IE-HGS-H5(6)0XX-05 

5.  Description of device function and setting 

5.1. 

Device setting from the manufacturer 

Value assigned to Relay1 and Relay2: 

none

 

Password for setting through keys:   

0000 

LCD display:   

 

 

 

on

 

value shown at first LCD line: 

 

temperature / CO

2

 - by device type

 

value shown at second LCD line: 

 

relative humidity

 

/

 

dew point temp. - by device type 

temperature unit: 

 

 

 

°C 

computed value preset: 

 

 

dew point

 

temperature 

relay response for error: 

 

 

stay unchanged at previous condition

 

acoustic alarm: 

 

 

 

off 

LED indication: 

up to 1000 ppm lights green LED, between 1000 and 
1200 ppm lights yellow LED and over 1200 ppm 
lights red LED 

altitude: 

 

 

 

 

300 m above sea level at the installation site 

 
 

 

5.2. 

Relay outputs 

Regulator is equipped with two relay outputs. It is possible to assign any input or computed value 

to each relay, to set comparing alarm limit, if the relay may close if measured value is higher (HI) 
or lower (Lo) than preset limit, delay for while must be preset condition true before relay close its 
contact and hysteresis for return to open status. Each relay status is indicated with LED diode and 
shown on LCD with corresponding symbols „

“ or „

“. 

Terminal block for connecting the relays is equipped with terminals GND, which are connected 

to the power supply of the device (see chapter 

Device connection

). When you need to use relays to 

switching the voltage identical with the supply voltage of the device, you can use jumpers J1 and J2 
for interconnection the power supply of the device directly with the common contacts of the relays. 

This  modification  is  used  in  devices  with  serial  number  higher  than  16981000 

(the  wiring 

diagram  of  the  relay  contacts  for  devices  with  serial  number  lower  than  16981000  is  given 
in the 

Appendix B

”)

The devices are equipped with two relays that are not intended for direct switching power circuits 

or  mains  voltage.  If  necessary,  use  suitable  type  of  external  relay  (an  example  of  wiring  is  given 
in the 

Appendix A”

). 

 
 
 

5.3. 

Carbon dioxide concentration measurement 

A multiple point CO2 and temperature adjustment procedure leads to excellent CO2 measurement 

accuracy over the entire temperature working range; this is a must for process control and  outdoor 
applications.  The  dual  wavelength  NDIR  CO2  sensing  procedure  compensates  automatically  for 
ageing effects. The CO2 module is highly resistant to pollution and offers maintenance free operation 
and  outstanding  long  term  stability.  Measured  values  can  be  read  in  „SLOW  mode“  (filtered, 
averaged) or in „FAST mode“ (current values without averaging). SLOW mode has advantages in 
applications  like  climate  control  because  of  filtering  short  time  peaks.  As  an  example  exhaled  air 
from an employee passing the sensor could affect the climate control negatively with a short response 
time  because  the  control  would  trigger  a  change  of  the  ventilation  based  on  this  one-time 
measurement. On the contrary in „FAST mode“ no software filter is used for calculating the output 

Содержание H5021

Страница 1: ...CO2 concentration temperature humidity and other calculated humidity variables regulator with two relay outputs H5021 H5024 H6020 Instruction Manual...

Страница 2: ...etting with using regulator keys 10 5 5 3 Extended setting mode 10 5 6 Restore to Factory default measurement part 14 6 ERROR STATES OF THE DEVICE 14 7 READINGS ON LCD DISPLAY 15 8 PREVENTIVE MAINTENA...

Страница 3: ...evice connection please Models marked HxxxxZ are non standard versions of the devices Description is not included in this manual Copyright COMET System Ltd It is prohibited to copy and edit this instr...

Страница 4: ...connection terminals are accessible after demounting of four screws in the corners of the box and removing the lid There is recommended to use screws with half round head with cross recessed screw ST...

Страница 5: ...IE HGS H5 6 0XX 05 5 3 Dimensions H5024 H6020...

Страница 6: ...IE HGS H5 6 0XX 05 6 H5021 4 Device connection...

Страница 7: ...upply voltage of the device you can use jumpers J1 and J2 for interconnection the power supply of the device directly with the common contacts of the relays This modification is used in devices with s...

Страница 8: ...d then Relay2 setting step by step Information about Relay1 are indicated with symbol for Relay2 with symbol at right top corner of LCD It is possible to edit parameters after pressing SET key and ent...

Страница 9: ...ion of internal setting new setting is possible to write only while during write period press SET key do requested setting in TSensor software press SET key on regulator and keep it down then click on...

Страница 10: ...nd changes are valid immediately after its storing it is NOT necessary to restart regulator 5 5 3 Extended setting mode During regulator operation it is possible to change only parameters described in...

Страница 11: ...found then output relay stays unchanged in previous status Relay1 switch OFF Relay1 switch On stays unchanged in previous status Relay2 switch OFF Relay2 switch On Change of Password for setting thro...

Страница 12: ...between green and yellow indication It means that if actual measured value is lower than YELL limit there is green LED active If actual measured value is higher than YELL limit then there is yellow LE...

Страница 13: ...ing show value on LCD don t show value on LCD Show CO2 concentration at LCD display This item provides to choice if CO2 value may be displayed at LCD display or not It is possible to change it after S...

Страница 14: ...is over upper limit of allowed full scale range There is a reading Err1 on LCD display Value read from the device is 999 9 This state appears in case of Measured temperature is higher than approximat...

Страница 15: ...ncorrect writing procedure to device s memory occurred Error 9 inserted password is not valid there is shown for short time message Err9 on LCD display 7 Readings on LCD display C F reading next to th...

Страница 16: ...125Vac 2A 60 W 62 5 VA EMC EN 61326 1 EN 55011 9 1 2 H5021 CO2 regulator Concentration of CO2 Accuracy 100 ppm 5 of measuring value at 25 C 77 F and 1013 hPa Range 0 to 10000 ppm Temperature dependen...

Страница 17: ...50 C 32 to 122 F Long term stability typ 20 ppm year Resolution 1 ppm Measuring temperature and humidity range is limited in accordance with the graph below Response time measurement of temperature a...

Страница 18: ...ew point temperature Range 60 to 80 C 76 to 176 F Accuracy 1 5 C 2 7 F at ambient temperature T 25 C 77 F and relative humidity RH 30 for more details see graphs below Absolute humidity Range 0 to 400...

Страница 19: ...itch off the LCD display at ambient temperatures above 70 C 158 F around electronics Operating humidity range H5021 0 to 100 RH no condensation H5024 H6020 5 to 95 RH no condensation Operating pressur...

Страница 20: ...5 to 95 RH no condensation atmospheric pressure 700 a 1100 hPa Dimensions see dimensional drawings Weight approximately H5021 1m probe 420 g H5021 2m probe 450 g H5021 4m probe 510 g H5024 330 g H6020...

Страница 21: ...Connection of external power relay Coil data chart of external power relay nominal voltage max 50V nominal power max 60VA current max 2A 11 Appendix B Wiring diagram of relay contacts for devices wit...

Отзывы: