506843-01
Page 39 of 39
Issue 1132
REQUIREMENTS for COMMONWEALTH of MASSACHUSETTS
Modifications to NFPA-54, Chapter 10 -
Revise NFPA-54 section 10.8.3 to add the following
requirements:
For all side wall, horizontally vented, gas fueled equipment
installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those
owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7)
feet above the finished grade in the area of the venting,
including but not limited to decks and porches, the following
requirements shall be satisfied:
1.
INSTALLATION OF CARBON MONOXIDE
DETECTORS.
At the time of installation of the side
wall, horizontally vented, gas-fueled equipment, the
installing plumber or gas fitter shall observe that a
hard wired carbon monoxide detector with an alarm
and battery backup is installed on the floor level where
the gas equipment is to be installed. In addition, the
installing plumber or gas fitter shall observe that a
battery operated or hard wired carbon monoxide
detector with an alarm is installed on each additional
level of the dwelling, building or structure served by
the side wall, horizontally vented, gas fueled
equipment. It shall be the responsibility of the property
owner to secure the services of qualified licensed
professionals for the installation of hard wired carbon
monoxide detectors.
a. In the event that the side wall, horizontally vented,
gas fueled equipment is installed in a crawl space
or an attic, the hard wired carbon monoxide
detector
with alarm and
battery backup may be installed on
the next adjacent floor level.
b. In the event that the requirements of this
subdivision
cannot be met
at the time of completion of
installation, the owner shall have a period of thirty
(30) days to comply with the above requirements;
provided, however, that during said thirty (30) day
period, a battery operated carbon monoxide
detector with an alarm shall be installed.
2.
APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required in
accordance with the above provisions shall comply
with NFPA 720 and be ANSI/UL 2034 listed and IAS
certified.
3.
SIGNAGE
. A metal or plastic identification plate shall
be permanently mounted to the exterior of the building
at a minimum height of eight (8) feet above grade
directly in line with the exhaust vent terminal for the
horizontally vented, gas fueled heating appliance or
equipment. The sign shall read, in print size no less
than one half (1/2) inch in size,
“GAS VENT DIRECTLY
BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
4. INSPECTION. The state or local gas inspector of the
side wall, horizontally vented, gas-fueled equipment
shall not approve the installation unless, upon
inspection, the inspector observes carbon monoxide
detectors and signage installed in accordance with
the provisions of 248 CMR 5.08(2)(a) 1 through 4.
EXEMPTIONS: The following equipment is exempt
from 24 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment
Not Required to Be Vented” in the most current edition
of NFPA 54 as adopted by the Board; and
2. Product Approved side wall, horizontally vented, gas
fueled equipment installed in a room or structure
separate from the dwelling, building or structure used
in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS -
GAS EQUIPMENT VENTING SYSTEM PROVIDED.
When the manufacturer of Product Approved side wall,
horizontally vented, gas fueled equipment provides a
venting system design or venting system components with
the equipment, the instructions provided by the
manufacturer for installation of the equipment and the
venting system shall include:
1. Detailed instructions for the installation of the venting
system design or the venting system components:
and
2. A complete parts list for the venting system design or
venting system.
MANUFACTURER REQUIREMENTS -
GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.
When the manufacturer of Product Approved sidewall,
horizontally vented, gas fueled equipment does not provide
the parts for venting the flue gases, but identifies “special
venting systems,” the following requirements shall be
satisfied by the manufacturer:
1. The referenced “special venting system” instructions
shall be included with the appliance or equipment
installation instructions; and
2. The “special venting systems” shall be Product
Approved by the Board, and the instructions for that
system shall include a parts list and detailed
installation instructions.
A copy of all installation instructions for all Product
Approved side wall, horizontally vented, gas fueled
equipment, all venting instructions, all parts lists for
venting instructions, and/or all venting design
instructions shall remain with the appliance or
equipment at the completion of the installation.