background image

 

 

TECHNICAL CHARACTERISTICS 

Electrical parameters 

Value 

Power supply voltage 

13 - 28 Vdc (rated: 24 Vdc) 

Current consumption at startup 

Peak of 22 mA max. for 4 sec., thus 0.76 mA max. 

Current consumption at 24 Vdc 

Relay usage 

Connection to 

conventional zone 

  Normal / in fault 

2.80 mA 

  In Alarm 

12 mA (rated) 

  Calibration / alignment mode 

20 mA 

Status at power-up 

In normal operation after 10 sec. 

“Earth / ground” connection 

None 

Characteristics of the relay contacts 

Alarm and fault: 1 NO or 1 NC, 1 A @ 50 Vdc 

Alarm relays 

Factory: NO (normally open) position 

Fault relay 

Factory: NC (normally closed) position 

 

Dimensions 

Width (mm) 

Height (mm) 

Depth (mm) 

Surface-mounted base 

115 

115 

78 

Flush-mounted base 

115 

115 

68 

Reflector  

104 

104 

 

Mechanical parameters 

Value 

Tightening torque for terminal screws 

0.4 Nm 

Maximum cross-section of wires 

1.5 mm

2

, 1 wire per terminal 

Protection rating: 

  E / R part 

  Flush-mounted base 

 
IP 54 
IP 41 

 

Optical parameters 

Value 

Wavelength 

940 nm 

Operating distance 

3 to 30 m 

Max. E / R corner misalignment 

± 0.35° 

Max. reflector corner misalignment 

± 5° 

Max. E / R corner movement 

± 1.8° 

Viewing angle of indicator 

180° 

Fault threshold 

92% 

Alarm thresholds 

Level 1 = 0.63 dB 

Level 5 = 1.19 dB 

Level 2 = 0.78 dB 

Level 6 = 1.33 dB 

Level 3 = 0.92 dB 

Level 7 = 1.39 dB 

Level 4 = 1.05 dB 

Level 8 = Level 7 

 

Isolator parameters (ICC) 

Features 

Type of short-circuit isolator 

Simple and “controllable” isolator 

Power supply voltage from loop 

V

max

 = 28 Vdc; V

nom

 = 24 Vdc; V

min

 = 13 Vdc 

Maximum current 

I

C max

 = 350 mA; I

S max

 = 1 A; I

L max

 = 100 µA 

Maximum impedance 

Z

C max

 = 8 

 , switch closed 

ICC opening voltage 

V

SO max

 = 7.6 V; V

SO min

 = 6.0 V 

ICC repositioning voltage 

V

SC min

 = 6.0 V; V

SC max

 = 7.6 V 

 

Note on storing the configuration and data: 

The  configuration  data, as  with  all  other  previously  established  data,  is stored  in  a non-volatile  memory, capable  of 
running for at least 5 years at an ambient temperature of 55°C with no external detector power supply. 

Содержание 48BFC000

Страница 1: ...1 OPTICAL BEAM LINEAR SMOKE DETECTOR WITH REFLECTOR 3 30 M 48BFC000 Please read this manual before using the equipment and keep it safe for future reference...

Страница 2: ...with national installation regulations Make sure both the detector and reflector can be accessed for commissioning and maintenance procedures A 2 2 Rules for the installation site The E R and the ref...

Страница 3: ...Securing the reflector 6 Deactivating the laser pointer press button Caution Leave a free area of at least 30 cm around each element installed on the wall A 2 4 Flush mounted base The flush mounted b...

Страница 4: ...ified the point indicated by the laser beam The reflector is secured in 2 steps Step 1 securing the safety reflector support Use screws with a maximum diameter of 4 mm to secure the safety reflector s...

Страница 5: ...2 x 0 5 mm2 cables are recommended for COM COM and TL TL respectively The K terminal is connected by means of a wire from a 2 x 0 5 mm2 cable COMMISSIONING A 4 MAIN STEPS Commissioning takes place by...

Страница 6: ...you press the button to deactivate the laser pointer make sure the detector and reflector are not exposed to direct sunlight Note If the orange light flashes after a succession of green pulses carry o...

Страница 7: ...ection rating E R part Flush mounted base IP 54 IP 41 Optical parameters Value Wavelength 940 nm Operating distance 3 to 30 m Max E R corner misalignment 0 35 Max reflector corner misalignment 5 Max E...

Страница 8: ...one B MAINTENANCE The specific equipment required for servicing the detector is A clean slightly damp cloth for cleaning the E R window and the reflector The alarm test filter to be positioned in fron...

Страница 9: ...9...

Отзывы: