeowner for future reference INSTALLATION INSTRUCTIONS GDD80C Warm Air Gas Furnace Downflow Air Discharge P 506843 01 P506843 01 UnitDimensions 2 GDD80CPartsArr...

Страница 2: ...DD80C Unit Dimensions inches mm FRONT VIEW SIDE VIEW A 368 14 1 2 Model GDD80C B C in mm in mm in mm 340 13 3 8 330 13 533 21 504 19 7 8 495 19 1 2 D in mm 203 8 121 4 3 4 070B3 090B4 110C5 045A3 446...

Страница 3: ...01 Page 3 of 39 Issue 1132 Expanded View Figure 1 BLOWER ASSEMBLY CABINET CONTROL BOX INTERNAL FLUE PIPE ASSEMBLY FLUE CHASE HEAT EXCHANGER GAS VALVE ACCESS PANEL BURNER BOX ASSEMBLY COMBUSTION AIR I...

Страница 4: ...by a licensed professional installer or equivalent service agency or the gas supplier WARNING Certifications These units are CSAInternational certified to ANSI Z21 47 In the USA installation of gas f...

Страница 5: ...m thermostat must control the furnace The use of fixed jumpers that will provide continuous heating is not allowed The return air duct must be provided and sealed to the furnace Return air temperature...

Страница 6: ...wndraft can occur in the furnace vent pipe or chimney As a result combustion gases enter the living space creating a potentially dangerous situation In the absence of local codes concerning air for co...

Страница 7: ...ining the furnace the return air must be handled by ducts which are sealed to the furnace casing and which terminate outside the space containing the furnace This is especially important when the furn...

Страница 8: ...et and outlet air openings shall each have a free area of at least one square inch per 4 000 Btu 645 mm per 1 17 kW per hour of the total input rating of all equipment in the enclosure Figure 5 EQUIPM...

Страница 9: ...er housing Setting Equipment WARNING Do not install the furnace on its front or its back Do not connect the return air ducts to the back of the furnace Doing so will adversely affect the operation of...

Страница 10: ...ce may be installed on a combustible wood floor if an optional additive base is installed between the furnace and the combustivle floor WARNING Improper installation of the furnace can result in perso...

Страница 11: ...s for correctly sized opening in floor and installation of cabinet 2 When cooling cabinet is in place set and secure the furnace according to the instructions that are provided with the cooling coil S...

Страница 12: ...red for the unit to operate properly A filter must be in place any time the unit is operating Duct System Use industry approved standards such as those published by Air Conditioning Contractors of Ame...

Страница 13: ...for common venting A chimney with one or more sides exposed to the outside of the structure is considered to be an exterior chimney An exterior masonry chimney that is not tile lined must be lined wit...

Страница 14: ...ney Never connect a Category I appliance to a chimney that is servicing a solid fuel appliance If a fireplace chimney flue is used to vent this appliance the fireplace opening must be permanently seal...

Страница 15: ...nts between sections of single wall connector piping shall be fastened by screws or other approved means 13 When the vent connector used for Category I appliances must be located in or pass through a...

Страница 16: ...onfigureations with zero lateral lengths are assumed to have no elbows in the vent system For all other vent configurations the vent system is assumed to have two 90 elbows For each additional 90 elbo...

Страница 17: ...onfigureations with zero lateral lengths are assumed to have no elbows in the vent system For all other vent configurations the vent system is assumed to have two 90 elbows For each additional 90 elbo...

Страница 18: ...Capacity Type B Double Wall Vents with Type B Double Wall Connectors Serving Two or More Category I Appliances Common Vent Capacity Type B Double Wall Vents with Type B Double Wall Connectors Serving...

Страница 19: ...Two or more Category I Appliances Table 8 NOTE Single appliance venting configureations with zero lateral lengths are assumed to have no elbows in the vent system For all other vent configurations the...

Страница 20: ...are located and other spaces of the building Turn on clothes dryers and any appliances not connected to the common venting system Turn on any exhaust fans such as range hoods and bathroom exhausts so...

Страница 21: ...The piping must be supported at proper intervals every 8 to 10 feet 2 44 to 3 01 m with suitable hangers or straps Install a drip leg in vertical pipe runs to the unit 5 A 1 8 N P T plugged tap or pr...

Страница 22: ...gas lines gas valve must be disconnected and isolated See Figure 19 Gas valves can be damaged if subjected to pressures greater than 1 2 psig 3 48 kPa 14 inches w c IMPORTANT Electrostatic discharge c...

Страница 23: ...25 for integrated control configuration This terminal is energized when the indoor blower is operating Any accessory rated up to one amp can be connected to this terminal with the neutral leg of the...

Страница 24: ...hermostat instructions Indoor Blower Speeds 1 When the thermostat is set to FAN ON the indoor blower will run continuously on the fan speed when there is no cooling or heating demand 2 When the unit i...

Страница 25: ...506843 01 Page 25 of 39 Issue 1132 Wiring Diagram Figure 23 045A3M 070B3M 045A3M 090B4M 110C5M...

Страница 26: ...506843 01 Page 26 of 39 Issue 1132 Typical Field Wiuring Diagram Figure 24 Figure 25 Integrated Control Automatic Hot Surface Ignition System...

Страница 27: ...ns exactly a fire or explosion may result causing property damage personal injury or death WARNING 6 Move switch on gas valve to OFF Do not force See Figure 26 7 Wait five minutes to clear out any gas...

Страница 28: ...curate reading shut off all other gas appliances connected to meter Supply Pressure Measurement A threaded plug on the inlet side of the gas valve provides access to the supply pressure tap Remove the...

Страница 29: ...lower is deenergized Longer off delay settings provide lower return air temperatures shorter settings provide higher return air temperatures See Figure 28 Table 12 For Safety shut unit off and remove...

Страница 30: ...rn off electrical power to furnace 2 Remove blower access panel 3 Disconnect existing speed tap at integrated control speed terminal NOTE Termination of any unused motor leads must be insulated 4 Plac...

Страница 31: ...60 415 1425 300 240 1225 215 0 40 1615 430 1395 310 255 1185 0 50 1570 450 325 1210 265 1145 240 0 60 1545 465 340 1165 280 1085 315 0 70 N A 350 1120 295 1040 265 0 80 N A 365 1080 305 280 Low cfm Wa...

Страница 32: ...connections 2 Check for the correct voltage at the furnace furnace operating Correct voltage is 120VAC 10 3 Check amp draw on the blower motor with inner blower panel in place Unit Nameplate_________...

Страница 33: ...ve the combustion air inducer to avoid damaging blower gasket If gasket is damaged it must be replaced to prevent leakage 5 Remove the collector box located behind the combustion air inducer Be carefu...

Страница 34: ...x inserts 16 Reinstall collector box and combustion air assembly Reinstall all screws to the collector box and combustion air inducer Failure to replace all screws may cause leaks Inspect gaskets for...

Страница 35: ...seal between the return air and the room where the furnace is installed Return air duct Must be properly attached and provide an air seal to the unit Operating performance Unit must be observed during...

Страница 36: ...epair parts are available through independent Allied Air dealers When ordering parts include the complete furnace model number listed on the CSA International nameplate Example GDD80C045A3M All servic...

Страница 37: ...506843 01 Page 37 of 39 Issue 1132 Start Up Performance Check List UNIT SET UP...

Страница 38: ...506843 01 Page 38 of 39 Issue 1132 UNIT OPERATION...

Страница 39: ...imum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less...

Отзывы: