background image

IST-2237.EO01.01

 

Istruzione / User’s Manual / Manuel d’utilisation 

Pag.11/11

 

 

 

 

TECNOCONTROL S.r.l. Via Miglioli 47 SEGRATE ( MI ) 

 

Tel. +39 02 26922890 - Fax +39 02 2133734

 

 

 

 

Fig. 1 –

 

Dimensioni /

 Size / 

Dimensions 

 

 

1

 

2

 

3

 

4

 

ON

 

OFF

 

Centrale rivelazione gas 

Gas Central Unit

 

Centrale de détection

 

RL

 

-

 

+

 

Dip Switch

 

mV

 

Test Uscita  

Output Test 

Sortie Test 

40÷200mV

 

 

 

 

 

Uscita in 4÷20 mA 

4÷20 mA Output 

Sortie en 4÷20 mA

 

 

 

ALARM 1 

 

 

ALARM 2 

 

 

 

 

ALARM 3 

 

 

FAULT 

SET

 

Fig. 2 -

 Schema di collegamento

 

/ Wiring diagram / Schéma

 

TESTmV

 

TP2 

TP1 

Scheda Uscite Relé / Relays Output Board / Sortie sur Realis

 

12

-2

4V

 

m

A

 

12÷24Vdc 

Alimentazione 

Power Supply 

Alimentation

 

 

 

Fig. 3 -

 Tester di calibrazione 

/ Calibration Tester / Kit de Calibration 

F1 

F2 

Tasti / 

Key / Touches

 

TC014

 

0,3 L/min

 

1 L/min

 

 

 

Alimentazione 

/ Power Supply / Alimentation

 

100

 

300

 

400

 

500

 

50

 

0

 

5

 

200

 

Vdc

 

RL=Resistenza di carico 

/ Load resistor / Resistance de charge

 

RL

 

Ohm

 

Fig.4 -

 

Alimentazione / Resistenza di Carico 4÷20mA 

Power supply / Load resistance diagram 4÷20mA 
Alimentation / Résistance de charge 4÷20mA

 

600

 

0

 

10

 

15

 

20

 

25

 

28

 

650

 

10,8

 

24

 

Area di funzionamento 

Allowable oparating region 

350

 

700

 

800 

 

Содержание SE237EO

Страница 1: ... Temps de réponse T90 20 secondi seconds secondes Ripetibilità Repeatability Répétitivité 1 del segnale signal Precisione Accuracy Precision 2 del segnale in aria signal in air du signal en air Deriva a lungo termine Long time drift Dérive à long terme 2 segnale mese signal per month du signal chaque mois 5 sulla vita operativa over Operating Life sur sa vie Temp umidità di funzionamento Operation...

Страница 2: ...secondi il Led giallo si spegne e si accende il Led verde ON che indica il normale funzionamento Dopo questo tempo il sensore è in grado di rilevare il gas ma raggiunge le condizioni di stabilità ottimali dopo circa 15 minuti di funzionamento continuo Funzionamento Normale deve essere acceso il solo Led Verde ON ALLARMI i 3 livelli d allarme possono essere impostati con diverse soglie utilizzando ...

Страница 3: ...e oltre il 30 In questi casi il sensore deve essere sostituito Attenzione i sensori elettrochimici per Ossigeno contengono una piccola quantità di acetato di potassio che è corrosivo Normalmente non avvengono perdite dal sensore questo può essere causato solo da un azione mecca nica violenta o un uso oltre i limiti di funzionamento Il sensore contiene anche piccole quantità di piombo ossido di pio...

Страница 4: ... i puntali del milliamperometro direttamente sui morsetti S e verificare che ci sia 17 4mA circa Applicando il gas al 15 O2 controllare che si raggiunga un valore di circa 136mV ovvero che l uscita in mA diminuisca fino a circa 13 6 mA Poi i valori dopo aver tolto il gas torneranno progressivamente al valore normale in aria Regolazione Fine Uscita in mA Codice Reg Fine F2 F1 F1 F2 questa funzione ...

Страница 5: ...to repair Yellow and Green LED activates FAULT relays activate and 0mA output signal this happens when the Cartridge Sensor is not working First try to perform the procedure of Calibration in Air as described in the section Test and Calibration Calibration in Air finally try to replace a new Cartridge Sensor If the condition is not change it will be necessary to replace the unit and or send it bac...

Страница 6: ... Led relay ALARM1 with the 1 red Led relay ALARM2 with the 2 red Led relay ALARM3 with the 3 red Led At the end all the Led will remain lighted for around 5 seconds then the central returns at the conditions of normal operation It is advisable to perform this operation every 6 12 months according to the use Note this function is not working if the 1 and or the 2 and or the 3 red Led have already t...

Страница 7: ... fication et calibrage en utilisant par codes les touches F1 et F2 CARACTÉRISTIQUES DU GAZ L Oxygène O2 est un gaz incolore inodore légèrement plus lourd que l air sa densité relative à l air est de 1 1 Ce n est pas un gaz inflammable mais étant fortement oxydant il réagit avec les matériaux combustibles et réduc teurs en facilitant leur combustion déterminant ainsi des risques d incendie et d exp...

Страница 8: ...e Tableau 1 en fonction de la section du câble utilisé Dans le cas d alimentation de plusieurs détecteurs en parallèle il est nécessaire de calculer la chute de tension sur les portions communes des câbles Un câble sans écran est normalement utilisé avec 2 conducteurs pour l alimentation les conducteurs pour les sorties relais Dans le cas où l on utilise également le signal de sortie en 4 20 mA il...

Страница 9: ...gnote chaque 8 secondes dans ce cas inter rompre la procédure puis exécutez le contrôle en coupant et en rétablissant l alimentation du détecteur En cas de persistance il sera nécessaire de remplacer et ou renvoyer le détecteur au fournisseur pour réparation Important Durant l opération de étalonnage l appareil portant la sortie S au 0mA L étalonnage doit être exécuté en air propre exclusivement m...

Страница 10: ...rom the 12Vdc power Supply Distance max d installation d un détecteur sous 12Vcc Massima distanza cui può essere installato ogni rivelatore se è alimentato a 24Vcc The maximum distance to install each detector from the 24Vdc power Supply Distance max d installation d un détecteur sous 24Vcc 0 75 mm2 26 Ω km 100 m 300 m 1 mm2 20 Ω km 150 m 400 m 1 5 mm2 14 Ω km 200 m 500 m 2 5 mm2 8 Ω km 400 m 800 ...

Страница 11: ...mento Wiring diagram Schéma TESTmV TP2 TP1 Scheda Uscite Relé Relays Output Board Sortie sur Realis S 12 24V mA 12 24Vdc Alimentazione Power Supply Alimentation Fig 3 Tester di calibrazione Calibration Tester Kit de Calibration F1 F2 Tasti Key Touches TC014 0 3 L min 1 L min Alimentazione Power Supply Alimentation 100 300 400 500 50 0 5 200 Vdc RL Resistenza di carico Load resistor Resistance de c...