respiratory tract and can cause effects on the central nervous system, eyes and lungs that can be damaged by the 
inhalation of high concentrations. 

OPERATIONAL DESCRIPTION 

The electrochemical sensor is temperature compensated, but is sensitive to extreme humidity variations. 

Preheating

: when powered, the sensor needs a time of preliminary heating of about 60 seconds. During this peri-

od the yellow LED “

FAULT

” flashes. After this period, the yellow LED light off, the green LED “

ON

” illuminates to in-

dicate normal functioning. After this period the unit is able to detect gas even if it attains the optimum stability con-
ditions after about 15 minutes continual functioning.  

Normal operation

: the green LED “

ON

” should be light on. 

ALARMS:

 different alarms levels can be set by Dip-Switch (

see table 2

). 

The 1st° Red LED

 (

ALARM 1

) illuminates when  the Gas concentration  attains 1st alarm level.  And  after about 3 

seconds the “ALARM 1" relay will activate. 

The  2nd  Red  LED

  (

ALARM 2

)  illuminates  when  the  Gas  concentration  attains  2nd  alarm  level  and  after  about  3 

seconds, the “ALARM 2" relay will activate. 

The  3rd  Red  LED

  (

ALARM  3

)  illuminates  when  the  Gas  concentration  attains  3rd  alarm  level  and  after  about  3 

seconds, the “ALARM 3" relay will activate. 

Faults

the instrument signal different kind of failures, as listed below. The Yellow LED illuminates, the "

S

" output 

falls down to 0mA and the “

FAULT

 normally activated relay deactivate. The "

FAULT

" relay, if necessary, can be used 

both to signal remotely an occurred damage and to signal the absence of power to the instrument. 

Yellow LED illuminates each 4 seconds (

with Green LED activate

):

 

this happens when the “

Cartridge Sensor

” has 

overcome  its  theoretical  period  of  life  (2  years  approximately)  and  its  correct  operation  is  no  longer  guaranteed. 
The detector keeps on operating normally but it is necessary to replace, as soon as possible, the “

Cartridge Sen-

sor

” with a new one. The type to be required is described at 

Page1

. The replacement procedure is described in the 

attached manual. 

Yellow  LED  activates,  Green  LED  off  (

FAULT  relays  activate  and  0mA  output  signal

):

 

this  signal  different  kind  of 

faults. 

1)

  The  Dip  Switch  set  up  is  wrong,  please  verify  (

see  Table  2

). 

2)

  The  “

Cartridge  Sensor

”  is  not  working, 

please  replace  with  new  one. 

3)

 

If  a  new

 

Cartridge  Sensor

”  is  installed  or  it  is  not  correctly  connected  or  a  not 

compatible one is mounted. Please check the cartridge connections and compatibility (

see Table 3

) these checks are 

made connecting and disconnecting the device.

 

If the condition does not change, it will be necessary to replace the 

unit and/or send it back to the supplier to repair. 

Yellow and Green LED activates (

FAULT relays activate and 0mA output signal

):

 

this happens when the “

Cartridge 

Sensor

” is not working. First try to perform the procedure of “

Calibration in Air

” as described in the section

 “Test 

and  Calibration  >  Calibration  in  Air”

,  finally  try  to  replace  a  new 

“Cartridge  Sensor

”.  If  the  condition  is  not 

change, it will be necessary to replace the unit and/or send it back to the supplier to repair. 

All LED activate (

FAULT relays activate and >24mA output signal

):

 

this happens  when the “

Cartridge Sensor

”  is not 

working or gas concentration is out of scale (higher than 30%v/v O

2

). If there are not any gas leaks and the condi-

tion is not change, it will be necessary to replace the unit and/or send it back to the supplier to repair. 

INSTALLATION 

The detector must be accurately installed according to the national dispositions in force on the safety of the plants 
and installation of electric devices. 

Detector positioning

:

 The 

Fig. 2

 shows the instrument size. The unit must be positioned vertically with the sensor 

downwards. 

It should be fixed at 1.60 m from the floor (the O

2

 gas is lighter as air). 

Electrical Connection (

see Fig.2

)

: the maximum distance to install each detector from the power supply show in the 

Table 1

.

 If more than one detector is to be powered in parallel, it is necessary to consider the voltage drop across 

the supply cable. Normally use a two wire cable (

not shielded

) for power  the conductors for output relay. 

If 

the output signal is used in mA, please use 3 conductors screened  conductors for relay output. The max 
load resistor is 50 ohm with 12Vdc power supply, while is 400 ohm with 24Vdc power supply (

see Fig.4

). 

Power Supply terminals, on the main board, are plug-in type, it is necessary to extract them to make the connec-
tion. Pay attention when you insert them again, being polarized. The relays terminals, on outputs board, are fixed.

 

The sealed relays are

 

tension free 

SPST (

S

ingle 

P

ole 

S

ingle 

T

hrow)

 

contacts and should be set NO (Normally Open) or 

NC (Normally Closed) by positioning the 4th Dip-Switch (

see Table 3

). With the

 

Dip-Switches from 1 to 3 the concen-

tration for alarm activations is determined. 

Note: Dip-Switch should be set with instrument powered off. Dip-Switch settled in reserved position acti-

vate Fault indications (

see Operational Description > Faults

). 

Important:

 

Once  installation  is  completed,

 

power  up  the  unit,  wait  about 

20÷30  minutes

  and  then  to  adjust  the 

sensor to the environment, 

only if it is necessary

,

 

carry out the 

Calibration in Air 

(

see

 Test and Calibration

).

 

WARNING 

Average life

: The sensitive element used in this detector has an excellent stability in time. In fresh air and in nor-

mal working condition the 

sensor's life is

 

about 2 years

. After this period the yellow LED “

FAULT

” flashes every 4 

seconds, is necessary replacing the “

Cartridge Sensor

”. 

Periodical testing

: we advise to carry out working tests every 6 or 12 months as explained in the chapter “

Tests 

and Calibration

”. 

Note:

 the detector is not able to detect Oxygen gas outside the room where it is installed, neither inside walls nor 

under the floor. 

Содержание 47RTS282EO

Страница 1: ...a Response Time Temps de r ponse T90 20 secondi seconds secondes Ripetibilit Repeatability R p titivit 1 del segnale signal Precisione Accuracy Precision 2 del segnale in aria signal in air du signal...

Страница 2: ...FAULT Dopo circa 60 secondi il Led giallo si spegne e si accende il Led verde ON che indica il normale funzionamento Dopo questo tempo il sensore in grado di rilevare il gas ma raggiunge le condizion...

Страница 3: ...ni di O2 molto elevate oltre il 30 In questi casi il sensore deve essere sostituito Attenzione i sensori elettrochimici per Ossigeno contengono una piccola quantit di acetato di potassio che corrosivo...

Страница 4: ...on i puntali del milliamperometro direttamente sui morsetti S e verificare che ci sia 17 4mA circa Applicando il gas al 15 O2 controllare che si raggiunga un valore di circa 136mV ovvero che l uscita...

Страница 5: ...activate and 0mA output signal this happens when the Cartridge Sensor is not working First try to perform the procedure of Calibration in Air as described in the section Test and Calibration Calibrati...

Страница 6: ...red Led relay ALARM3 with the 3 red Led At the end all the Led will remain lighted for around 5 seconds then the central returns at the conditions of normal operation It is advisable to perform this...

Страница 7: ...er les op rations de v ri fication et calibrage en utilisant par codes les touches F1 et F2 CARACT RISTIQUES DU GAZ L Oxyg ne O2 est un gaz incolore inodore l g rement plus lourd que l air sa densit r...

Страница 8: ...t indi qu e dans le Tableau 1 en fonction de la section du c ble utilis Dans le cas d alimentation de plusieurs d tecteurs en parall le il est n cessaire de calculer la chute de tension sur les portio...

Страница 9: ...squ la fin Durant la proc dure une rare possibilit existe que la LED Jaune clignote chaque 8 secondes dans ce cas inter rompre la proc dure puis ex cutez le contr le en coupant et en r tablissant l al...

Страница 10: ...lla to ogni rivelatore se alimentato a 12Vcc The maximum distance to install each detec tor from the 12Vdc power Supply Distance max d installation d un d tecteur sous 12Vcc Massima distanza cui pu es...

Страница 11: ...a di collegamento Wiring diagram Sch ma TESTmV TP2 TP1 Scheda Uscite Rel Relays Output Board Sortie sur Realis S 12 24V mA 12 24Vdc Alimentazione Power Supply Alimentation Fig 3 Tester di calibrazione...

Отзывы: