Comet System T2314 Скачать руководство пользователя страница 8

 

  IE-SNC-T23(4)14-04 

 

If jumper during switching ON the power is not closed, device communicates in accordance 
with stored setting. 

 

If jumper is closed during device operation, device temporarily changes its address to 00h, 
it will  communicate  in  the  same  communication  speed  as  before  closing  jumper  and  will 
communicate without check sum. After jumper is opened setting of address and check sum 
is reset in accordance with values stored in the device. 

 

Communication speed and check sum are possible to change only if jumper is closed. 

 

Jumper  closed  and  button  pressed  for  longer  than  six  seconds  –  causes  restoring  of 
manufacturer  setting 

of  communication  protocol

,  i.e.  sets  Modbus  RTU  communication 

protocol, device address sets to 01h and communication speed to 9600Bd - after button press 
there  is  “dEF”  message  blinking  at  LCD  display.  Six  seconds  later  message  “dEF”  stays 
shown, it means manufacturer setting 

of communication protocol

 is done. 

 

ARION communication protocol - AMiT company 

The device supports communication protocol ARiON version 1.00. For more details see file 

Description of communication protocols of Txxxx series

 or 

www.amit.cz

. 

 

Communication with HWg Poseidon units 

 

Device  supports  communication  with  HWg-Poseidon  units.  For  communication  with  this 

unit set the device with setup software TSensor to communication protocol HWg–Poseidon and set 
correct  device  address.  This  communication  protocol  supports  read  temperature  at  °C,  relative 
humidity,  one  of  computed  value  (dew  point  temperature  or  absolute  humidity)  and  barometric 
pressure  at  kPa (depended by device type).  For  atmospheric pressure correction to  altitude setting 
there is Users software TSensor. 

Jumper and button 

If  communication  with  HWg  Poseidon  unit  is  selected,  the  function  of  jumper  and  button  is  as 
follows: 

 

Jumper  opened  and  button  shortly  pressed  –  device  goes  to  Info  mode,  see  chapter  „Info 
mode“

 

Jumper  closed  and  button  pressed  for  longer  than  six  seconds  –  causes  restoring 
of manufacturer setting 

of communication protocol

, i.e. sets Modbus RTU communication 

protocol, device address sets to 01h and communication speed to 9600Bd - after button press 
there  is  “dEF”  message  blinking  at  LCD  display.  Six  seconds  later  message  “dEF”  stays 
shown, it means manufacturer setting 

of communication protocol

 is done. 

 
 

Error States of the device 

Device continuously checks its state during operation. In case error is found LCD displays 

corresponding error code: 

Error 0 

First line displays „Err0“. 
Check sum error of stored setting inside device’s memory. This error appears if incorrect writing 
procedure  to  device’s  memory  occurred  or  if  damage  of  calibration  data  appeared.  At  this  state 
device does not measure and calculate values. It is a serious error, contact distributor of the device 
to fix. 

Содержание T2314

Страница 1: ...cturer reserves the right to make technical changes to the device without previous notice Misprints reserved Manufacturer is not responsible for damages caused by using the device in conflict with thi...

Страница 2: ...www cometsystem com It supports make the adjustment of the device too This procedure is described at file Calibration manual pdf which is installed commonly with the software Change of some parameter...

Страница 3: ...r side The cable should be led in one line i e NOT to tree or star Termination resistor should be located at the end For short distance other topology is allowed Terminate the network by a termination...

Страница 4: ...4 IE SNC T23 4 14 04 Dimensions T2314 Transmitter with RS232 Dimensions T2414 Transmitter with RS485 Dimensions T2314L T2414L Connection see Appendix B...

Страница 5: ...IE SNC T23 4 14 04 5 Typical application wiring connection of terminals T2314 power from communication port T2314 power from external voltage source T2414 RS485...

Страница 6: ...bit registers Read Holding Registers 04 0x04 Reading of 16 bit input gates Read Input Registers 16 0x10 Setting of more 16 bit registers Write Multiple Registers Jumper and button Jumper and button ar...

Страница 7: ...g Note In case there is a need for reading of measured values from the device with higher resolution than one decimal measured values in device are stored also in Float format which is not directly co...

Страница 8: ...ce with setup software TSensor to communication protocol HWg Poseidon and set correct device address This communication protocol supports read temperature at C relative humidity one of computed value...

Страница 9: ...sure or error state of value If selected pressure unit is mBar or oz in2 or mmHg or inH2O or kPa there is shown only value number without corresponding pressure unit symbol 3 near by left display marg...

Страница 10: ...allowed manipulation It is not allowed to operate the device under conditions other than specified in technical parameters Devices are not designed for locations with chemically aggressive environmen...

Страница 11: ...connector marked RS232 directly to the PC connect power to connector marked RS485 Power voltage 6V DC from an external acdc adapter connect to pin 9 0V connect to pin 5 Also mutually connect pin 2 and...

Отзывы: