14
IE-SNC-T33(4)11+T73(4)10-07
Recommended calibration interval:
1 year
Measuring interval and LCD display refresh:
0.5 s, atmospheric pressure 2 s
Power:
9 to 30 V dc
Consumption: T3311(L), T3313(L), T7310(L)
6 mA
T3411(L), T7410(L)
max. 0.5W
Protection of the case with electronics and terminals:
T3311(L), T3313(L) T3411(L)
IP65
T7310(L), T7410(L)
IP54
Protection of the sensor cover:
IP40
Filtering ability of the sensor cover:
0.025 mm
Operating conditions:
Operating temperature range: -30 to +80 °C, over +70°C switch LCD display off
Operating temperature range of measuring tip with sensor
T3313(L)
: -30 to +125 °C
Operating relative humidity range: 0 to 100 %RH
Outer influence in accordance with Czech National Standard 33-2000-3:
normal environment with those specifications: AE1, AN1, AR1, BE1
Working position: with sensor cover downwards
Electromagnetic compatibility: complies EN 61326-1
Not allowed manipulation
:
It is not allowed to operate the device under conditions other than
specified in technical parameters. Devices are not designed for locations with chemically
aggressive environment. Temperature and humidity sensors must not be exposed to direct
contact with water or other liquids. It is not allowed to remove the sensor cover—to avoid
any mechanical damage of the sensors.
Do not use the device in an explosive
environment.
Storing conditions:
temperature -30 to +80 °C, humidity 0 to 100 %RH without condensation
Dimensions:
see dimensional drawings
Weight:
approximately: T3311 230 g, T3311L 150 g, T7310 230 g, T7310L 150 g,
T3313 305 g, T3313L 225 g, T3411(L) 150 g, T7410(L) 155 g
Material of the case:
ABS
End of operation
Device itself (after its life) is necessary to liquidate ecologically!
Technical support and service
Technical support and service is provided by distributor. For contact see warranty certificate.
4
There is possible to change response time. For more details see file “Description of calibration and
adjustment procedure.pdf”, which is installed together with Users software.